2005-08-08 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 BUILDING
  
 A. FROM PREVIOUS REVIEW: COMMENT NUMBER
 TO REFLECT NUMBER FROM FIRST REVIEW:
 3. CABINET DOORS ARE STILL SHOWN ON THE
 THE DETAILS 1/A-6, D/A-6 & H/A-6. THE
 CABINET DOORS ARE NOT ALLOWED IN THE
 CLEAR FLOOR SPACE FOR THE SINKS.
 4. SHT A5.0 WALL TO BE NONABSORBENT PER
 SECTION 1204.2. RESPONSE NOTED, BUT
 REQUIREMENT TO USE WATER PROOF EPOXY
 PAINT SHALL BE CALLED OUT IN THE FINISH
 LEGEND OR FINISH NOTES. SECTION 104.2.1.
 5. SHT A6.0 DETAIL #1 TO REFLECT FIG. 31
 CHAPTER 11. INDICATE ALL MEASUREMENTS AS
 SHOWN IN FIG. 31. (SEE DETAIL 13/A9.0) -
 RESPONSE NOTED, BUT LAYOUT STILL DOES
 NOT COMPLY. 27" MEASUREMENT FOR
 CLEARANCE SHOWN ABOVE THE SINK.
 **NEW COMMENT** SINK DEPTH TO BE 6-1/2"
 MAXIMUM. PLEASE INDICATE ON DETAIL.
 11-4.24.4
  
 NEW COMMENT:
 1B. SEE ATTACHED SHEET CONCERNING THE
 DESIGN PROFESSIONAL AND FS 533.80(2)(B).
  
  
 REVIEW BY KEN STEVENS