| Date |
Text |
| 2005-06-07 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 BUILDING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. PLANS SHALL BE ROUTED TO DBPR |
| | DIVISION OF HOTEL AND RESTURANTS FOR |
| | REVIEW. MINIMUM OF 2 STAMPED SETS OF |
| | PLANS SHALL BE SUBMITTED TO THE CITY FOR |
| | REVIEW WITH 2 PAGE "WORK SHEETS" |
| | ATTACHED TO EACH SET. SECTION 101.4.7. |
| | 2. SUBMIT CALCULATIONS FOR MINIMUM |
| | FACILITIES FOR 1ST AND 6TH FLOOR COMMON |
| | AREAS PER TABLES 1003.2 (BLDG) AND 104.3 |
| | (PLMG). SHOW SQUARE FEET OF EACH COMMON |
| | AREA. ASSEMBLY AREAS SHALL HAVE POTTY |
| | PARITY PER SECTION 403.1.1. |
| | 3. GREASE INTERCEPTOR SHALL BE SIZED BY |
| | RODNEY COMPO, ENVIRONMENTAL COMPLIANCE. |
| | (561) 837-4074, E-MAIL [email protected], |
| | OR FAX (561) 659-7458. THE DETERMINATION |
| | WORKSHEET FROM MR. COMPO SHALL BE |
| | ATTACHED TO PLANS WHEN RESUBMITTING FOR |
| | REVIEW. |
| | 4. SHT C-8 CIVIL WATER AND SEWER PLANS. |
| | NO WATER SERVICE TO THE BUILDING IS |
| | SHOWN. PLEASE INDICATE WATER SERVICE ON |
| | PLANS INCLUDING PIPE SIZE, VALVES, |
| | BACKFLOW ECT. |
| | 5. SHTS A-1.0, & A-6.1,(DETAILS 10 & 11) |
| | LOUNGE SINK SHALL COMPLY WITH 11-4.24 |
| | AND ALL SUBSECTIONS. SHOW THE FOLLOWING: |
| | A. HEIGHT 11-4.24.2 |
| | B. KNEE CLEARANCE 11-4.24.3 |
| | C. SINK DEPTH 11-4.24.4 |
| | D. CLEAR FLOOR SPACE 11-4.24.5 SHALL BE |
| | FORWARD APPROACH, AND SHALL EXTEND A |
| | MAXIMUM 19" UNDERNEATH THE SINK. CABINET |
| | DOORS ARE NOT APPROVED, MUST BE "CLEAR" |
| | FLOOR SPACE. |
| | E. EXPOSED PIPES & SURFACES 11-4.24.6 |
| | F. FAUCETS 11-4.24.7 |
| | 6. SHOW COMPLIANCE WITH SECTIONS |
| | 11-9.1.2, 11-9.1.3, 11-9-1-4, & 11-9.2.3 |
| | INDICATE ROOM NUMBERS FOR EACH |
| | REQUIREMENT. |
| | 7. SHT A-1.5 SUBMIT CALCULATIONS FOR |
| | PRIMARY AND SECONDARY ROOF DRAINS PER |
| | SECTIONS 1106 & 1107 AND ALL SUBSECTIONS |
| | INDICATE THE SQUARE FOOTAGE OF EACH |
| | AREA, AND SHOW 1/2 AREA OF ALL VERTICAL |
| | WALLS INCLUDING PARAPETS ADDED TO THE |
| | SQUARE FOOTAGE OF EACH AREA AS WELL AS |
| | ANY ROOF AREA DRAINING ON TO THE FOOR |
| | FROM ABOVE IN THE CALCULATIONS. SHOW THE |
| | LOCATIONS FOR ALL SECONDARY ROOF DRAINS. |
| | 8. SHT A-6.0 SHOW CLEAR FLOOR SPACE FOR |
| | LAVS. SECTION 11-4.19.3. |
| | 9. SHT A-6.2 SHOW THE ACCESSIBLE W/C'S |
| | TO BE 18" OFF THE WALL TO THE CENTERLINE |
| | OF THE FIXTURE, AS REQUIRED IN FIG. 28. |
| | 10) SHT A-6.2 SHOW THE FOLLOWING FOR THE |
| | ACCESSIBLE FIXTURES: |
| | FOR W/C'S |
| | A. CLEAR FLOOR SPACE. 11-4.16.2 |
| | B. HEIGHT 11-4.16.3 (ONE SHOWS 15") |
| | C. GRAB BARS 11-4.16.4 (ONE SHOWS 37") |
| | D. FLUSH CONTROLS 11-4.16.5 |
| | E. DISPENSERS 11-4.16.6 |
| | FOR URINAL |
| | A. HEIGHT 11-4.18.2 |
| | B. CLEAR FLOOR SPACE 11-4.18.3 |
| | C. FLUSH CONTROLS 11-4.18.4 |
| | FOR LAVS |
| | A. HEIGHT & CLEARANCES 11-4.19.2 |
| | B. CLEAR FLOOR SPACE 11-4.19.3 |
| | C. EXPOSED PIPES & SURFACES 11-4.19.4 |
| | D. FAUCETS 11-4.19.5 |
| | 11. SHT A-8.0 ROOM FINISH SCHEDULE. 1ST |
| | FLOOR AND 6TH FLOOR TOILET ROOMS. WALLS |
| | SHALL BE NON-ABSORBENT UP TO 4' ABOVE |
