| 2005-12-22 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 05041273 |
| | ADD: 424 HAMPTON RD |
| | CONT: CLASSIC CONSTRUCTION |
| | TEL: (561)719-5111 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVISION REVIEW |
| | ACTION: DENIED |
| | |
| | 1) THE PERMIT THAT WAS PULLED ORIGINALLY |
| | WAS WITHIN THE CONFINES OF TENANT |
| | SEPERATION WALLS. THE REVISION INDICATES |
| | WORK BEING COMPLETED IN THE COMMON AREA, |
| | WHICH WILL OPEN NEW ISSUES. |
| | FL BLD CODE 104.2.1.2 |
| | ADDITIONAL INFORMATION REQUIRED: |
| | |
| | 1A) PROVIDE A COMPLETE FLOOR PLAN FOR |
| | THIS COMPLETE FLOOR. PROVIDE THE |
| | OCCUPANT LOAD FOR THIS FLOOR. THE |
| | DOORWAY TO THE STAIR TOWER MAY BE |
| | SWINGING IN THE WRONG DIRECTION. |
| | 1012.1.2 EGRESS DOORS SHALL BE SIDE |
| | SWINGING TYPE.DOORS SHALL SWING IN THE |
| | DIRECTION OF EGRESS FOR THE FOLLOWING |
| | 1. WHEN SERVING AN OCCUPANT LOAD OF |
| | 50 OR MORE. |
| | |
| | 1B) PROVIDE IF THIS IS A FIRE |
| | SPRINKLERED BUILDING, WHAT FIRE RATING |
| | DOES THIS TRANSFORMER HAVE? IS THIS A |
| | DRY OR OIL FILLED TRANSFORMER? |
| | |
| | 1C) IT APPEARS TO SIT ON THE FLOOR AND |
| | DEPENDING ON THE SIZE AND LOCATION IT |
| | MAY CONFLICT WITH :1003.2.4 OBJECTS |
| | PROJECTING FROM WALLS WITH THEIR LEADING |
| | EDGES BETWEEN27 AND 80 INCHES (686 |
| | AND 2032 MM)ABOVE THE FINISHED FLOOR |
| | SHALL PROTRUDENO MORE THAN 4 INCHES |
| | (102 MM) INTO WALKS, CORRIDORS, |
| | PASSAGEWAYS ORAISLES.FREE-STANDING |
| | OBJECTS MOUNTED ON POSTS OR PYLONS MAY |
| | OVERHANG 12INCHES (305 MM) MAXIMUM |
| | FROM 27 TO 80 INCHES (686 AND 2032 MM) |
| | ABOVE THE GROUND OR FINISHED FLOOR. |
| | |
| | 1D)11-4.4.1 GENERAL OBJECTS PROJECTING |
| | FROM WALLS (FOR EXAMPLE, TELEPHONES) |
| | WITH THEIR LEADING EDGES BETWEEN 27 IN. |
| | AND 80 IN. (685 MM AND 2030 MM) ABOVE |
| | THE FINISHED FLOOR SHALL PROTRUDE NO |
| | MORE THAN 4 IN. (100 MM) INTO WALKS, |
| | HALLS, CORRIDORS, PASSAGEWAYS, OR AISLES |
| | (SEEFIGURE 11-8(A)).OBJECTS MOUNTED |
| | WITH THEIR LEADING EDGES AT OR BELOW 27 |
| | IN. (685 MM) ABOVE THE FINISHED FLOOR |
| | MAY PROTRUDE ANY AMOUNT (SEEFIGURE |
| | 11-8(A) AND FIGURE 11-8(B)). |
| | FREE-STANDING OBJECTS MOUNTED ONPOSTS |
| | OR PYLONS MAY OVERHANG 12 IN (305 MM) |
| | MAXIMUM FROM 27 IN. TO 80 IN. (685 MM TO |
| | 2030 MM) ABOVE THE GROUND OR FINISHED |
| | FLOOR (SEE FIGURE 11-8(C) AND FIGURE |
| | 11-8(D)).PROTRUDING OBJECTS SHALL NOT |
| | REDUCE THE CLEAR WIDTH OF AN ACCESSIBLE |
| | ROUTE OR MANEUVERING SPACE (SEE FIGURE |
| | 11-8(E). |
| | BUILDING PLAN REVIEW |