Plan Review Notes
Plan Review Notes For Permit 05041364
Permit Number 05041364
Review Stop E
Sequence Number 1
Notes
Date Text
2005-05-11 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE HAND DRAWN CHANGES ON THE PLAN
 ARE NOT ACCEPTABLE FOR RETENTION OR JOB
 SITE REVIEWED PLAN PER 104.2.1.3 FBC.
  
 2} A RECEPTACLE MUST BE ADDED TO THE
 REAR OF THE BUILDING (IF NONE EXIST)PER
 210.52(E).
  
 3} THE ENGINEER MUST ATTACH A TITLE
 BLOCK TO THE PLANS PER 61G15-23.002.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW