Plan Review Notes
Plan Review Notes For Permit 05041760
Permit Number 05041760
Review Stop P
Sequence Number 1
Notes
Date Text
2005-06-07 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 BUILDING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. PLANS SHALL BE ROUTED TO DBPR
 DIVISION OF HOTEL AND RESTURANTS FOR
 REVIEW. MINIMUM OF 2 STAMPED SETS OF
 PLANS SHALL BE SUBMITTED TO THE CITY FOR
 REVIEW WITH 2 PAGE "WORK SHEETS"
 ATTACHED TO EACH SET. SECTION 101.4.7.
 2. SUBMIT CALCULATIONS FOR MINIMUM
 FACILITIES FOR 1ST AND 6TH FLOOR COMMON
 AREAS PER TABLES 1003.2 (BLDG) AND 104.3
 (PLMG). SHOW SQUARE FEET OF EACH COMMON
 AREA. ASSEMBLY AREAS SHALL HAVE POTTY
 PARITY PER SECTION 403.1.1.
 3. GREASE INTERCEPTOR SHALL BE SIZED BY
 RODNEY COMPO, ENVIRONMENTAL COMPLIANCE.
 (561) 837-4074, E-MAIL [email protected],
 OR FAX (561) 659-7458. THE DETERMINATION
 WORKSHEET FROM MR. COMPO SHALL BE
 ATTACHED TO PLANS WHEN RESUBMITTING FOR
 REVIEW.
 4. SHT C-8 CIVIL WATER AND SEWER PLANS.
 NO WATER SERVICE TO THE BUILDING IS
 SHOWN. PLEASE INDICATE WATER SERVICE ON
 PLANS INCLUDING PIPE SIZE, VALVES,
 BACKFLOW ECT.
 5. SHTS A-1.0, & A-6.1,(DETAILS 10 & 11)
 LOUNGE SINK SHALL COMPLY WITH 11-4.24
 AND ALL SUBSECTIONS. SHOW THE FOLLOWING:
 A. HEIGHT 11-4.24.2
 B. KNEE CLEARANCE 11-4.24.3
 C. SINK DEPTH 11-4.24.4
 D. CLEAR FLOOR SPACE 11-4.24.5 SHALL BE
 FORWARD APPROACH, AND SHALL EXTEND A
 MAXIMUM 19" UNDERNEATH THE SINK. CABINET
 DOORS ARE NOT APPROVED, MUST BE "CLEAR"
 FLOOR SPACE.
 E. EXPOSED PIPES & SURFACES 11-4.24.6
 F. FAUCETS 11-4.24.7
 6. SHOW COMPLIANCE WITH SECTIONS
 11-9.1.2, 11-9.1.3, 11-9-1-4, & 11-9.2.3
 INDICATE ROOM NUMBERS FOR EACH
 REQUIREMENT.
 7. SHT A-1.5 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS PER
 SECTIONS 1106 & 1107 AND ALL SUBSECTIONS
 INDICATE THE SQUARE FOOTAGE OF EACH
 AREA, AND SHOW 1/2 AREA OF ALL VERTICAL
 WALLS INCLUDING PARAPETS ADDED TO THE
 SQUARE FOOTAGE OF EACH AREA AS WELL AS
 ANY ROOF AREA DRAINING ON TO THE FOOR
 FROM ABOVE IN THE CALCULATIONS. SHOW THE
 LOCATIONS FOR ALL SECONDARY ROOF DRAINS.
 8. SHT A-6.0 SHOW CLEAR FLOOR SPACE FOR
 LAVS. SECTION 11-4.19.3.
 9. SHT A-6.2 SHOW THE ACCESSIBLE W/C'S
 TO BE 18" OFF THE WALL TO THE CENTERLINE
 OF THE FIXTURE, AS REQUIRED IN FIG. 28.
