| Date |
Text |
| 2005-09-21 00:00:00 | *********** UNSAT 4TH REVIEW ********* |
| | |
| | 1)NOTE: PLEASE SEE ELECTRICAL CODE |
| | COMPLIANCE COMMENTS HAVE BEEN ADDRESSED |
| | BY NEW ENGINEER OF RECORD, HOWEVER |
| | PLEASE SEE COMMENT BELOW. |
| | |
| | PLEASE SEE NE PLANS BY ENGINEER DO NOT |
| | CONTAIN NEW LAYOUT FOR ELECTRICAL |
| | LIGHTING/CEILING PLANS. |
| | THE EXISTING LIGHTING/CEILING PLANS |
| | "A-3" COULD HAVE BEEN USED FOR LIGHTING |
| | LAYOUT ONLY , HOWEVER PLEASE SEE BOTH |
| | SETS CONTAIN "PHOTOCOPIES" OF SIGNED AND |
| | SEALED PLANS BY THE ARCHITECT??? |
| | PLEASE SEE NEW SHEET A-1 AND A-3 WHICH |
| | ARE NOT SIGNED, DATED AND SEALED. |
| | PLEASE SEE BLDG REVIEW FOR SHEET A-1. |
| | |
| | PLEASE EITHER HAVE NEW ENGINEER OF |
| | RECORD REVISE NEW SHEET E-1 TO INCLUDE |
| | NEW ELECTRICAL LIGHTING/CEILING LAYOUT |
| | OR PLEASE HAVE NEW SIGNED, DATED AND |
| | SEALED PLANS FOR SHEET A-3. |
| | |
| | IN EITHER CASE, PLEASE REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW |
| | REVISED , CORRECTED SHEETS INTO COMPLETE |
| | SETS FOR REVIEW AND STAMPING. |
| | |
| | IF THERE ARE ANY QUESTIONS, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE. |
| | |