| 2005-06-08 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 05041760 |
| | ADD: XXX W. EXECUTIVE CENTER DR. |
| | (74-43-43-20-00-000-3010) |
| | CONT: THE WEITZ CO. |
| | TEL: (561)686-5511 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) ADDRESS TO BE DETERMINED BY CITY MIS |
| | DEPARTMENT, JOHN HIGGINS 822-1239. |
| | |
| | 2) PERMIT APPLICATION CORRECT THE PCN TO |
| | (74-43-43-20-00-000-3010) OR PROVIDE |
| | ADDITIONAL INFORMATION. |
| | |
| | 3) LOW VALUE, CALCULATED VALUE IS: |
| | $9,907,170.00 SEE ADDITIONAL FEES. |
| | |
| | 4) FL S. S. 553.71(7) " THRESHOLD |
| | BUILDING" MEANING ANY BUILDING WHICH IS |
| | GREATER THAN (3) STORIES OR 50 FT IN |
| | HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN |
| | CY CLASSIFICATION AS DEINED IN THE |
| | FLORIDA BUILDING CODE WHICH EXCEEDS |
| | 5,000 SQ FT IN AREA AND AN OCCUPANT |
| | CONTENT OF GREATER THAN 500 PERSONS. |
| | 105.13.1 THE ENFORCING AGENCY SHALL |
| | REQUIRE A SPECIAL INSPECTOR TO PERFORM |
| | SRUCTURAL INSPECTIONS ON A THRESHOLD |
| | BUILDING PURSUANT TO A STRUCTURAL INSPEC |
| | TION PLAN PREPARED BY THE ENGINEER OF |
| | RECORD. THE STRUCTURAL INSPECTION PLAN |
| | MUST BE SUBMITTED TO THE ENFORCING AGEN- |
| | CY PRIOR TO THE ISSUANCE OF A BUILDING |
| | PERMIT FOR THE CONSTRUCTION OF A THRESH- |
| | OLD BUILDING. THE PURPOSE OF THE SRUCTUR |
| | AL INSPECTION PLAN IS TO PROVIDE SPECIF- |
| | IC INSPECTION PROCEDURES AND SCHEDULES |
| | SO THAT THE BUILDING CAN BE ADEQUATELY |
| | INSPECTED FOR COMPLIANCE WITH THE |
| | PERMITTED DOCUMENTS. |
| | S-7 SHORING NOTES, SHORING TO BE SET |
| | BY CONTRACTOR BUT THE THRESHOLD |
| | INSPECTOR TO SIGN OFF FOR APPROVAL. |
| | |
| | 5) WPB AMENDMENT 105.13.6. W.P.B. |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | REQUEST FOR THRESHOLD BUILDINGS A |
| | SPECIAL INSPECTOR AS REQUIRED BY S. |
| | 553.79(5) FLORIDA STATUTES TO THE MIN- |
| | IMUM INSPECTIONS REQUIRED BY THIS CODE. |
| | CONTACT HAROLD PISKURA MANAGER OF THE |
| | SPECIAL INSPECTOR PROGRAM AT (561) |
| | 805-6711 FOR FURTHER INFORMATION BEFORE |
| | THE PERMIT MAY BE ISSUED. |
| | |
| | 6) W.P.B. AMENDMENT 105.13.4.4 ALL PLANS |
| | FOR THE BUILDING WHICH ARE REQUIRED TO |
| | BE SIGNED AND SEALED BY THE ARCHITECT OR |
| | ENGINEER OF RECORD CONTAIN A STATEMENT |
| | THAT, TO THE BEST OF THE ARCHITECT'S OR |
| | ENGINEER'S KNOWLEDGE, THE PLANS AND |
| | SPECIFICATIONS COMPLY WITH THE |
| | APPLICABLE FIRE-SAFETY STANDARDS AS |
| | DETERMINED BY THE LOCAL AUTHORITY IN |
| | ACCORDANCE WITH THIS SECTION AND 633 |
| | FLORIDA STATUTE. |
| | |
| | 7) 903.8.2 FLOR ST STATUTE 553.895(2) |
| | ALL RESIDENTIAL BUILD. 3 OR MORE STORIES |
| | TALL WHETHER DESIGNATED AS TOWNHOUSE, |
| | CONDOMINIUMS, "APARTMENT HOUSES, |
| | TENEMENTS, GARDEN APARTMENTS OR BY ANY |
| | OTHER NAME SHALL BE SUPPLIED BY FIRE |
| | SPRINKLERS MEETING NFPA 101. |
| | |
| | 8) FL BLD CODE 1804.2.2 QUESTIONABLE |
| | SOILS: |
| | A) THE REPORT SUBMITTED DOES HAVE A |
| | RAISED SEAL BUT THE SIGNATURE IS COPIED. |
| | B) TEST BORING SHEETS COPIED NOT SIGNED |
| | OR SEALED. |
| | PLANS, SPECIFICATIONS,REPORTS OR |
| | OTHER DOCUMENTS PREPARED BY THE DESIGN |
| | PROFESSIONAL AND BEING FILED FOR PUBLIC |
| | RECORD SHALL HAVE THE SIGNATURE AND |
| | SEAL OF THE DESIGN PROFESSIONAL AFFIXED |
| | TO THE DOCUMENT. |
| | FL STATE STAT: 61G15-23.002 ENGINEERS |
| | FL ATATE STAT: 61G16.003 ARCHITECTS |
| | |
| | 9) SURVEY OR SITE PLAN WITH THE |
| | FOOTPRINT LOCATED ON PROPERTY,WITH |
| | DIMENSIONS TO THE PROPERTY LINES, |
| | TABLE 600,% OF ALLOWABLE OPENINGS. |
| | |
| | 10) BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 11) HANSON PROFESSIONAL SERVICES TO |
| | COMPLY WITH CERTIFICATE OF AUTHORIZATION |
| | NUMBER TO BE ON PLANS, THE ADDRESS |
| | LISTED WITH THE STATE OF FL IS |
| | SPRINGFIELD, ILL. 481.219 F.S. |
| | CERTIFICATE OF AUTHORIZATION.THE TITLE |
| | BLOCK FOR ANY SHEET BEARING THE NAME OF |
| | AN ARCHITECT PRACTICING UNDER A |
| | FICTITIOUS NAME, A CORPORATION, OR A |
| | PARTNERSHIP, OFFERING ARCHITECTURAL |
| | SERVICES, SHALL INCLUDE THE CERTIFICATE |
| | OF AUTHORIZATION NUMBER. |
| | |
| | 12)A-0.1 CONSTRUCTION TYPE INDICATES THE |
| | BUILDING TO BE A TYPE IV, UNPROTECTED, |
| | FULLY SPRINKLERED STRUCTURE, HOWEVER |
| | SHEET A-3.0 INDICATES TOP OF BUILDING TO |
| | BE 71.66' WITH 6 STORIES. THIS IS IN |
| | EXCESS OF THE ALLOWABLE 55' AND 5 |
| | STORIES ALLOWED UNDER TABLE 500. |
| | FOOTNOTE "H" DOES NOT ALLOW FOR A STORY |
| | INCREASE.THIS IS A TYPE II |
| | CONSTRUCTION. SEE TABLE 500 AND 604. |
| | |
| | 13A) PROVIDE: 11-4.1.2(1) AT LEAST ONE |
| | ACCESSIBLE ROUTE COMPLYING WITH 11-4.3 |
| | SHALL PROVIDED WITHIN THE BOUNDARY OF |
| | THE SITE FROM PUBLIC TRANSPORTATION |
| | STOPS, ACCESSIBLE PARKING SPACES, |
| | PASSENGER LOADING ZONES IF PROVIDED, AND |
| | PUBLIC STREETS OR SIDEWALKS, TO AN |
| | ACCESSIBLE BUILDING ENTRANCE. |
| | |
| | 13B) PROVIDE: 11-4.1.3(1) AT LEAST ONE |
| | ACCESSIBLE ROUTE COMPLYING WITH 11-4.3 |
| | SHALL CONNECT ACCESSIBLE BUILDING OR |
| | FACILITY ENETRANCES WITH ALL ACCESSIBLE |
| | SPACES AND ELEMENTS WITHIN THE BUILDING |
| | OR FACILITY. |
| | |
| | 14)11-4.6.2 LOCATION. ACCESSIBLE PARKING |
| | SPACES SERVING A PARTICULARBUILDING |
| | SHALL BE LOCATED ON THE SHORTEST SAFELY |
| | ACCESSIBLE ROUTE OFTRAVEL FROM |
| | ADJACENT PARKING TO AN ACCESSIBLE |
| | ENTRANCE.IN PARKINGFACILITIES THAT |
| | DO NOT SERVE A PARTICULAR BUILDING, |
| | ACCESSIBLE PARKINGSHALL BE LOCATED ON |
| | THE SHORTEST ACCESSIBLE ROUTE OF TRAVEL |
| | TO ANACCESSIBLE PEDESTRIAN ENTRANCE |
| | OF THE PARKING FACILITY.IN BUILDINGS |
| | WITHMULTIPLE ACCESSIBLE ENTRANCES |
| | WITH ADJACENT PARKING, ACCESSIBLE |
| | PARKING SPACES SHALL BE DISPERSED AND |
| | LOCATED CLOSEST TO THE ACCESSIBLE |
| | ENTRANCES. EACH PARKING SPACE MUST BE NO |
| | LESS THAN 12 FEET WIDE. |
| | |
| | 15) PROVIDE COMPLIANCE WITH HEAD ROOM |
| | BENEATH STAIRS- A BARRIEER TO WARN BLIND |
| | OR VISUALLY IMPAIRED PERSONS SHALL BE |
| | PROVIDED.11-4.4.2.SEE SHEET A-7.0 . |
| | |
| | 16A) 11-9.1.2 PLANS INDICATE 120 |
| | SLEEPING UNITS, 11-9.1.2 REQUIRES 2 |
| | ROOMS WITH ROLL IN SHOWERS, PROVIDE |
| | COMPLIANCE. |
| | |
| | 16B) FL S. S. 509 A NUMBER OF ROOMS |
| | EQUALING AT LEAST 5% OF THE GUEST ROOMS |
| | MINUS THE NUMBER OF "ACCESSIBLE ROOMS" |
| | REQUIRED BY THE TABLE IN 11-9.1.2 SHALL |
| | PROVIDE THE ADDITIOINAL SPECIAL |
| | ACCESSIBILTY FEATURES OF 11-9.2.3 |
| | 11-9.2.3 HOTEL, MOTEL AND CONDOMINIUM |
| | SPECIAL ACCESSIBILITY FEATURE. |
| | NOTHING IN THIS SECTION SHALL BE |
| | CONSTRUED AS RELIEVING THE OWNER OF THE |
| | RESPONSIBILITY OF PROVIDING ACCESSIBLE |
| | ROOMS IN CONFORMANCE WITH 11-9.1 |
| | 11-9.5 OF THE CODE. |
| | |
| | IN ALL BUILDINGS, STRUCTURES AND |
| | FACILITIES LICENSED AS A HOTEL, MOTEL OR |
| | RESORT CONDOMINIUM PURSUANT TO CHAPTER |
| | 509, FLORIDA STATUTES, A NUMBER |
| | OF ROOMS EQUALING AT LEAST 5 PERCENT |
| | OF THE GUEST ROOMS MINUS THE NUMBER |
| | OF ACCESSIBLE ROOMS REQUIRED BY THE |
| | TABLE IN 11-9.1.2 SHALL PROVIDE THE |
| | FOLLOWING ADDITIONAL SPECIAL |
| | ACCESSIBILITY FEATURES: |
| | |
| | 11-9.2.3(1) GRAB RAILS IN BATHROOMS |
| | AND TOILET ROOMS WHICH COMPLY |
| | WITH ?11-4.16.4 OF THIS CODE. |
| | |
| | 11-9.2.3(2) ALL BEDS IN DESIGNED |
| | ACCESSIBLE GUEST ROOMS SHALL BE |
| | OPEN-FRAME TYPE TO PERMIT PASSAGE OF |
| | LIFT DEVICES. |
| | |
| | 11-9.2.3(3) ALL STANDARD WATER |
| | CLOSET SEATS SHALL BE AT A HEIGHT OF |
| | 15 INCHES, MEASURED VERTICALLY FROM |
| | THE FINISH FLOOR TO THE TOP OF THE |
| | SEAT, WITH A VARIATION OF PLUS OR |
| | MINUS 1/2 INCH.A PORTABLE OR |
| | ATTACHED RAISED TOILET SEAT SHALL BE |
| | PROVIDED IN ALL DESIGNATED |
| | PERMANENT DISABILITY ACCESSIBLE |
| | ROOMS. |
| | |
| | |
| | 17) 11-9.3.1 GENERAL. IN SLEEPING ROOMS |
| | REQUIRED TO COMPLY WITH THISSECTION, |
| | AUXILIARY VISUAL ALARMS SHALL BE |
| | PROVIDED AND SHALL COMPLY WITH |
| | ?11-4.28.4.VISUAL NOTIFICATION |
| | DEVICES SHALL ALSO BE PROVIDED IN |
| | UNITS, SLEEPING ROOMS AND SUITES TO |
| | ALERT ROOM OCCUPANTS OF INCOMING |
| | TELEPHONE CALLS AND A DOOR KNOCK OR |
| | BELL. |
| | |
| | 18) 11-9.1.4(1) IN ORDER TO PROVIDE |
| | PERSONS WITH DISABILITIES A RANGE OF |
| | OPTIONS EQUIVALENT TO THOSE AVAILABLE |
| | TO OTHER PERSONS SERVED BY THE |
| | FACILITY, SLEEPING ROOMS AND SUITES |
| | REQUIRED TO BE ACCESSIBLE BY |
| | 11-9.1.2 SHALL BE DISPERSED AMONG THE |
| | VARIOUS CLASSES OF SLEEPING |
| | ACCOMMODATIONS AVAILABLE TO PATRONS OF |
| | THE PLACE OF TRANSIENT LODGING. |
| | FACTORS TO BE CONSIDERED INCLUDE ROOM |
| | SIZE, COST, AMENITIES PROVIDED, AND |
| | THE NUMBER OF BEDS PROVIDED. |
| | |
| | 19) 11-9.4 OTHER SLEEPING ROOMS AND |
| | SUITES. DOORS AND DOORWAYS DESIGNED TO |
| | ALLOW PASSAGE INTO AND WITHIN ALL |
| | SLEEPING UNITS OR OTHER COVERED UNITS |
| | SHALL COMPLY WITH 11-4.13.5. CLEAR |
| | WIDTH. |
| | |
| | 20A) 11-4.10.5 RAISED AND BRAILLE |
| | CHARACTERS ON HOISTWAY ENTRANCES. |
| | |
| | 20B) 11-4.10.12(2) TACTILE, BRAILLE, AND |
| | VISUAL CONTROL INDICATORS. |
| | |
| | 21) 11-4.30 SIGNAGE.?11-4.30.1 |
| | GENERAL. SIGNAGE REQUIRED TO BE |
| | ACCESSIBLE BY ?11-4.1 SHALL COMPLY WITH |
| | THE APPLICABLE PROVISIONS OF ?11-4.30. |
| | |
| | |
| | |
| | 22)SHEET A-1.0 HAWTHORN ROOMPROVIDE |
| | USEAGE, FOR THIS REVIEW CONSIDERED AS |
| | RESTRAUNT OCC LOAD 2104/15= 141 |
| | OCCUPANTS REQUIRES (2) EXITS, 1/3 THE |
| | DISTANCE OF THE ROOM APART, 1004.1.4 |
| | WHERE 2 OR MORE EXITS OR EXIT ACCESS |
| | DOORS ARE REQUIED, AT LEAST 2 OF THE |
| | EXIT OR EXIT ACCESS DOORS SHALL BE |
| | PLACED A DISTANCE APART EQUAL TO NOT |
| | LESS THAN 1/2 OF THE LENGTH OF THE |
| | MAXIMUM OVERALL DIAGONAL DIMENSION OF |
| | THE BUILDING OR AREA TO BE SERVED, |
| | (1/3RD DISTANCE FOR FIRE SPRINKLERED |
| | BUILDINGS). |
| | |
| | 23)SHEET A-1.0,/A- 6.3 TRIM CIRCULAR |
| | COLUMN WRAP, CHAIRAIL AND 8" CROWN |
| | MOLDING, PROVIDE ADDITIONAL DETAILS SEE |
| | 803.4 FOAM PLASTICS. FOAM PLASTICS SHALL |
| | NOT BE USED AS INTERIOR FINISH.4 |
| | EXECPTIONS. |
| | |
| | 24) SHEET A-1.0705.2.4.1 GENERAL. |
| | REFUSE AND LAUNDRY CHUTES, ACCESS AND |
| | TERMINATION ROOMS AND INCINERATOR ROOMS |
| | SHALL BE CONSTRUCTED IN ACCORDANCE WITH |
| | 705.2.4.2 THROUGH 705.2.4.6.INDICATE |
| | COMPLIANCE |
| | |
| | 25) SHEET A-1.0 705.2.4.4 TERMINATION |
| | ROOM. REFUSE AND LAUNDRY CHUTES SHALL |
| | DISCHARGE INTO AN ENCLOSED TERMINATION |
| | ROOM COMPLETELY SEPARATED FROM THE |
| | REMAINDER OF THE BUILDING BY |
| | CONSTRUCTION AND OPENING PROTECTIVES |
| | IN ACCORDANCE WITH TABLE 705.1.2. |
| | REFUSE CHUTES SHALL NOT TERMINATE IN AN |
| | INCINERATOR ROOM. INDICATE COMPLIANCE |
| | |
| | 26) SHEET A-1.2/ A-1.3705.2.4.3 |
| | REFUSE AND LAUNDRY CHUTE ACCESS ROOMS. |
| | ACCESS OPENINGSFOR REFUSE AND |
| | LAUNDRY CHUTES SHALL BE LOCATED IN ROOMS |
| | OR COMPARTMENTSCOMPLETELY ENCLOSED |
| | BY CONSTRUCTION AND OPENING PROTECTIVES |
| | IN ACCORDANCE WITH TABLE 705.1.2. |
| | ACCESS OPENINGS TO REFUSE AND LAUNDRY |
| | CHUTES SHALL NOT BE LOCATED IN EXIT |
| | ACCESS CORRIDORS OR EXIT ENCLOSURES. |
| | INDICATE COMPLIANCE. |
| | |
| | 27) ALL RATED CORRIDORS, ETC: |
| | 704.2.1.4 CORRIDOR PARTITIONS, SMOKE |
| | STOP PARTITIONS, HORIZONTAL EXIT PART- |
| | ITIONS, EXIT ENCLOSURES, AND FIRE |
| | RATED WALLS REQUIRED TO HAVE PROTECTED |
| | OPENINGS SHALL BE EFFECTIVELY AND |
| | PERMANETLY IDENTIFIED WITH SIGNS OR |
| | STENCILING IN A MANNER ACCEPTABLE TO THE |
| | AUTHORITY HAVING JURISDICTION. SUCH IDEN |
| | TIFICATION SHALL BE ABOVE ANY DECORATIVE |
| | CEILING CEILING AND IN CONCEALED SPACES. |
| | SUGGESTED WORDING" FIRE & SMOKE BARRIER |
| | PROTECT ALL OPENINGS". |
| | |
| | 28) 1016.4 STAIR IDENTIFICATION. AN |
| | APPROVED SIGN SHALL BE LOCATED AT EACH |
| | FLOOR LEVEL LANDING IN ALL ENCLOSED |
| | STAIRWAYS OF BUILDINGS FOUR OR MORE |
| | STORIES IN HEIGHT.THE SIGN SHALL |
| | INDICATE THE FLOOR LEVEL AND THE |
| | AVAILABILITY OF ROOF ACCESS FROM THAT |
| | STAIRWAY AND AN IDENTIFICATION OF THE |
| | STAIRWAY.THE SIGN SHALL ALSO STATE THE |
| | FLOOR LEVEL OF AND DIRECTION TO |
| | EXIT DISCHARGE.THE SIGN SHALL BE |
| | LOCATED APPROXIMATELY 5 FT (1524 MM) |
| | ABOVE THE FLOOR LANDING IN A POSITION |
| | WHICH IS READILY VISIBLE WHEN THE |
| | DOOR IS IN THE OPEN OR CLOSED POSITION. |
| | |
| | 29) SHEET A-1.3 INDICATES A EXIT ONTO |
| | THE ROOF DOOR 615B/ 615 A, SEE 1006.2.2 |
| | FOR REQUIRED ROOF-OVER BALCONY, PORCH OR |
| | GALLERY. |
| | |
| | 30) SHEET A-1.3 DETAIL A-5.2 DETAIL# 4 |
| | INDICATES A USE OF A RAISED WALKABLW |
| | DECK AND HANDRAIL. PROVIDE DETAILS FOR |
| | GAURDRAIL, INDICATE COMPLIANCE WITH: |
| | |
| | 30A)11015.3 OPENINGS. OPEN GUARDRAILS |
| | SHALL HAVE INTERMEDIATE RAILS OR |
| | ORNAMENTAL PATTERN SUCH THAT A 4-INCH |
| | (102 MM) DIAMETER SPHERE CANNOT PASS |
| | THROUGH ANY OPENING UP TO A HEIGHT OF 34 |
| | INCHES.A BOTTOM RAIL OR CURB |
| | SHALL BE PROVIDED THAT WILL REJECT THE |
| | PASSAGE OF 2-INCH (51 MM) DIAMETER |
| | SPHERE. |
| | |
| | 30B)1608.2.2.1 GUARDRAIL SYSTEMS SHALL |
| | BE DESIGNED AND CONSTRUCTED FOR A |
| | CONCENTRATED LOAD OF 200 LB (890 N) |
| | APPLIED AT ANY POINT AND IN ANY |
| | DIRECTION AT THE TOP OF THE GUARDRAIL. |
| | |
| | 30C)1608.2.2.2 GUARDRAIL SYSTEMS LOCATED |
| | OTHER THAN WITHIN DWELLING UNITS SHALL |
| | BE DESIGNED AND CONSTRUCTED FOR A LOAD |
| | OF 50 PLF (730 N/M) APPLIED HORIZONTALLY |
| | AT THE REQUIRED GUARDRAIL HEIGHT AND A |
| | SIMULTANEOUS LOAD OF 100 PLF (1459 N/M) |
| | APPLIED VERTICALLY DOWNWARD AT THE TOP |
| | OF THE GUARDRAIL. |
| | |
| | 30D) 1608.2.2.3 THE GUARDRAIL SYSTEM |
| | SHALL ALSO BE DESIGNED ANDCONSTRUCTED TO |
| | RESIST A 200 LB (890 N) CONCENTRATED |
| | HORIZONTAL LOAD APPLIED ON A 1 SQ FT |
| | AREA (0.093 M^2) AT ANY POINT IN THE |
| | SYSTEM INCLUDING INTERMEDIATE RAILS OR |
| | OTHER ELEMENTS SERVING THIS PURPOSE. |
| | |
| | 31) SHEET A-1.3 ROOM 621 A MULTI-PURPOSE |
| | ROOM WITH AN OCC LOAD OF 260 (ASSEMBLY |
| | OCCUPANCY) REQUIRES A 2HR RATED WALL/ |
| | WITH 1 1/2 HR RATED DOORS, SEE TABLE |
| | 705.1.2. |
| | |
| | 32A) SHEET A-1.3 CONFERENCE ROOM |
| | INDICATES A 1 HR RATED WALL, PROVIDE |
| | INFORMATION ON THE RATING OF WINDOW NEXT |
| | TO DOOR.TABLE 705.1.2. |
| | |
| | 32B)THIS SAME WINDOW TO BE SAFETY GLASS, |
| | HAZARDOUS AREA. FL BLD CODE 2405.2 |
| | HAZARDOUS LOCATION PROVIDE SAFETY GLASS |
| | FOR THIS LOCATION. |
| | |
| | 33) SHEET A-4.1 DETAIL 3 INDICATES THE |
| | USE OF ELEVATED SLABS & CMU. 2111.1.9* |
| | LOCAL AMENDMENT, WHERE EXTERIOR WALL |
| | MASONARY UNITS BEAR ON A CONCRETE FLOOR |
| | SURFACE, A 1.5" RECESS SHALL BE PROVIDED |
| | TO MINIMIZE WATER INTRUSION INTO |
| | FINISHED AREAS. |
