| 2005-05-09 00:00:00 | ********* UNSAT ********* |
| | |
| | HAWTHORNE SUITES 6- STORY HOTEL |
| | |
| | 1)NOTE: PLEASE SEE MISSING LICENSE |
| | INFORMATIONREQUIRED ON TITLE BLOCKS |
| | PER FAC 61G1-16.004 FOR ARCHITECT'S AND |
| | ARCHITECTUAL FIRMS. PLEASE ALSO SEE FAC |
| | 61G15-23.002 FOR ENGINEERS AND |
| | ENGINEERING FIRMS. |
| | PLEASE SEE FS 481.219 AND FS 471.023. |
| | |
| | 2)NOTE: PLEASE SEE LS 101 5-9 FOR |
| | CIRCUITING OF EM LIGHTING. PLEASE SEE |
| | STAIRS AND HALL WILL REQUIRE TWO CIRUITS |
| | FROM EM PANEL OR BATTERY BACK-UP |
| | FIXTURES WILL BE REQUIRED. |
| | |
| | 3)NOTE: PLEASE VERIFY EM LTS REQUIRED IN |
| | ELEVATOR EQUIPMENT RMS AND ELECTRICAL |
| | RMS. LS 101 5-9 |
| | |
| | 4)NOTE: PLEASE SEE NOTE #28 ON |
| | ELECTRICAL EQUIPMENT SCHEDULE. PLEASE |
| | SEE 695.4B1, THE OVERCURRENT PROTECTIVE |
| | DEVICE(S) SHALL BE SELECTED OR SET TO |
| | CARRY INDEFINITELY THE SUM OF THE |
| | LOCKED-ROTOR CURRENT OF THE FIRE PUMP |
| | MOTOR(S) AND THE PRESSURE MAINTENANCE |
| | PUMP MOTOR(S) AND THE FULL-LOAD CURRENT |
| | OF THE ASSOCIATED FIRE PUMP ACCESSORY |
| | EQUIPMENT WHEN CONNECTED TO THIS POWER |
| | SUPPLY. PLEASE SEE 300A IS SHOWN FOR |
| | LOCKED ROTOR EXCEEDING. |
| | PLEASE ALSO SEE LOCATION OF FIRE PUMP |
| | DISCONNECT/ SERVICE MEANS SHALL BE |
| | REMOTE FROM MAIN ELECTRICAL SERVICE. |
| | PLEASE SEE NEC 2002 695.3 COMMENTARY |
| | THE POWER SOURCE FOR AN ELECTRIC |
| | MOTOR-DRIVEN FIRE PUMP MUST BE RELIABLE |
| | AND HAVE ADEQUATE CAPACITY TO CARRY THE |
| | LOCKED-ROTOR CURRENTS OF THE FIRE PUMP |
| | MOTOR AND ACCESSORY EQUIPMENT. THESE TWO |
| | MAIN REQUIREMENTS ENSURE THAT THE FIRE |
| | PUMP WILL OPERATE IN THE EVENT OF A FIRE |
| | WITHOUT BEING ACCIDENTALLY DISCONNECTED |
| | AND THAT THE FIRE PUMP WILL CONTINUE TO |
| | OPERATE UNTIL THE FIRE IS EXTINGUISHED, |
| | THE FIRE PUMP IS PURPOSELY SHUT DOWN, OR |
| | THE PUMP ITSELF IS DESTROYED. |
| | PLEASE SEE FOLLOWING COMMENTS FOR |
| | REQUESTED INFORAMTION INCLUDING FIRE |
| | PUMP INFORMATION. |
| | PLEASE SEE FIRE PUMP IS SHOWN HAVING TWO |
| | FEEDS FROM THE MAIN SWITCH BOARD?? |
| | |
| | 5)NOTE: PLEASE SEE ELECTRICAL PANELS / |
| | OCP NOT PERMITTED IN STORAGE AREAS AND |
| | AREAS WITH EASILY IGNITIBLE MATERIALS. |
| | PLEASE SEE 110.26,408.7 240.24D |
| | PLEASE SEE THESE AREAS SHALL BE |
| | DEDICATED TO ELECTRICAL EQUIPMENT. |
| | |
| | 6)NOTE:PLEASE SEE DISCONNECTING MEANS |
| | REQUIRED FOR FEEDS FROM GENERATOR TO BE |
| | LOCATED AT MAIN BLDG/ ELECTRICAL RMS. |
| | PLEASE SEE 225.31-36. |
| | |
| | 7)NOTE: PLEASE SEE GENERATOR APPEARS TO |
| | BE A SEPARATELY DERIVED SYSTEM. PLEASE |
| | SEE NOTES TO ELECTRICAL RISER DIAGRAM |
| | APPEARS TO SHOW TRANSFER SWITCH(S) AS |
| | 4-POLE?? |
| | PLEASE SEE 250.30 FOR SYSTEM SEPARATELY |
| | DERIVED. |
| | PLEASE SEE ALSO SEE 250.24,250.6 FOR |
| | GROUNDING/EQUIPMENT GROUNDING. |
| | |
| | 8)NOTE: PLEASE SEE NOTES TO RISER |
| | DIAGRAM #15 AND #16 ARE LEFT BLANK? |
| | HOWEVER, PLEASE SEE THESE #'S ARE USED |
| | ON RISER. |
| | |
| | 9)NOTE: PLEASE SEE FIRE PUMP DISC IS |
| | SHOWN BEING CONNECTED TO MAIN SERVICE |
| | EQUIPMENT. PLEASE SEE 695.4 THIS IS NOT |
| | PERMITTED. FIRE PUMP DISCONNECTING MEANS |
| | SHALL BE DIRECTLY CONNECTED TO UTILITY |
| | SERVICE. FPL. |
| | |
| | 10)NOTE: PLEASE VERIFY OF MSB HAS A MCB |
| | WITH A MANUAL MEANS OF DISCONNECT |
| | LOCATED ON THE OUTSIDE OF EQUIPMENT. |
| | PLEASE SEE 230.76,230.79 |
| | |
| | 11)NOTE: PLEASE CORRELATE OCP SHOWN ON |
| | MSWBD WITH RATINGS OF PANELS. PLEASE SEE |
| | SOME PANELS ARE SHOWN WITH 400A OCP AND |
| | PANELS ARE RATED AT 225A'S. |
| | PLEASE SEE 100A OCP FEEDING PANELS RATED |
| | AT 400A'S. PLEASE SEE THIS IS OK, |
| | HOWEVER ITEMS ON PANEL APPEAR TO HAVE |
| | LOAD EXCEEDING THE 100'S. |
| | THIS CAN NOT BE VERIFIED AT THIS TIME |
| | DUE TO LOAD CALCS NOT BEING SHOWN ON |
| | EACH PANEL. |
| | |
| | 12)NOTE: PLEASE SEE 250.104 FOR OTHER |
| | METAL PIPES REQUIRED. (FIRE PUMP) ETC. |
| | |
| | 13)NOTE: PLEASE PROVIDE LOAD ON EACH |
| | PANEL SCHEDULE PER NEC 220,215.5 |
| | |
| | 14)NOTE: PLEASE SHOW ALL CONTINUOUS |
| | LOADS AND LARGEST MOTORS LOADS @ 125%. |
| | PLEASE SEE LIGHTING ETC. 215.3,230.42 |
| | ETC. |
| | |
| | 15)NOTE: PLEASE SEE NOE FEEDERS |
| | SHOWN/NOTED FOR PD1. 215.5,310.16,240.4 |
| | |
| | 16)NOTE: PLEASE SEE NO PANEL SCHEDULE |
| | WAS PROVIDED FOR PANEL "PP". |
| | 215.5 |
| | |
| | 17)NOTE: PLEASE SEE PANEL H3P IS ALSO |
| | SHOWN AS HP3? |
| | PLEASE CORRELATE. |
| | |
| | 18)NOTE: PLEASE SEE FIRE PUMP IS NOT |
| | SHOWN BEING FED FROM THE GENERATOR? |
| | PLEASE SEE TWO MEANS OF POWER SHALL BE |
| | SUPPLIED FOR BLDG'S EXCEEDING |
| | 75'/HIGH-RISE. IF BLDG DOES NOT EXCEED |
| | 75', A DIRECT CONNECTION TO FPL MAY BE |
| | ACCEAPTED AS A RELIABLE SOURCE. |
| | |
| | 19)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| | PLANS AND CORRELATE WITH PANEL |
| | SCHEDULES. PLEASE ALSO SEE TYPICAL |
| | SUITES SHALL REQUIRE THIS ALSO. |
| | |
| | 20)NOTE: PLEASE SEE NOTE #28 ON |
| | EQUIPMENT SCHEDULE MENTIONS THAT |
| | PLUMBING CONTRACTOR IS TO SUPPLY AND |
| | INSTALL FIRE PUMP, FIRE PUMP |
| | CONTROLLER/DISCONNECT ETC. |
| | PLEASE SEE STATE OF FLORIDA ECLB SCOPE |
| | OF WORK PERMITTED UNDER PLUMB |
| | CONTRACTORSA LICENSE DOES NOT PERMIT PC, |
| | TO INSTALL ELECTRICAL EQUIPMENT. PELASE |
| | ADJUST NOTES. |
| | |
| | 21)NOTE: PLEASE SEE NUMEROUS PANEL |
| | SCHEDULES WHICH INDICATE 30A OCP ON #12 |
| | AWG? |
| | PLEASE SEE 310.16 AND 240.4 FOR MIN |
| | SIZING REQUIRED. |
| | |
| | 22)NOTE: PLEASE SEE WIND LOADING IS |
| | REQUIRED FOR SITE LIGHTING POLES AND |
| | FIXTURES. THIS IS REQUIRED AT THIS TIME |
| | IF SHOWN ON PLANS. |
| | WIND LOADING IS @ 140MPH PER FBC. |
| | |
| | 23)NOTE: : PLEASE SEE EEP IS BEING FED |
| | WITH A 100A OCP FROM GEN? HOWEVER THIS |
| | IS BEING FED WITH 400A OCP FROM MSWBD? |
| | |
| | 24)NOTE: PLEASE SEE NOTES TO RISER |
| | DIAGRAM MENTIONS 9-4" CONDUITS TO MAINS, |
| | HOWEVER CONDUCTORS FOR THESE CONDUITS |
| | COULD NOT BE LOCATED? |
| | PLEASE SEE 240.4,310.16 |
| | 215.5 |
| | |
| | 25)NOTE: PLEASE PROVIDE ALL MANUFACTURE |
| | SPEC/CUT SHEETS FOR FIRE PUMP, FIRE PUMP |
| | CONTROLLER, ATS'S SWITCHES, GENERATOR |
| | ETC. PLEASE ALSO PROVIDE INFORMATION FOR |
| | GEN. PRIME MOVER. IF A SUB-BASE FUEL |
| | TANK, PLEASE PROVIDE MANUFACT SHEETS. |
| | |
| | 26)NOTE: PLEASE SEE NEC 2002 210.8B3 FOR |
| | GFI PROTECTION REQUIRED IN KITCHEN/ |
| | SERVING AREAS. PLEASE ALSO SEE EMPLOYEE |
| | KITCHEN. |
| | |
| | 27)NOTE: PLEASE SEE POSSIBLE COMMENTS |
| | FROM OTHER REVIEWER(S) WHICH MAY HAVE AN |
| | AFFECT ON ELECTRICAL PLANS. |
| | |
| | 28)NOTE: PLEASE SEE DUE TO MISSING |
| | INFORMATION A COMPLETE REVIEW FOR CODE |
| | COMPLIANCE CAN NOT BE DONE AT THIS TIME. |
| | PLEASE BE SURE TO PROVIDE ALL |
| | INFORMATION AS REQUESTED ABOVE. |
| | |
| | ***PLEASE BE SURE TO REMOVE OLD/VOIDED |
| | SHEETS FROM SETS AND ONLY INSERT NEW |
| | REVISED SHEETS INTO THREE COMPLETE SETS |
| | FOR REVIEW AND STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| 2005-05-06 00:00:00 | NOTES TO FOLLOW UPON COMPLETION OF |
| | REVIEW. |
| | PLANS WILL BE IN THE FAILED STATUS ONCE |
| | THESE NOTES ARE COMPLETE. |
| | 5/6/05 |