| 2005-04-26 00:00:00 | ************ UNSAT ************ |
| | |
| | 1)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| | PLANS AND CORRELATE WITH THE SUBMITTED |
| | PANEL SCHEDULE. |
| | 215.5 |
| | |
| | 2)NOTE: PLEASE SEE PLANS SHOW TWO |
| | PANELS, PLEASE VERIFY IF ANY CIRCUITING |
| | TO OUT OF SECOND PANEL SHOWN? IF SO, |
| | PLEASE SUBMIT PANEL SCHEDULE AND |
| | CORRELATE. |
| | 215.5 |
| | |
| | 3)NOTE: PLEASE SHOW LOAD CALCULATIONS, |
| | PLEASE SHOW PER |
| | 220.3,220.10,220.11,220.13 ETC. |
| | PLEASE ALSO SHOW ALL CONTINOUS LOADS |
| | AT 125% PER 215.3,230.42 |
| | |
| | 4)NOTE: PLEASE SEE 424.3B FOR MIN OCP |
| | FOR AHU. PLEASE SEE UNTI IS SHWON WITH |
| | 10KW HEAT, 40 OCP AND #8 AWG. |
| | 240.4,310.16 ETC. |
| | |
| | 5)NOTE: PLEASE SEE SERVICE IS SHOWN AS |
| | EXISTING, HOWEVER SERVICE AS SHOWN DOES |
| | NOT MEET CODE COMPLIANCE FOR SEC'S OR |
| | FEEDERS. |
| | PLEASE SEE #4 SHOWN FOR 200A'S. |
| | PLEASE SEE 310.16, 240.4B |
| | |
| | 6)NOTE: PLEASE SEE MISSING EQUIPMENT |
| | GROUNDING CONDUCTOR FROM MAIN TO PANEL. |
| | 250.110,250.122,250.24 ETC. |
| | |
| | 7)NOTE: PLEASE SEE 700.12E FOR |
| | CIRCUITING OF EM/EXT LTS. |
| | |
| | PLEASE SEE OTHER POSSIBLE COMMENTS FROM |
| | OTHER REVIEWER(S) WHICH MAY HAVE AN |
| | AFFECT ON ELECTRICAL PLANS. |
| | |
| | PLEASE REMOVE AN AND ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO COMPLETE SETS FOR REVIEW AND |
| | STAMPING. |
| | |