| 2005-06-27 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2001 |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| | TO THE FBC2001 |
| | |
| | 1.)CODE COMPLIANCE FOR THE WINDOWS |
| | CANNOT BE DETERMINED UNTIL DESIGN |
| | PRESSURES FOR THE BUILDING HAVE BEEN |
| | DETERMINED, SEE ITEMS #5 AND 6 FROM |
| | PREVIOUS LIST. |
| | |
| | 2.)SEE ATTACHED FS553.80(2)(B). |
| | |
| | 3.)THE RECEIPT OF A TRANSMITTAL LETTER |
| | ADDRESSING SOME OF THE COMMENTS IS |
| | ACKNOWLEDGED.HOWEVER, THE PLAN IS TO |
| | SHOW CODE COMPLIANCE.COMMENTS |
| | REGARDING ACCESSIBILITY AND FIRE |
| | RESISTANCE CANNOT BE ADDRESSED WITH A |
| | LETTER, ESPECIALLY A LETTER SIGNED BY |
| | SOMEONE OTHER THAN THE ARCHITECT AND NOT |
| | SEALED. |
| | |
| | 4.)ITEM 13 WAS NOT PROPERLY ADDRESSED. |
| | PLEASE READ THE CODE SECTION AND IF YOU |
| | DO NOT UNDERSTAND IT PLEASE CONTACT ME |
| | TO DISCUSS.THE TRANSMITTAL LETTER |
| | STATED THAT THE ADJOINING DOORS WERE |
| | SHOWN ON THE PLAN.THE PLAN NOTES THAT |
| | THESE DOORS ARE TO REMAIN OR BE REMOVED |
| | AT THE DISCRETION OF RRI.IF THERE ARE |
| | ADJOINING DOORS IN OTHER ROOMS BUT NOT |
| | IN THE ACCESSIBLE ROOMS AT THE |
| | DISCRETION OF THE OWNER, THIS IS NOT |
| | CODE COMPLIANT.FBC11-9.1.4(1).ROOM |
| | TYPES, NUMBER OF BEDS, WOULD BE |
| | CONSIDERED AN AMENITY. |
| | |
| | THE FOLLOWING COMMENTS FROM THE PREVIOUS |
| | REVIEW WERE NOT ADDRESSED ON THE PLAN; |
| | ITEMS #1, 3, 5, 6, 12, 13, 14, 19, 20, |
| | 24.FOR YOUR CONVENIENCE, THEY ARE |
| | LISTED BELOW: |
| | |
| | 1.) THE "LEGAL DESCRIPTION" ON THE |
| | NOTICE OF COMMENCEMENT IS TO INCLUDE THE |
| | LEGAL DESCRIPTION OF THE PROPERTY |
| | FS713.13(1)(A)1.ONLY AN ADDRESS WAS |
| | PROVIDED. |
| | |
| | 3.)SHEET A0.1, PROJECT DATA, HAS 2C AS |
| | CONSTRUCTION TYPE, WHAT IS C?PLEASE |
| | SEE FBC604 AND CLARIFY. |
| | |
| | 5.)WHERE ARE THE WINDOWS BEING |
| | INSTALLED?WHAT SIZE? |
| | |
| | 6.)PROVIDE INFORMATION REQUIRED BY |
| | FBC1606.1.7.DESIGN PRESSURES FOR THE |
| | WINDOWS ARE REQUIRED TO DETERMINE CODE |
| | COMPLIANCE.ALSO PROVIDE MEAN ROOF |
| | HEIGHT. |
| | |
| | |
| | 10.) ON THE FLORIDA PRODUCT APPROVAL, |
| | CIRCLE THE PRODUCT YOU WISH TO INSTALL. |
| | |
| | 11.)THE ADA ROOM DETAILS (SUCH AS |
| | A4.4, ADA CODE COMPLIANCE) REFER TO 28 |
| | CFR PART 36.PLEASE NOTE THAT THE |
| | GOVERNING CODE IS FBC CHAPTER 11, |
| | ACCESSIBILITY. |
| | |
| | 12.)THE EXISTING UNIVERSAL DOUBLE AND |
| | SINGLE UNITS HAVE BEEN REPLACED BY |
| | UNIVERSAL KING UNITS.PLEASE SEE |
| | FBC11-9.1.4(1) AND REVISE."FACTORS TO |
| | BE CONSIDERED INCLUDE ROOM SIZE, COST, |
| | AMENITIES PROVIDED, AND THE NUMBER OF |
| | BEDS PROVIDED."ADJOINING ROOMS WOULD |
| | ALSO BE CONSIDERED AN AMENITY.INDICATE |
| | ACCESSIBLE ROOMS WITH AN ADJOINING DOOR |
| | ON THE PLAN. |
| | |
| | 13.)SLEEPING ACCOMMODATIONS FOR |
| | PERSONS WITH HEARING IMPAIRMENTS |
| | REQUIRED, FBC11-9.1.3. |
| | |
| | 14.)INCLUDE WINDOW REPLACEMENT ON THE |
| | PERMIT APPLICATION. |
| | |
| | 16.)***NOTE*** ITEM #16 ADDRESSED |
| | UNDER A SEPARATE PERMIT (ACCESSIBLE |
| | ENTRANCE, ROUTE, ETC.). |
| | |
| | 19.)DRAWER HARDWARE IS TO BE COMPLIANT |
| | WITH FBC11-4.25.4, FBC11-4.27.4. |
| | |
| | 20.)SPECIFY DESIGN CRITERIA FOR |
| | STRENGTH OF GRAB BARS, ETC. |
| | FBC11-4.26.3. |
| | |
| | 24.)PROVIDE INTERIOR FINISH |
| | CLASSIFICATION FBC803.2. |
| | |
| | |
| | WHEN RESUBMITTING, REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED.SUBMIT OLD SHEETS |
| | SEPARATELY.TO EXPEDITE PLAN REVIEW, |
| | PROVIDE A TRANSMITTAL LETTER INDICATING |
| | HOW EACH ITEM WAS ADDRESSED. |