| Date |
Text |
| 2005-07-15 00:00:00 | ************ UNSAT ************* |
| | |
| | |
| | PLEASE SEE A NEW ELECTRICAL RISER FOR |
| | NEW SERVICE IS NOW BEING SUBMITTED. |
| | |
| | 1)NOTE: PLEASE SUBMIT/SHOW AIC RATING |
| | FOR NEW MAIN. IT IS NOTED THAT AIC |
| | RATING IS INDICATED FOR SUB PANEL. |
| | 110.9,215.5 |
| | |
| | 2)NOTE: PLEASE INDICATE SIZE OF EXISTING |
| | METER. PREVIOUS SERVICE RISER INDICATED |
| | 100A'S? NEW MAIN IS 200A'S. |
| | 215.5 |
| | |
| | 3)NOTE: PLEASE SEE NOW AN EQUIPMENT |
| | GROUNDING CONDUCTOR IS SHOWN FROM METER |
| | TO MAIN/FIRST MEANS OF DISCONNECT. |
| | PLEASE SEE 250.6,250.24, EQUIPMENT |
| | GROUNDING CONDUCTORS ARE ONLY INSTALLED |
| | AFTER THE FIRST MEANS OF DISCONNECT. |
| | |
| | 4)NOTE: PLEASE SEE 2002 NEC 210.8B3 |
| | WHICH REQUIRES ALL 15- AND 20-AMPERE, |
| | 125-VOLT RECEPTACLES IN NONDWELLING-TYPE |
| | KITCHENS TO BE GFCI PROTECTED. THIS |
| | REQUIREMENT APPLIES TO EACH AND EVERY |
| | 15- AND 20-AMPERE, 125-VOLT KITCHEN |
| | RECEPTACLE, WHETHER OR NOT THE |
| | RECEPTACLE SERVES COUNTERTOP APPLIANCES. |
| | |
| | 5)NOTE: PLEASE SEE ADDRESS ON PLANS |
| | INDICATE 420 HAMPTON, HOWEVER PERMIT |
| | APPLICATION SHOWS 424 AND OUR SYSTEM |
| | SHOWS 424, PLEASE CORRELATE. |
| | |
| | |
| | PLEASE SEE PLANS ARE COMING ABCK FOR |
| | PLUMBING NOTES, PLEASE MAKE THE ABOVE |
| | CHANGES/CORRECTIONS AT THIS TIME. |
| | |
| | PLEASE REMOVE ANY OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | ONE COPY OF OLD/VOIDED SHEETS SHALL BE |
| | SUBMITTED FOR REFERENCE ONLY. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |