| Date |
Text |
| 2006-05-01 00:00:00 | 1) FBC 13-103.1.2 BEFORE A BUILDING |
| | PERMIT CAN BE ISSUED, THE SUBMITTED |
| | ENERGY CODE COMPLIANCE FORMS SHALL BE |
| | SIGNED BY THE BUILDING OWNER, THE |
| | OWNER'S ARCHETECT OR OTHER AUTHORIZED |
| | AGENT LEGALLY DESIGNATED BY THE OWNER. |
| | |
| | 2) BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 3) PLANS WHICH WERE BROUGHT IN UNDER THE |
| | 2001 FBC CANNOT BE CHANGE TO 2004 CODE |
| | DURING THE REVIEW PROCESS. SEE SHEET 2 |
| | OF 6. WHICH REFERS TO THE 2004 CODE.SO |
| | PLEASE CHANGE INFORMATION TO REFLECT THE |
| | 2001 CODE. |
| | |
| | 4) THE PRODUCT APPROVAL FOR THE MODIFIED |
| | ROOF INDICATES A WOOD INSULATED SYSTEM |
| | HOWEVER, THE INFORMATION ON THE DRAWINGS |
| | ABOUT THE ROOF (SHEET 2), DOES NOT |
| | INDICATE ANY INSULATION. THE PRODUCT |
| | APPROVAL HAS TO MATCH WHAT IS ON THE |
| | DRAWINGS. READ THE APPROVED ASSEMBLY TO |
| | BE SURE THAT IS THE TYPE WHICH WILL BE |
| | INSTALLED. |
| | |
| | 5 ) 713.13(2) F.S.THE NOTICE OF |
| | COMMENCEMENT MUST BE RE-RECORDED BECAUSE |
| | THE DESCRIBED IMPROVEMENT OR |
| | CONSTRUCTION DID NOT COMMENCE WITHIN 90 |
| | DAYS OF RECORDING. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | TEL:(561)805-6726 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |