| 2005-05-05 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 FUEL GAS |
| | FBC-2001 CHAPTE 1 |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | FUEL GAS CODE. |
| | 2. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2001 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.5.2 AND TABLES 402(1) THRU |
| | 402(34). |
| | 3. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES (A)(3). |
| | 4. SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER FBC-2001 FUEL GAS CODE |
| | SECS. 502 THRU 506. |
| | 5) A RESIDENTIAL GENERATOR PERMIT SHALL |
| | BE APPLIED FOR BY THE CONTRACTOR THAT |
| | SETS AND HOOKS UP THE GENERATOR. THE |
| | FOLLOWING INFORMATION IS REQUIRED: |
| | A. A SURVEY/SITE PLAN IS REQUIRED |
| | SHOWING THE LOCATION OF THE GENERATOR |
| | AND THE SET BACKS FOR THE PROPERTY LINE. |
| | THE DISTANCE FROM ALL OPENINGS IN THE |
| | STRUCTURE SHALL BE SHOWN ON THE PLAN. |
| | B. REVIEWS BY THE FOLLOWING ARE |
| | REQUIRED PRIOR TO ANY PERMIT BEING |
| | ISSUED FOR THE GENERATOR. ZONING, |
| | MECHANICAL, ELECTRIC, BUILDING, AND FUEL |
| | GAS. |
| | 6) ALL INFORMATION, DRAWINGS, |
| | SPECIICATIONS AND ACCOMPANYING DATA |
| | SHALL BEAR THE NAME AND SIGNATURE OF THE |
| | PERSON RESPONSIBLE FOR THE DESIGN . |
| | SECTION 104.2.1. |
| | |