Plan Review Notes
Plan Review Notes For Permit 05041404
Permit Number 05041404
Review Stop B
Sequence Number 2
Notes
Date Text
2005-06-27 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)CODE COMPLIANCE FOR THE WINDOWS
 CANNOT BE DETERMINED UNTIL DESIGN
 PRESSURES FOR THE BUILDING HAVE BEEN
 DETERMINED, SEE ITEMS #5 AND 6 FROM
 PREVIOUS LIST.
  
 2.)SEE ATTACHED FS553.80(2)(B).
  
 3.)THE RECEIPT OF A TRANSMITTAL LETTER
 ADDRESSING SOME OF THE COMMENTS IS
 ACKNOWLEDGED.HOWEVER, THE PLAN IS TO
 SHOW CODE COMPLIANCE.COMMENTS
 REGARDING ACCESSIBILITY AND FIRE
 RESISTANCE CANNOT BE ADDRESSED WITH A
 LETTER, ESPECIALLY A LETTER SIGNED BY
 SOMEONE OTHER THAN THE ARCHITECT AND NOT
 SEALED.
  
 4.)ITEM 13 WAS NOT PROPERLY ADDRESSED.
 PLEASE READ THE CODE SECTION AND IF YOU
 DO NOT UNDERSTAND IT PLEASE CONTACT ME
 TO DISCUSS.THE TRANSMITTAL LETTER
 STATED THAT THE ADJOINING DOORS WERE
 SHOWN ON THE PLAN.THE PLAN NOTES THAT
 THESE DOORS ARE TO REMAIN OR BE REMOVED
 AT THE DISCRETION OF RRI.IF THERE ARE
 ADJOINING DOORS IN OTHER ROOMS BUT NOT
 IN THE ACCESSIBLE ROOMS AT THE
 DISCRETION OF THE OWNER, THIS IS NOT
 CODE COMPLIANT.FBC11-9.1.4(1).ROOM
 TYPES, NUMBER OF BEDS, WOULD BE
 CONSIDERED AN AMENITY.
  
 THE FOLLOWING COMMENTS FROM THE PREVIOUS
 REVIEW WERE NOT ADDRESSED ON THE PLAN;
 ITEMS #1, 3, 5, 6, 12, 13, 14, 19, 20,
 24.FOR YOUR CONVENIENCE, THEY ARE
 LISTED BELOW:
  
 1.) THE "LEGAL DESCRIPTION" ON THE
 NOTICE OF COMMENCEMENT IS TO INCLUDE THE
 LEGAL DESCRIPTION OF THE PROPERTY
 FS713.13(1)(A)1.ONLY AN ADDRESS WAS
 PROVIDED.
  
 3.)SHEET A0.1, PROJECT DATA, HAS 2C AS
 CONSTRUCTION TYPE, WHAT IS C?PLEASE
 SEE FBC604 AND CLARIFY.
  
 5.)WHERE ARE THE WINDOWS BEING
 INSTALLED?WHAT SIZE?
  
 6.)PROVIDE INFORMATION REQUIRED BY
 FBC1606.1.7.DESIGN PRESSURES FOR THE
 WINDOWS ARE REQUIRED TO DETERMINE CODE
 COMPLIANCE.ALSO PROVIDE MEAN ROOF
 HEIGHT.
  
  
 10.) ON THE FLORIDA PRODUCT APPROVAL,
 CIRCLE THE PRODUCT YOU WISH TO INSTALL.
  
 11.)THE ADA ROOM DETAILS (SUCH AS
 A4.4, ADA CODE COMPLIANCE) REFER TO 28
 CFR PART 36.PLEASE NOTE THAT THE
 GOVERNING CODE IS FBC CHAPTER 11,
 ACCESSIBILITY.
  
 12.)THE EXISTING UNIVERSAL DOUBLE AND
 SINGLE UNITS HAVE BEEN REPLACED BY
 UNIVERSAL KING UNITS.PLEASE SEE
 FBC11-9.1.4(1) AND REVISE."FACTORS TO
 BE CONSIDERED INCLUDE ROOM SIZE, COST,
 AMENITIES PROVIDED, AND THE NUMBER OF
 BEDS PROVIDED."ADJOINING ROOMS WOULD
 ALSO BE CONSIDERED AN AMENITY.INDICATE
 ACCESSIBLE ROOMS WITH AN ADJOINING DOOR
 ON THE PLAN.
  
 13.)SLEEPING ACCOMMODATIONS FOR
 PERSONS WITH HEARING IMPAIRMENTS
 REQUIRED, FBC11-9.1.3.
  
 14.)INCLUDE WINDOW REPLACEMENT ON THE
 PERMIT APPLICATION.
  
 16.)***NOTE*** ITEM #16 ADDRESSED
 UNDER A SEPARATE PERMIT (ACCESSIBLE
 ENTRANCE, ROUTE, ETC.).
  
 19.)DRAWER HARDWARE IS TO BE COMPLIANT
 WITH FBC11-4.25.4, FBC11-4.27.4.
  
 20.)SPECIFY DESIGN CRITERIA FOR
 STRENGTH OF GRAB BARS, ETC.
 FBC11-4.26.3.
  
 24.)PROVIDE INTERIOR FINISH
 CLASSIFICATION FBC803.2.
  
  
 WHEN RESUBMITTING, REPLACE ONLY SHEETS
 WHICH HAVE CHANGED.SUBMIT OLD SHEETS
 SEPARATELY.TO EXPEDITE PLAN REVIEW,
 PROVIDE A TRANSMITTAL LETTER INDICATING
 HOW EACH ITEM WAS ADDRESSED.