 10) SHT A-6.2 SHOW THE FOLLOWING FOR THE
 ACCESSIBLE FIXTURES:
 FOR W/C'S
 A. CLEAR FLOOR SPACE. 11-4.16.2
 B. HEIGHT 11-4.16.3 (ONE SHOWS 15")
 C. GRAB BARS 11-4.16.4 (ONE SHOWS 37")
 D. FLUSH CONTROLS 11-4.16.5
 E. DISPENSERS 11-4.16.6
 FOR URINAL
 A. HEIGHT 11-4.18.2
 B. CLEAR FLOOR SPACE 11-4.18.3
 C. FLUSH CONTROLS 11-4.18.4
 FOR LAVS
 A. HEIGHT & CLEARANCES 11-4.19.2
 B. CLEAR FLOOR SPACE 11-4.19.3
 C. EXPOSED PIPES & SURFACES 11-4.19.4
 D. FAUCETS 11-4.19.5
 11. SHT A-8.0 ROOM FINISH SCHEDULE. 1ST
 FLOOR AND 6TH FLOOR TOILET ROOMS. WALLS
 SHALL BE NON-ABSORBENT UP TO 4' ABOVE
 THE FLOOR. EXPLAIN HOW THIS WILL
 ACHIEVED BY PAINTING GWB. SECTION 1204.2
 12. ALL MECH., ELECT., & PLMB. SHEETS.
 EACH SHEET OF PLANS WHICH MUST BE SEALED
 UNDER THE PROVISIONS OF CHAPTER 471
 SHALL BE SEALED, SIGNED AND DATED BY THE
 PROFESSIONAL ENGINEER. 61G15-23.002(1).
 NO DATE AFFIXED TO SEAL/SIGNATURE. -
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME AND LICENSE NUMBER, AS WELL AS THE
 NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. 61G15-23.002(2)
 FAC, & FS 471.025.
 13. SHT P-01 DOMESTIC PUMPS SHALL BE
 LISTED. SUBMIT MANUF. SPECIFICATION
 SHEETS. SECTION 303.4
 14. SHT P-01 170 GAL. SYNCROFLO
 HYDROCUMULATOR TANK HAS NO PIPING TO IT.
 PLEASE INDICATE HOW THIS WILL BE PIPED.
 SECTION 104.2.1.
 15. SHTS P-02A & P-04B 2" EXPRESS DRAIN
 FOR FIRE SPRINKLER SYSTEM TO DRAIN TO
 THE SANT. SYSTEM. SECTION 701.4
 16. SHT P-02A INDICATE SANT. RISER
 NUMBER FOR LINE NEXT TO ST/10 RISER.
 SECTION 104.2.1.
 17. SHT P-02A LINES AT MATCH LINE ABOVE
 BUILDING SANT. DRAIN LINE (GAS, HOT
 WATER ECT.) NOT SHOWN AS CONTINUING ON
 SHT P-02B. PLEASE INDICATE WHERE THESE
 LINES CONTINUE TO RUN, LABEL AND
 IDENTIFY ALL LINES. SECTION 104.2.1.
 18. SHTS P-02A & P-02C 2-WAY CLEANOUTS
 ARE REQUIRED ON THE INLET AND OUTLET OF
 THE GREASE INTERCEPTOR. CITY STANDARD. -
 ALSO A 2-WAY CLEANOUT IS REQUIRED NEAR
 THE JUNCTION OF THE BUILDING DRAIN AND
 THE BUILDING SEWER. SECTION 708.3.
 19. SHT P-02C KITCHEN EQUIPMENT
 CONNECTION NOTES 1 & 4. THE AIR GAP
 SHALL BE TWICE THE DIAMETER OF THE
 EFFECTIVE OPENING OF THE INDIRECT WASTE
 PIPE. SECTION 802.2.1.
 20. SHT P-02C MORE INFORMATION IS
 REQUIRED ON THE "OPEN SITE DRAINS".
 PLEASE INDICATE WHAT TYPE OF FIXTURE
 THIS IS, AND WHAT IS THE PURPOSE FOR
 THIS FIXTURE. SECTION 104.2.1.
 21. SUBMIT A BUILDING DRAIN SANITARY
 RISER DIAGRAM IN ISOMETRIC FORM SHOWING
 ALL PIPE SIZES, CLEANOUTS, VENTS, RISER
 LOCATIONS, AND DRAINAGE FIXTURE UNITS AS
 THEY ACCUMULATE IN THE SYSTEM. SECTIONS
 104.2.1. & 140.3.1.1.
 22. SHT P-02B SANT. BRANCH LINE
 CONNECTING DOWNSTREAM OF RISER P/8.
