| 2005-08-29 00:00:00 | ********* UNSAT 3RDREVIEW ********** |
| | |
| | PLEASE SEE NOTES FROM PREVIOUS REVIEWS |
| | AND NEW COMMENTS DUE TO COMPLETE NEW |
| | ELECTRICAL RISER SUBMITTED. |
| | |
| | 1)NOTE: PLEASE SEE RISER NOW INDICATES |
| | AND NEW TRANSFOMER AND 277/480V SYSTEM |
| | BEING SHOWN. |
| | PLEASE SEE FS 471.003, WHICH REQUIRES |
| | NEW WORK FOR 277/480V TO BE SIGNED AND |
| | SEALED BY AN ENGINEER/PE. |
| | |
| | 2)NOTE: PLEASE SEE MISSING EQUIPMENT |
| | GROUNDING CONDUCTOR(S) FOR TRANSFORMER. |
| | 250.110, SIZED PER 250.122 |
| | PLEASE ALSO SEE 250.30, 250.66 FOR |
| | SIZING OF GROUNDING FOR TRANSFORMER. |
| | |
| | 3)NOTE: PLEASE SEE 210.8B3, 2002 NEC |
| | REQUIRES ALL 15- AND 20-AMPERE, 125-VOLT |
| | RECEPTACLES IN NONDWELLING-TYPE KITCHENS |
| | TO BE GFCI PROTECTED. THIS REQUIREMENT |
| | APPLIES TO EACH AND EVERY 15- AND |
| | 20-AMPERE, 125-VOLT KITCHEN RECEPTACLE, |
| | WHETHER OR NOT THE RECEPTACLE SERVES |
| | COUNTERTOP APPLIANCES. |
| | |
| | 4)NOTE: PLEASE SUBMIT LOAD CALCUALTIONS |
| | FOR NOW ADDING NEW LOADS TO EXISTING |
| | MAIN DIST SYSTEM. |
| | 220 |
| | |
| | 5)NOTE: PLEASE SEE FS 553.80(2)(B) |
| | ATTACHED WITH RESPECT TO DESIGN |
| | PROFESSIONAL AND REPEAT COMMENTS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |