Plan Review Notes
Plan Review Notes For Permit 05041760
Permit Number 05041760
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2005-05-31 00:00:00****DENIED****
  
 1) ALL LIFE SAFETY SHALL BE IN
 ACCORDANCE WITH NFPA 101, 2003 EDITION.
  
 2) CHAPTER 26 OF NFPA 101 IS REFERENCED
 IN REGARDS TO OCCUPANT CLASSIFICATION,
 HOWEVER CHAPTER 28 SHOULD BE USED.
  
 3) TACTILE SIGNS ARE REQUIRED AT EXITS.
  
 4) PLEASE CLARIFY THE OCCUPANT LOAD FOR
 THE HAWTHORN ROOM AND EXPLAIN EXITING.
  
 5) WHAT IS THE SEPARATION BETWEEN THE
 ELECTRIC ROOM AND THE HC SUITE ON THE
 FIRST FLOOR?
  
 6) SIGNAGE IS REQUIRED WITHIN THE STAIR
 ENCLOSURES INDICATING THE TOP, BOTTOM,
 FLOOR NUMBER AND ROOF ACCESS.
  
 7) IT APPEARS THAT AN ADDITIONAL EXIT
 SIGN MAY BE REQUIRED AT THE 6TH FLOOR
 CORRIDOR LEADING TO STAIR #1.
  
 8) THE DOOR TO THE FOOD SERVICE ROOM
 WHEN OPEN, APPEARS TO OBSTRUCT THE
 CORRIDOR BY GREATER THAN 1/2 THE WIDTH.
  
 9) THE ELEVATOR LOBBIES ABOVE THE LEVEL
 OF EXIT DISCHARGE, ARE REQUIRED TO BE
 SEPARATED FROM THE REMAINDER OF THE
 BUILDING.
  
 10) WHAT IMPACT WILL THE CARD READERS
 HAVE ON EXITING?
  
 11) AN ADDRESS NUMBER AT LEAST 6" IN
 HEIGHT AND CONTRASTING TO THE
 BACKGROUND, WILL BE REQUIRED ON THE
 BUILDING.
  
 12) PLEASE PROVIDE THE PRESCRIPTIVE
 STRENGTH REQUIREMENTS OF ALL HANDRAILS
 AND GUARDRAILS.
  
 13) PANIC HARDWARE IS REQUIRED ON DOORS
 SERVING AN OCCUPANT LOAD OF MORE THAT
 100 PERSONS.
  
 14) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR THE FIRE SPRINKLER AND
 FIRE ALARM SYSTEMS.
  
 15) NEW FIRE ALARM SYSTEMS SUPERVISING A
 SPRINKLER SYSTEM SHALL BE MONITORED BY
 UL CERTIFIED CENTRAL STATION SERVICE.
  
 16) A CHAIN AND LOCK SHALL BE PROVIDED
 ON THE DOUBLE CHECK DETECTOR ASSEMBLY IN
 ADDITION TO ELECTRONIC SUPERVISION.
  
 17) PLEASE SEE ELECTRICAL COMMENTS IN
 REGARDS TO THE FIRE PUMP REQUIREMENTS.
  
 18) SMOKE DETECTORS WIRED TO THE FIRE
 ALARM SYSTEM ARE REQUIRED IN THE
 CORRIDORS AND OTHER COMMON AREAS. SINGLE
 STATION SMOKE DETECTORS ARE REQUIRED IN
 LIVING UNITS.
  
 19) DUCT SMOKE DETECTORS WHERE PROVIDED,
 ARE TO MEET LOCAL REQUIREMENTS OF
 INITIATING A GENERAL FIRE ALARM, AND NOT
 SUPERVISORY SIGNAL.
  
 20) TEMPORARY STANDPIPES SHALL BE
 PROVIDED WHEN THE BUILDING REACHES 3
 STORIES OR 30' IN HEIGHT.
  
 21) PLEASE ILLUSTRATE IF ELEVATORS ARE
 STRETCHER ACCESSIBLE.
  
 22) A KNOX BOX WILL BE REQUIRED NEAR THE
 FRONT ENTRANCE.
  
 23) LOCKING KNOX BOX CAPS SHALL BE
 PROVIDED FOR THE FIRE DEPARTMENT
 CONNECTION.
  
 24) FIRE DEPARTMENT CONNECTION SHALL BE
 LOCATED NO FURTHER THAN 150' FROM THE
 CLOSEST FIRE HYDRANT.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 835-2951 OR 805-6722
  
  
  
  
  
  
  
  
  
  