 PLEASE INDICATE WHAT FIXTURES CONNECT TO
 THIS BRANCH LINE. SECTION 104.2.1.
 23. SHT P-07 WATER HEATER DETAIL. BOTTOM
 FED WATER HEATERS SHALL HAVE A VACUUM
 RELIEF VALVE INSTALLED. SECTION 504.2. -
 ONE WATER HEATER DETAIL INDICATES (3
 REQUIRED) AND THE OTHER DETAIL INDICATES
 (6 REQUIRED). PLEASE CLARIFY. SECTION
 104.2.1.
 24. SHT P-08 ROOFTOP PIPING SUPPORT TO
 COMPLY WITH TABLE 308.5. - INDICATE HOW
 SUPPORT IS ATTACHED TO ROOF AND HOW THE
 SUPPORTS COMPLY WITH 140 MPH WIND LOADS.
 SECTION 104.2.1.
 25. SHT P-10 RISER P/3 DOES NOT REFLECT
 THE FLOOR PLAN AT 6TH FLOOR. SECTION
 104.2.1.
 RISERS P/7 & P7A DOES NOT REFLECT THE
 FLOOR PLAN 6TH FLOOR. SECTION 104.2.1.
 26. SHT P-11 BLDG DRAIN DOES NOT REFLECT
 THE FLOOR PLAN. CLEANOUT IS NOT SHOWN ON
 THE FLOOR PLAN UPSTREAM OF BRANCH LINE
 TO RISER P/2. SECTION 104.2.1.
 26. SHT P-11 RISER P/4 DOES NOT REFLECT
 THE FLOOR PLAN AT 6TH FLOOR. SECTION
 104.2.1.
 27. SHT P-11 PARTIAL SANITARY RISER
 DIAGRAM DOES NOT REFLECT THE FLOOR PLAN.
 F2 ON FLOOR PLAN SHOWN AS F1 ON RISER
 DIAGRAM. PLEASE CORRELATE RISER WITH
 FLOOR PLAN. SECTION 104.2.1.
 28. SHT P-13 RISER DOES NOT REFLECT
 FLOOR PLAN. FLOOR DRAINS UPSTREAM OF
 P/14 SHOWN AS 3" ON FLOOR PLAN AND 4"
 ON THE RISER DIAGRAM. SECTION 104.2.1.
 ALSO PIPE SHALL NOT REDUCE IN THE
 DIRECTION OF FLOW. SECTION 704.2
 29. SHT P-14 THE FOLLOWING CORRECTIONS
 ON THE FOLLOWING RISER REQUIRED:
 A. ST/3 5" MINIMUM ON HORIZONTAL
 B. ST/9 4" MINIMUM ON HORIZONTAL
 C. ST/11 4" MINIMUM ON HORIZONTAL
 D. ST/13 4" MINIMUM ON HORIZONTAL
 E. ST/15 4" MINIMUM ON HORIZONTAL
 30. THE FOLLOWING INFORMATION IS RQUIRED
 FOR GAS PERMIT:
 A. SHT P-08 SUBMIT AN ISOMETRIC DRAWING
 THAT CLEARLY SHOWS ALL CUT SECTIONS OF
 PIPE AND CORRESPONDING LENGTHS PER
 FBC-2001 FUEL GAS CODE.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 C. TYPE OF GAS, (LP OR NATURAL)
 D. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 E. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 GAS CODE SECTION 304. - THIS IS FOR THE
 WATER BOOSTER.
 F. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI. -
 DELEVERY PRESSURE IS USUALLY 11 TO 14
 INCHES OF WATER COLUMN OR 56 INCHES OF
 WATER COLUMN, AND PLANS SHOW 7". PLEASE
 CHECK WITH GAS PROVIDER AND VERIFY THE
 DELIVERY PRESSURE.
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 H. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 I. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 31. ARCHITECTURAL SHEETS, THERE ARE SOME
 SHEETS THAT ARE NOT SEALED, AND MOST
 SHEETS THE SEAL DOES NOT SHOW THE
 INFORMATION REQUIRED BY FAC 61G1-16.002
 AND FS 481.221 - THE TITLE BLOCK IS
 MISSING THE FOLLOWING INFORMATION:
 (2) FIRM LICENSE NUMBER
 SEE FAC 61G1-16.004 & FS 481.2055
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]