| 2005-05-31 00:00:00 | ****DENIED**** |
| | |
| | 1) ALL LIFE SAFETY SHALL BE IN |
| | ACCORDANCE WITH NFPA 101, 2003 EDITION. |
| | |
| | 2) CHAPTER 26 OF NFPA 101 IS REFERENCED |
| | IN REGARDS TO OCCUPANT CLASSIFICATION, |
| | HOWEVER CHAPTER 28 SHOULD BE USED. |
| | |
| | 3) TACTILE SIGNS ARE REQUIRED AT EXITS. |
| | |
| | 4) PLEASE CLARIFY THE OCCUPANT LOAD FOR |
| | THE HAWTHORN ROOM AND EXPLAIN EXITING. |
| | |
| | 5) WHAT IS THE SEPARATION BETWEEN THE |
| | ELECTRIC ROOM AND THE HC SUITE ON THE |
| | FIRST FLOOR? |
| | |
| | 6) SIGNAGE IS REQUIRED WITHIN THE STAIR |
| | ENCLOSURES INDICATING THE TOP, BOTTOM, |
| | FLOOR NUMBER AND ROOF ACCESS. |
| | |
| | 7) IT APPEARS THAT AN ADDITIONAL EXIT |
| | SIGN MAY BE REQUIRED AT THE 6TH FLOOR |
| | CORRIDOR LEADING TO STAIR #1. |
| | |
| | 8) THE DOOR TO THE FOOD SERVICE ROOM |
| | WHEN OPEN, APPEARS TO OBSTRUCT THE |
| | CORRIDOR BY GREATER THAN 1/2 THE WIDTH. |
| | |
| | 9) THE ELEVATOR LOBBIES ABOVE THE LEVEL |
| | OF EXIT DISCHARGE, ARE REQUIRED TO BE |
| | SEPARATED FROM THE REMAINDER OF THE |
| | BUILDING. |
| | |
| | 10) WHAT IMPACT WILL THE CARD READERS |
| | HAVE ON EXITING? |
| | |
| | 11) AN ADDRESS NUMBER AT LEAST 6" IN |
| | HEIGHT AND CONTRASTING TO THE |
| | BACKGROUND, WILL BE REQUIRED ON THE |
| | BUILDING. |
| | |
| | 12) PLEASE PROVIDE THE PRESCRIPTIVE |
| | STRENGTH REQUIREMENTS OF ALL HANDRAILS |
| | AND GUARDRAILS. |
| | |
| | 13) PANIC HARDWARE IS REQUIRED ON DOORS |
| | SERVING AN OCCUPANT LOAD OF MORE THAT |
| | 100 PERSONS. |
| | |
| | 14) SEPARATE SHOP DRAWINGS AND PERMITS |
| | ARE REQUIRED FOR THE FIRE SPRINKLER AND |
| | FIRE ALARM SYSTEMS. |
| | |
| | 15) NEW FIRE ALARM SYSTEMS SUPERVISING A |
| | SPRINKLER SYSTEM SHALL BE MONITORED BY |
| | UL CERTIFIED CENTRAL STATION SERVICE. |
| | |
| | 16) A CHAIN AND LOCK SHALL BE PROVIDED |
| | ON THE DOUBLE CHECK DETECTOR ASSEMBLY IN |
| | ADDITION TO ELECTRONIC SUPERVISION. |
| | |
| | 17) PLEASE SEE ELECTRICAL COMMENTS IN |
| | REGARDS TO THE FIRE PUMP REQUIREMENTS. |
| | |
| | 18) SMOKE DETECTORS WIRED TO THE FIRE |
| | ALARM SYSTEM ARE REQUIRED IN THE |
| | CORRIDORS AND OTHER COMMON AREAS. SINGLE |
| | STATION SMOKE DETECTORS ARE REQUIRED IN |
| | LIVING UNITS. |
| | |
| | 19) DUCT SMOKE DETECTORS WHERE PROVIDED, |
| | ARE TO MEET LOCAL REQUIREMENTS OF |
| | INITIATING A GENERAL FIRE ALARM, AND NOT |
| | SUPERVISORY SIGNAL. |
| | |
| | 20) TEMPORARY STANDPIPES SHALL BE |
| | PROVIDED WHEN THE BUILDING REACHES 3 |
| | STORIES OR 30' IN HEIGHT. |
| | |
| | 21) PLEASE ILLUSTRATE IF ELEVATORS ARE |
| | STRETCHER ACCESSIBLE. |
| | |
| | 22) A KNOX BOX WILL BE REQUIRED NEAR THE |
| | FRONT ENTRANCE. |
| | |
| | 23) LOCKING KNOX BOX CAPS SHALL BE |
| | PROVIDED FOR THE FIRE DEPARTMENT |
| | CONNECTION. |
| | |
| | 24) FIRE DEPARTMENT CONNECTION SHALL BE |
| | LOCATED NO FURTHER THAN 150' FROM THE |
| | CLOSEST FIRE HYDRANT. |
| | |
| | |
| | MIKE WENNERGREN, A/CAPTAIN |
| | WPBFR(561) 835-2951 OR 805-6722 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |