| Plan Review Notes For Permit 05041543 |
| Permit Number |
05041543 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-05-02 00:00:00 | **** REDLINED**** | | | | | | | | | 1) CORRELATE PANEL SCHEDULE "B" WITH | | | RISER. SHOWS 3-#6'S FOR SUB PANEL AND | | | RISER SHOWS 2-#6'S AND 1-#8. | | | | | | 2) PLEASE SEE NEC 220 MOTOR LOADS ON SUB | | | PANEL ARE AT 100%, 125% FOR ALL | | | CONTINOUS LOADS. | | | LOAD ON SUB PANEL IS NOT DERATED AS | | | LIGHTING LOADS. | | | | | | | | | PLEASE REVISETHE ABOVE ALONG WITH ANY | | | OTHER REVISIONS. |
|