Plan Review Notes
Plan Review Notes For Permit 05041404
Permit Number 05041404
Review Stop B
Sequence Number 1
Notes
Date Text
2005-05-24 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.) THE "LEGAL DESCRIPTION" ON THE
 NOTICE OF COMMENCEMENT IS TO INCLUDE THE
 LEGAL DESCRIPTION OF THE PROPERTY
 FS713.13(1)(A)1.ONLY AN ADDRESS WAS
 PROVIDED.
  
 2.) THE ARCHITECT'S SEAL IS TO BE DATED
 AS WELL AS SIGNED, FAC61G1-16.003,
 FS481.
  
 3.)SHEET A0.1, PROJECT DATA, HAS 2C AS
 CONSTRUCTION TYPE, WHAT IS C?PLEASE
 SEE FBC604 AND CLARIFY.
  
 4.)PRODUCT APPROVALS FOR FIXED GLASS
 WINDOWS WERE SUBMITTED.PLEASE SUBMIT
 LEGIBLE, ORIGINAL DOCUMENTS.THIS WAS A
 PHOTOCOPY STAMPED BY ANOTHER
 MUNICIPALITY.WWW.FLORIDABUILDING.ORG
 ON THE CLEAN COPY, INDICATE WHICH
 PRODUCT YOU ARE INSTALLING.
  
 5.)WHERE ARE THE WINDOWS BEING
 INSTALLED?WHAT SIZE?
  
 6.)PROVIDE INFORMATION REQUIRED BY
 FBC1606.1.7.DESIGN PRESSURES FOR THE
 WINDOWS ARE REQUIRED TO DETERMINE CODE
 COMPLIANCE.ALSO PROVIDE MEAN ROOF
 HEIGHT.
  
 7.)PROVIDE A WINDOW BUCK DETAIL OR
 FASTENING SCHEDULE.
  
 8.)IMPACT PROTECTION REQUIRED
 FBC1606.1.4.
  
 9.)SEE ATTACHED IMPLEMENTATION
 STANDARD FOR HURRICANE MISSILE IMPACT
 PROTECTION, ITEMS 13 AND 14.SHUTTERS
 ARE ALLOWED FOR FIRST FLOOR ONLY IF
 APPROVED BY BUILDING OFFICIAL (IMPACT
 GLASS REQUIRED FOR SECOND AND THIRD
 FLOORS).IF YOU INTEND TO USE SHUTTERS
 FOR THE FIRST FLOOR WINDOWS, A PRE-STORM
 PREPARATION PLAN MUST BE APPROVED BY THE
 BUILDING OFFICIAL.THIS PLAN MAY BE
 SUBMITTED SEPARATELY FROM THE
 RESUBMITTAL FOR THE PERMIT.NOTE THAT
 SHUTTERS CANNOT BE STORED OFF SITE.
  
 10.) ON THE FLORIDA PRODUCT APPROVAL,
 CIRCLE THE PRODUCT YOU WISH TO INSTALL.
  
 11.)THE ADA ROOM DETAILS (SUCH AS
 A4.4, ADA CODE COMPLIANCE) REFER TO 28
 CFR PART 36.PLEASE NOTE THAT THE
 GOVERNING CODE IS FBC CHAPTER 11,
 ACCESSIBILITY.
  
 12.)THE EXISTING UNIVERSAL DOUBLE AND
 SINGLE UNITS HAVE BEEN REPLACED BY
 UNIVERSAL KING UNITS.PLEASE SEE
 FBC11-9.1.4(1) AND REVISE."FACTORS TO
 BE CONSIDERED INCLUDE ROOM SIZE, COST,
 AMENITIES PROVIDED, AND THE NUMBER OF
 BEDS PROVIDED."ADJOINING ROOMS WOULD
 ALSO BE CONSIDERED AN AMENITY.INDICATE
 ACCESSIBLE ROOMS WITH AN ADJOINING DOOR
 ON THE PLAN.
  
 13.)SLEEPING ACCOMMODATIONS FOR
 PERSONS WITH HEARING IMPAIRMENTS
 REQUIRED, FBC11-9.1.3.
  
 14.)INCLUDE WINDOW REPLACEMENT ON THE
 PERMIT APPLICATION.
  
 15.)THE APPLICATION STATES THAT
 "ELECTRICAL AND PLUMBING WILL BE
 INCLUDED UNDER THIS PERMIT."A REVIEW
 WILL BE DONE UNDER THIS PERMIT BUT
 SEPARATE PERMIT APPLICATIONS FROM THE
 SUBCONTRACTORS ARE REQUIRED AS THIS IS
 NOT WITHIN THE SCOPE OF GC LICENSE.
  
 16.)PROVIDE (ACCESSIBILITY)
 INFORMATION IN REGARDS TO THE ENTRANCE,
 ACCESSIBLE ROUTE, SIGNAGE, EXISTING
 RESTROOMS, TELEPHONES IN THE LOBBY.SEE
 FBC11-4.1.6(2), DUTY TO PROVIDE
 ACCESSIBLE FEATURES IN THE EVENT OF
 DISPROPORTIONALITY.IF ALL ITEMS ARE
 ALREADY ACCESSIBLE, SHOW COMPLIANCE ON
 THE PLAN (EXISTING CONDITIONS DETAIL).
  
 17.)FBC*104.2.1, INFORMATION IS TO BE
 SPECIFIC, AND THE TECHNICAL CODES SHALL
 NOT BE CITED AS A WHOLE OR IN PART.FOR
 INSTANCE, A4.4, ADA CODE COMPLIANCE,
 "ALL OBJECTS AND CONTROLS INTENDED FOR
 GUEST USE COMPLY W/4.2.5 AND 4.2.6" AND
 "DOOR HARDWARE COMPLIANT W/4.13.9."
 PROVIDE SPECIFICATION, NOT CODE SECTION,
 IN ALL INSTANCES ON THE PLAN WHERE A
 CODE NUMBER WAS GIVEN IN LIEU OF DESIGN
 CRITERIA.THE TWO ABOVE WERE PROVIDED
 AS AN EXAMPLE; THERE MAY BE OTHER CODE
 REFERENCES WHICH NEED FURTHER DESIGN
 SPECIFICATION.
  
 18.) PROVIDE ENTRY DOOR WIDTH FOR THE
 ACCESSIBLE UNITS.
  
 19.)DRAWER HARDWARE IS TO BE COMPLIANT
 WITH FBC11-4.25.4, FBC11-4.27.4.
  
 20.)SPECIFY DESIGN CRITERIA FOR
 STRENGTH OF GRAB BARS, ETC.
 FBC11-4.26.3.
  
 21.)SHOW THE DEPTH OF THE PTAC FOR THE
 ACCESSIBLE UNITS, MAX OF 10" FBC11
 FIGURE 6.WHEN SCALED, THIS DIMENSION
 IS GREATER THAN 12".
  
 22.)COMBUSTIBLES NOT ALLOWED IN
 CONCEALED SPACES (2X4 BLOCKING) IN TYPE
 I, II AND IV CONSTRUCTION EXCEPT AS
 ALLOWED IN FBC707.1 AND FBC CHAPTER 8.
  
 23.)A8.0, ELEVATIONS SHOW STUCCO.IS
 THIS EXISTING CONDITIONS OR NEW STUCCO?
 IF THIS IS NEW, PROVIDE A WALL SECTION.
  
 24.)PROVIDE INTERIOR FINISH
 CLASSIFICATION FBC803.2.
  
  
 WHEN RESUBMITTING, REPLACE ONLY SHEETS
 WHICH HAVE CHANGED.SUBMIT OLD SHEETS
 SEPARATELY.TO EXPEDITE PLAN REVIEW,
 PROVIDE A TRANSMITTAL LETTER INDICATING
 HOW EACH ITEM WAS ADDRESSED.
  
  