| Plan Review Notes For Permit 05041273 |
| Permit Number |
05041273 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-06-04 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | | | | 1. SUBMIT A SANITARY RISER DIAGRAM SHOW | | | ALL PIPE SIZES, VENTING, AND POINTS OF | | | CONNECTION AND TERMINATION. SECTION | | | 104.3.1.1. | | | 2. SUBMIT A WATER RISER DIAGRAM SHOWING | | | ALL PIPE SIZES, VALVES AND WATER HAMMER | | | ARRESTORS (WHERE REQUIRED BY SECTION | | | 604.9). | | | 3. SUBMIT A DETIAL SHOWING COMPLIANCE | | | WITH SECTION 11-4.24 AND ALL | | | SUBSECTIONS. CLEAR FLOOR SPACE SHALL BE | | | FORWARD APPROACH AND EXTEND A MAXIMUM OF | | | 19" UNDERNEATH THE SINK. | | | 4. A DRINKING FOUNTAIN IS REQUIRED PER | | | TABLE 403.1 | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] | | | |
|