| | THE FLOOR. EXPLAIN HOW THIS WILL |
| | ACHIEVED BY PAINTING GWB. SECTION 1204.2 |
| | 12. ALL MECH., ELECT., & PLMB. SHEETS. |
| | EACH SHEET OF PLANS WHICH MUST BE SEALED |
| | UNDER THE PROVISIONS OF CHAPTER 471 |
| | SHALL BE SEALED, SIGNED AND DATED BY THE |
| | PROFESSIONAL ENGINEER. 61G15-23.002(1). |
| | NO DATE AFFIXED TO SEAL/SIGNATURE. - |
| | ENGINEERS SHALL LEGIBLY INDICATE THEIR |
| | NAME AND LICENSE NUMBER, AS WELL AS THE |
| | NAME, ADDRESS AND CERTIFICATE OF |
| | AUTHORIZATION NUMBER OF THE ENGINEERING |
| | BUSINESS ON EACH SHEET. 61G15-23.002(2) |
| | FAC, & FS 471.025. |
| | 13. SHT P-01 DOMESTIC PUMPS SHALL BE |
| | LISTED. SUBMIT MANUF. SPECIFICATION |
| | SHEETS. SECTION 303.4 |
| | 14. SHT P-01 170 GAL. SYNCROFLO |
| | HYDROCUMULATOR TANK HAS NO PIPING TO IT. |
| | PLEASE INDICATE HOW THIS WILL BE PIPED. |
| | SECTION 104.2.1. |
| | 15. SHTS P-02A & P-04B 2" EXPRESS DRAIN |
| | FOR FIRE SPRINKLER SYSTEM TO DRAIN TO |
| | THE SANT. SYSTEM. SECTION 701.4 |
| | 16. SHT P-02A INDICATE SANT. RISER |
| | NUMBER FOR LINE NEXT TO ST/10 RISER. |
| | SECTION 104.2.1. |
| | 17. SHT P-02A LINES AT MATCH LINE ABOVE |
| | BUILDING SANT. DRAIN LINE (GAS, HOT |
| | WATER ECT.) NOT SHOWN AS CONTINUING ON |
| | SHT P-02B. PLEASE INDICATE WHERE THESE |
| | LINES CONTINUE TO RUN, LABEL AND |
| | IDENTIFY ALL LINES. SECTION 104.2.1. |
| | 18. SHTS P-02A & P-02C 2-WAY CLEANOUTS |
| | ARE REQUIRED ON THE INLET AND OUTLET OF |
| | THE GREASE INTERCEPTOR. CITY STANDARD. - |
| | ALSO A 2-WAY CLEANOUT IS REQUIRED NEAR |
| | THE JUNCTION OF THE BUILDING DRAIN AND |
| | THE BUILDING SEWER. SECTION 708.3. |
| | 19. SHT P-02C KITCHEN EQUIPMENT |
| | CONNECTION NOTES 1 & 4. THE AIR GAP |
| | SHALL BE TWICE THE DIAMETER OF THE |
| | EFFECTIVE OPENING OF THE INDIRECT WASTE |
| | PIPE. SECTION 802.2.1. |
| | 20. SHT P-02C MORE INFORMATION IS |
| | REQUIRED ON THE "OPEN SITE DRAINS". |
| | PLEASE INDICATE WHAT TYPE OF FIXTURE |
| | THIS IS, AND WHAT IS THE PURPOSE FOR |
| | THIS FIXTURE. SECTION 104.2.1. |
| | 21. SUBMIT A BUILDING DRAIN SANITARY |
| | RISER DIAGRAM IN ISOMETRIC FORM SHOWING |
| | ALL PIPE SIZES, CLEANOUTS, VENTS, RISER |
| | LOCATIONS, AND DRAINAGE FIXTURE UNITS AS |
| | THEY ACCUMULATE IN THE SYSTEM. SECTIONS |
| | 104.2.1. & 140.3.1.1. |
| | 22. SHT P-02B SANT. BRANCH LINE |
| | CONNECTING DOWNSTREAM OF RISER P/8. |
| | PLEASE INDICATE WHAT FIXTURES CONNECT TO |
| | THIS BRANCH LINE. SECTION 104.2.1. |
| | 23. SHT P-07 WATER HEATER DETAIL. BOTTOM |
| | FED WATER HEATERS SHALL HAVE A VACUUM |
| | RELIEF VALVE INSTALLED. SECTION 504.2. - |
| | ONE WATER HEATER DETAIL INDICATES (3 |
| | REQUIRED) AND THE OTHER DETAIL INDICATES |
| | (6 REQUIRED). PLEASE CLARIFY. SECTION |
| | 104.2.1. |
| | 24. SHT P-08 ROOFTOP PIPING SUPPORT TO |
| | COMPLY WITH TABLE 308.5. - INDICATE HOW |
| | SUPPORT IS ATTACHED TO ROOF AND HOW THE |
| | SUPPORTS COMPLY WITH 140 MPH WIND LOADS. |
| | SECTION 104.2.1. |
| | 25. SHT P-10 RISER P/3 DOES NOT REFLECT |
| | THE FLOOR PLAN AT 6TH FLOOR. SECTION |
| | 104.2.1. |
| | RISERS P/7 & P7A DOES NOT REFLECT THE |
| | FLOOR PLAN 6TH FLOOR. SECTION 104.2.1. |
| | 26. SHT P-11 BLDG DRAIN DOES NOT REFLECT |
| | THE FLOOR PLAN. CLEANOUT IS NOT SHOWN ON |
| | THE FLOOR PLAN UPSTREAM OF BRANCH LINE |
| | TO RISER P/2. SECTION 104.2.1. |
| | 26. SHT P-11 RISER P/4 DOES NOT REFLECT |
| | THE FLOOR PLAN AT 6TH FLOOR. SECTION |
| | 104.2.1. |
| | 27. SHT P-11 PARTIAL SANITARY RISER |
| | DIAGRAM DOES NOT REFLECT THE FLOOR PLAN. |
| | F2 ON FLOOR PLAN SHOWN AS F1 ON RISER |
| | DIAGRAM. PLEASE CORRELATE RISER WITH |
| | FLOOR PLAN. SECTION 104.2.1. |
| | 28. SHT P-13 RISER DOES NOT REFLECT |
| | FLOOR PLAN. FLOOR DRAINS UPSTREAM OF |
| | P/14 SHOWN AS 3" ON FLOOR PLAN AND 4" |
| | ON THE RISER DIAGRAM. SECTION 104.2.1. |
| | ALSO PIPE SHALL NOT REDUCE IN THE |
| | DIRECTION OF FLOW. SECTION 704.2 |
| | 29. SHT P-14 THE FOLLOWING CORRECTIONS |
| | ON THE FOLLOWING RISER REQUIRED: |
| | A. ST/3 5" MINIMUM ON HORIZONTAL |
| | B. ST/9 4" MINIMUM ON HORIZONTAL |
| | C. ST/11 4" MINIMUM ON HORIZONTAL |
| | D. ST/13 4" MINIMUM ON HORIZONTAL |
| | E. ST/15 4" MINIMUM ON HORIZONTAL |
| | 30. THE FOLLOWING INFORMATION IS RQUIRED |
| | FOR GAS PERMIT: |
| | A. SHT P-08 SUBMIT AN ISOMETRIC DRAWING |
| | THAT CLEARLY SHOWS ALL CUT SECTIONS OF |
| | PIPE AND CORRESPONDING LENGTHS PER |
| | FBC-2001 FUEL GAS CODE. |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | C. TYPE OF GAS, (LP OR NATURAL) |
| | D. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES (A)(3). |
| | E. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2001 FUEL |
| | GAS CODE SECTION 304. - THIS IS FOR THE |
| | WATER BOOSTER. |
| | F. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2001 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. - |
| | DELEVERY PRESSURE IS USUALLY 11 TO 14 |
| | INCHES OF WATER COLUMN OR 56 INCHES OF |
| | WATER COLUMN, AND PLANS SHOW 7". PLEASE |
| | CHECK WITH GAS PROVIDER AND VERIFY THE |
| | DELIVERY PRESSURE. |
| | G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2001 FUEL GAS CODE SEC 402.2 |
| | H. CLEARLY SHOW THE LOCATION AND CAP- |
| | ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| | OR ASME), THE DISTANCE OF THE TANK FROM |
| | THE BUILDING AND ADJACENT PROPERTY LINES |
| | THE DISTANCE OF THE TANK FROM ALL SOUR- |
| | CES OF IGNITION, OTHER CONTAINERS, BUILD |
| | INGS, AND THE LOCATION OF ANY BUILDING |
| | OPENINGS BELOW THE RELIEF VALVE OF THE |
| | TANK PER NFPA 58, TABLE 3-2.2.2. |
| | I. CLEARLY INDICATE ON THE PLAN IF THE |
| | LP TANK IS ABOVE OR BELOW GROUND, AND |
| | SHOW REQUIRED PROTECTION OF THE TANK AND |
| | APPURTENANCES PER NFPA 58. IF THE TANK |
| | IS BELOW GROUND THE CONTAINER SHALL BE |
| | SECURILY ANCHORED PER NFPA 58 SECTION |
| | 3-2.2.7(H). |
| | 31. ARCHITECTURAL SHEETS, THERE ARE SOME |
| | SHEETS THAT ARE NOT SEALED, AND MOST |
| | SHEETS THE SEAL DOES NOT SHOW THE |
| | INFORMATION REQUIRED BY FAC 61G1-16.002 |
| | AND FS 481.221 - THE TITLE BLOCK IS |
| | MISSING THE FOLLOWING INFORMATION: |
| | (2) FIRM LICENSE NUMBER |
| | SEE FAC 61G1-16.004 & FS 481.2055 |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |