2005-06-16 00:00:00DENIED:
 1.SUBMITTAL BOOK DOES NOT INCLUDE
 SUBMITTAL DATA FOR MECHANICAL EQUIPMENT;
 RTU'S, SPLIT SYSTEMS, EXHAUST FANS
 DRYERS, ETC.
  
 2.PLAN SHEET M-02 FAN SCHEDULE - FAN
 #7 &8 ARE INDICATED FOR DRYERS. THE
 "REMARK" COLOUM IT INDICATES #4 A
 BIRDSCREEN.PER 2001 FBC(M)504.4,
 SCREENS SHALL NOT BE INSTALLEDAT DUCT
 TERMINATION.
  
 3.PLAN SHEET M-03, GUEST LAUNDRY -
 2001 FBC(M)504.6 DOESNOT ALLOW FOR
 IN-LINE FANS IN THE DRYER EXHAUST DUCT.
 IS THIS APPLICATION PERMITTED BY THE
 DRYER MANUFACTURER?COMMERCIAL LAUNDRY
 ROOM - 2001 FBC(M) 504.7, EXHAUST FAN
 MOTORS SHALL BE LOCATED OUTSIDE THE
 AIRSTREAM. IN MULTIPLE INSTALLATIONS THE
 FAN SHALL RUN CONTINUOUSLY OR BE
 INTERLOCKED TO RUN WHEN ANY INDIVIDUAL
 UNIT IS RUNNING.
  
 4.PLEASE NOTE, PER 2001 FBC(M)504.2
 CLOTHES DRYER EXHAUST DUCTS SHALL NOTE
 PENETRATE OR TERMINATE WITHIN ANY FIRE
 BLOCKING OR ANY FIRE RATED ASSEMBLY
 UNLESS DUCT IS CONSTRUCTED OF GALVENIZED
 OR ALUMINUM AS SPECIFIED IN TABLE 603.3.
  
 5.EXHAUST SHALL NOT BE DIRECTED ONTO
 WALK-WAYS, OR TERMINATE IN A MANNER THAT
 CREATES A NUISANCE. 2001 FBC(M) 401.5.2.
  
 6.OUTSIDE AIR INTAKES SHALL BE LOCATED
 A MINIMUM OF 10 FT FORM ANY NOXIOUS
 CONTAMINANT, PARKING LOTS, AND LOADING
 DOCKS.2001 FBC(M)401.5.1
  
 7.PLAN SHEET M-04, CLARIFY LOCATION OF
 TW-2.IT APPEARS TO BE IN A CLOSET IN
 BEDROOM 1 & INDICATES 18" X 18" LOUVER
 DOOR.SHOULD THIS READ GRILLE?
 RETURN AIR FROM BEDROOM 2 REQUIRED.
 RETURN FROM BEDROOM 2 SHALL BE SIZED IN
 ACCORDANCE WITH 2001 FBC(M)601.4.
  
 8.PLAN SHEET M-05 & M-03, INDICATE
 RETURN AIR PLENUMS IN THE COMMON AREAS.
 NO COMBUSTIBLES ALLOWED ABOVE THE
 CEILING IN THE RETURN AIR PLENUM, 2001
 FBC(M) 602.2.1.
  
 9.PLAN SHEET M-07 NOTE #1, PLEASE NOTE
 AUXILIARY DRAIN PAN SHALL HAVE OVERFLOW
 ROTECTION.PLEASE INDICATE WHICH METHOD
 WILL BE USED AS SPECIFIED IN 307.2.3.
  
 10.PLEASE PROVIDE OUSTIDE AIR
 CALUCALTIONS FOR ALL AREAS PER 2001
 FBC(M) TABLE 403.3.
  
 11.PLEASE CLARIFY SMOKE CONTROL (IF
 ANY).PROVIDE SEQUENCE OF OPERATION.
  
 12. PROVIDE DETAIL FOR THE CONDESING
 UNIT STANDS LOCATED ON THE ROOF. HEIGHT
 FROM THE ROOF SURFACE TO THE BOTTOM OF
 THE SUPPORT RAIL SHALL BE IN ACCORDANCE
 WITH 2001 FBC 1511.7.PROVIDE DETAIL
 FOR SECURING UNITS.
  
 IF YOU HAVE ANY QUESTIONSS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  
  