| | |
| | 34) SHEET A-5.0 DETAIL# 6, THE CANOPY |
| | DETAIL INDICATES THE CEILING OF THE |
| | CANOPY TO BE CONSTRUCTED OF STUCCO ON |
| | 5/8" CEMENT BOARD. PROVIDE ADDITIONAL |
| | INFORMATION. THE STO PRODUCT APPROVAL |
| | SUBMITTED UNDER LIMITATIONS 3.1 "THIS |
| | SYSTEM IS NOT TO BE USED ON HORIZONTAL |
| | SURFACES. |
| | |
| | 35) THE PLANS ALSO INDICATE THE USE OF |
| | EFIS SYSTEMS FOR THE EXTERIOR WALLS, |
| | |
| | 35A) THE SUBMITTED STO EFIS REPORT |
| | INDICATES THAT IT WAS TESTED WITH STUDS |
| | AND PLYWOOD SUBSTRATE, PROVIDE TEESTING |
| | REPORT FOR THE ASSEMBLY THAT WILL BE |
| | USED FOR TYPE II BUILDING, SECTION 604 |
| | NONCOMBUSTIBLE EXTERIOR WALLS. |
| | |
| | 35B) SHOW COMPLIANCE WITH :2603.6 |
| | EXTERIOR WALLS OF BUILDINGS OF ANY |
| | HEIGHT. EXTERIOR WALLS OF |
| | BUILDINGS OF TYPES I, II, III, IV AND V0 |
| | CONSTRUCTION OF ANY HEIGHT SHALL |
| | COMPLY WITH ?2603.6.1 THROUGH ?2603.6.7. |
| | |
| | 35C)1404.1.1 ARCHITECTURAL TRIM ON |
| | BUILDINGS OF TYPE I, II AND IV |
| | CONSTRUCTION NOT MORE THAN THREE STORIES |
| | OR 40 FT (12.2 M) HIGH MAY BE OF |
| | TYPE VI CONSTRUCTION, AND MAY BE OF TYPE |
| | VI CONSTRUCTION ON ALL BUILDINGS |
| | OF TYPE III, V AND VI CONSTRUCTION. |
| | TRIM SHALL BE SECURED TO THE WALL |
| | WITH METAL OR OTHER APPROVED BRACKETS OR |
| | FASTENERS.WHEN ARCHITECTURAL |
| | TRIM IS LOCATED ALONG THE TOP OF |
| | EXTERIOR WALLS, IT SHALL BE COMPLETELY |
| | BACKED BY THE EXTERIOR WALL AND SHALL |
| | NOT EXTEND OVER THE TOP OF EXTERIOR |
| | WALLS. |
| | |
| | 36) S-7 CODE DESIGN NOTES INDICATE THAT |
| | THIS 6 STORY STRUCTURE WAAS DESIGNED TO |
| | ASCE 7-98, EXPOSURE "C". PROVIDE THE |
| | POSITIVE AND NEGATIVE PRESSURES FOR |
| | WALLS, INTERIOR AND END ZONES FOR THE |
| | EFIS APPLICATION,1606.1.1./ CHAPTER 6 |
| | ASCE 7-98. |
| | |
| | 37) IN READING THE ICC REPORT SUBMITTED |
| | FOR 5/8" DENS-GLASS GOLD THE REPORT |
| | STATES (7.4)IT IS PERMITTED WHERE THE |
| | DESIGN WIND PRESSURES DO NOT EXCEED |
| | 21.7 PSF. |
| | |
| | 38) PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 39) PRODUCT APPROVAL- ROOFING JOHN |
| | MANVILLE MODIFIED BITUMEN ROOF SYSTEMS, |
| | THIS REPORT THIS REPORT HAS (8) |
| | APPLICATIONS SOME INSULATEDAND OTHERS |
| | NON-INSULATED. DEPENDING ONWHICH REPORT |
| | USED, THE PRESSURES MAY HAVE LIMITATION |
| | 7 OR 9 NOT ALLOWING INCREASES. HIGHLIGHT |
| | THE REPORT TO BE USED.!!!!!! |
| | |
| | 40) CURRIES EXTERIOR DOORS THE |
| | 6'X7'DOORS LOCATED IN END ZONE 5 WILL |
| | REQUIRE -121PSF, SUBMITTED REPORTS LOW |
| | PRESSURE OR REPORTS ARE EXPIRED. SEE |
| | DOORS 130B & 137B.CURRIES 747 16 GA LOW |
| | PRESSURE REPORT ONLY GOOD FOR -62. |
| | |
| | 41) RESAM AES AUTO DOORS- LOW PRESSURE |
| | |
| | 42) PGT HORIZONTAL ROLLER WINDOWHR-810: |
| | LOW PRESSURES IN ZONE# 5, MISSING FL |
| | COVERSHEET. |
| | |
| | 43) MISSING REPORTS FOR WALL LOUVER, |
| | NO FL COVERSHEET. |
| | |
| | 44) EXTERIOR GUARDRAILS, MISSING PRODUCT |
| | APPROVALS & FL COVERSHEET. |
| | |
| | 45) FIXED WINDOWS, ABOVE AUTOMATIC |
| | SLIDING DOORS, NO REPORT,OR FL COVER |
| | SHEET. |
| | |
| | 46A) HORIZONTAL MULLION OVER FRONT |
| | HORIZONTAL SLIDING ENTRY DOOR. NO REPORT |
| | NOR FL COVERSHEET. |
| | |
| | 46B) 1707.4.5.1 MULLIONS OCCURRING |
| | BETWEEN INDIVIDUAL WINDOW AND GLASS |
| | DOOR ASSEMBLIES. TESTING REPORTS ARE |
| | REQUIRED BY AN APPROVED TESTING |
| | LABORATORY OR BE ENGINEERED. |
| | |
| | 46C) 1707.4.5.2 MULLIONS SHALL BE |
| | DESIGN- ED TO TRANSFER THE DESIGN |
| | PRESSURE LOADS APPLIED BY THE WINDOW OR |
| | DOOR ASSEMBLIES TO THE ROUGH OPENING |
| | SUBTRATE. |
| | |
| | 47) 3003.6.1 VENTS. HOISTWAYS OF ELEVA- |
| | TORS SERVING MORE THAN 3 FLOORS SHALL BE |
| | PROVIDED WITH MEANS OF VENTING SMOKE AND |
| | HOT GASES TO THE OUTER AIR IN CASE OF |
| | FIRE. |
| | |
| | 48) 3003.6.3 THE AREA OF THE VENTS SHALL |
| | BE NOT LESS THAN 3 SQ FT FOR EACH |
| | ELEVATOR CAR, WHICHEVER IS GREATER. |
| | |
| | 49) 3003.7.1 ACCESS TO MACHINE ROOMS AND |
| | MACHINERY SPACES. A PERMANENT, SAFE AND |
| | CONVENIENT MEANS OF ACCESS TO ELEVA- TOR |
| | MACHINE ROOMS AND OVERHEAD MACHINERY |
| | SPACES SHALL BE PROVIDED FOR AUTHORIZED |
| | PERSONAL. THE MEANS OF ACCESS SHALL NOT |
| | BE THROUGH RESTROOMS, DRESSING ROOMS, |
| | OR TENANT ( INCLUDING OWNER-OCCUPIED) |
| | SPACES. |
| | |
| | 50) 3003.4.1 IN ALL STRUCTURES THAT ARE |
| | MORE THAN THREE STORIES HIGH OR IN |
| | WHICH THE VERTICAL DISTANCE BETWEEN THE |
| | BOTTOM TERMINAL LANDING AND THE |
| | TOP TERMINAL LANDING EXCEEDS 25 FEET |
| | (7.6 M) MUST BE CONSTRUCTED TO |
| | CONTAIN AT LEAST ONE PASSENGER LEVATOR |
| | THAT IS OPERATIONAL AND WILL |
| | ACCOMMODATE AN AMBULANCE STRETCHER 76 |
| | INCHES (1931 MM) LONG AND 24 INCHES |
| | (610 MM) WIDE IN THE HORIZONTAL |
| | POSITION.THIS ELEVATOR SHALL BE |
| | IDENTIFIED. |
| | |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |