Text |
| 2005-06-09 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FBC-2001 BUILDING |
| | |
| | 1. SHT A1.0 IN THE INSTALLATION OR |
| | REMOVAL OF ANY PART OF THE DRAINAGE |
| | SYSTEM, DEAD ENDS SHALL BE PROHIBITED. |
| | SECTION 704.5 - ALL DEMO'D PIPING SHALL |
| | BE INSPECTED PRIOR TO COVERING. |
| | 2. SHT A3.0 MINIMUM FACILITIES TABLE |
| | 403.1. 3 DRINKING FOUNTAINS ARE REQUIRED |
| | BUT ONLY 2 ARE SHOWN. |
| | 3. SHT A3.0 SHOW CLEAR FLOOR SAPCE FOR |
| | ALL ACCESSIBLE FIXTURES IN THE TOILET |
| | ROOMS AND LOUNGES. PER SECTIONS 11-4.16, |
| | 11-4.19, 11-4.22, & 11-4.24. THE CLEAR |
| | FLOOR SPACE FOR THE LOUNGE SINKS SHALL |
| | BE FORWARD APPROACH AND EXTEND A MAXIMUM |
| | OF 19" UNDERNEATH THE SINK. CABINET |
| | DOORS ARE NOT APPROVED AS THEY WILL BE |
| | IN THE CLEAR FLOOR SPACE OF THE FIXTURE. |
| | OPENING UNDER THE SINK SHALL BE MINIMUM |
| | OF 30" AND SHALL BE INDICATED ON PLANS. |
| | 4. SHT A5.0 WALL TO BE NON-ABSORBENT PER |
| | SECTION 1204.2. INDICATE HOW PAINTED GWB |
| | WILL COMPLY WITH THIS REQUIREMENT. ROOMS |
| | 119A, 120, 187, & 188. |
| | 5. SHT A6.0 DETAIL #1 TO REFLECT FIG 31 |
| | CHAPTER 11. TOE CLEARANCE 6" MAX, PLANS |
| | TO 1'0". (SEE DETAIL 13/A9.0). |
| | 6. SHT P0.1 DOMESTIC WATER ISOMETRIC, |
| | WATER HAMMER ARRESTORS SHALL BE LOCATED |
| | NEAR THE FIXTURE IN AN "EFFECTIVE RANGE" |
| | NOT IN THE CEILING AS SHOWN. PDI-WH 201 |
| | - SANT. ISOMETRIC INDICATES ROOM 186, |
| | BUT NEEDS TO BE FOR ROOM 188. PLEASE |
| | CORRECT. SECTION 104.2.1. |
| | 7. SHT P2.1 ANY PORTION OF THE DRAINAGE |
| | SYSTEM INSTALLED UNDERGROUND SHALL BE |
| | NOT LESS THAN 2" IN DIAMETER. THE |
| | CONDENSATE LINES INDICATE 3/4", 1-1/4" & |
| | 1-1/2" UNDERGROUND PIPING. SECTION 710.3 |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |