| Notes |
| Date |
Text |
| 2005-05-05 00:00:00 | 1) PLEASE REFER TO COMMENT #1 BY | | | ELECTRICAL PLANS REVIEW REGARDING NUMBER | | | OF FLOORS INVOLVED. | | | | | | 2) PLEASE INDICATE THE LOCATIONS OF | | | ILLUMINATED EXIT SIGNS AND EMERGENCY | | | LIGHTING FACILITIES. | | | | | | 3) SEPARATE SHOP DRAWINGS AND PERMITS | | | ARE REQUIRED FOR FIRE ALARM AND FIRE | | | SPRINKLER REMODELS. | | | | | | 4) FIRE EXTINGUISHERS RATED 2A-10B,C ARE | | | REQUIRED TO BE MOUNTED WITH A TRAVEL | | | DISTANCE NOT TO EXCEED 75'. | | | | | | 5) CONSTRUCTION, ALTERATION AND | | | DEMOLITION TO COMPLY WITH NFPA 241. | | | | | | | | | MIKE WENNERGREN, A/CAPTAIN | | | WPBFR(561) 835-2910 OR 805-6722 |
|