| Date |
Text |
| 2005-06-16 00:00:00 | DENIED: |
| | 1.SUBMITTAL BOOK DOES NOT INCLUDE |
| | SUBMITTAL DATA FOR MECHANICAL EQUIPMENT; |
| | RTU'S, SPLIT SYSTEMS, EXHAUST FANS |
| | DRYERS, ETC. |
| | |
| | 2.PLAN SHEET M-02 FAN SCHEDULE - FAN |
| | #7 &8 ARE INDICATED FOR DRYERS. THE |
| | "REMARK" COLOUM IT INDICATES #4 A |
| | BIRDSCREEN.PER 2001 FBC(M)504.4, |
| | SCREENS SHALL NOT BE INSTALLEDAT DUCT |
| | TERMINATION. |
| | |
| | 3.PLAN SHEET M-03, GUEST LAUNDRY - |
| | 2001 FBC(M)504.6 DOESNOT ALLOW FOR |
| | IN-LINE FANS IN THE DRYER EXHAUST DUCT. |
| | IS THIS APPLICATION PERMITTED BY THE |
| | DRYER MANUFACTURER?COMMERCIAL LAUNDRY |
| | ROOM - 2001 FBC(M) 504.7, EXHAUST FAN |
| | MOTORS SHALL BE LOCATED OUTSIDE THE |
| | AIRSTREAM. IN MULTIPLE INSTALLATIONS THE |
| | FAN SHALL RUN CONTINUOUSLY OR BE |
| | INTERLOCKED TO RUN WHEN ANY INDIVIDUAL |
| | UNIT IS RUNNING. |
| | |
| | 4.PLEASE NOTE, PER 2001 FBC(M)504.2 |
| | CLOTHES DRYER EXHAUST DUCTS SHALL NOTE |
| | PENETRATE OR TERMINATE WITHIN ANY FIRE |
| | BLOCKING OR ANY FIRE RATED ASSEMBLY |
| | UNLESS DUCT IS CONSTRUCTED OF GALVENIZED |
| | OR ALUMINUM AS SPECIFIED IN TABLE 603.3. |
| | |
| | 5.EXHAUST SHALL NOT BE DIRECTED ONTO |
| | WALK-WAYS, OR TERMINATE IN A MANNER THAT |
| | CREATES A NUISANCE. 2001 FBC(M) 401.5.2. |
| | |
| | 6.OUTSIDE AIR INTAKES SHALL BE LOCATED |
| | A MINIMUM OF 10 FT FORM ANY NOXIOUS |
| | CONTAMINANT, PARKING LOTS, AND LOADING |
| | DOCKS.2001 FBC(M)401.5.1 |
| | |
| | 7.PLAN SHEET M-04, CLARIFY LOCATION OF |
| | TW-2.IT APPEARS TO BE IN A CLOSET IN |
| | BEDROOM 1 & INDICATES 18" X 18" LOUVER |
| | DOOR.SHOULD THIS READ GRILLE? |
| | RETURN AIR FROM BEDROOM 2 REQUIRED. |
| | RETURN FROM BEDROOM 2 SHALL BE SIZED IN |
| | ACCORDANCE WITH 2001 FBC(M)601.4. |
| | |
| | 8.PLAN SHEET M-05 & M-03, INDICATE |
| | RETURN AIR PLENUMS IN THE COMMON AREAS. |
| | NO COMBUSTIBLES ALLOWED ABOVE THE |
| | CEILING IN THE RETURN AIR PLENUM, 2001 |
| | FBC(M) 602.2.1. |
| | |
| | 9.PLAN SHEET M-07 NOTE #1, PLEASE NOTE |
| | AUXILIARY DRAIN PAN SHALL HAVE OVERFLOW |
| | ROTECTION.PLEASE INDICATE WHICH METHOD |
| | WILL BE USED AS SPECIFIED IN 307.2.3. |
| | |
| | 10.PLEASE PROVIDE OUSTIDE AIR |
| | CALUCALTIONS FOR ALL AREAS PER 2001 |
| | FBC(M) TABLE 403.3. |
| | |
| | 11.PLEASE CLARIFY SMOKE CONTROL (IF |
| | ANY).PROVIDE SEQUENCE OF OPERATION. |
| | |
| | 12. PROVIDE DETAIL FOR THE CONDESING |
| | UNIT STANDS LOCATED ON THE ROOF. HEIGHT |
| | FROM THE ROOF SURFACE TO THE BOTTOM OF |
| | THE SUPPORT RAIL SHALL BE IN ACCORDANCE |
| | WITH 2001 FBC 1511.7.PROVIDE DETAIL |
| | FOR SECURING UNITS. |
| | |
| | IF YOU HAVE ANY QUESTIONSS, PLEASE |
| | CONTACT PATTY KRAUSS AT (561)805-6719. |
| | |
| | |