2005-05-10 00:00:00PASSED
  
  
 1) IN THE CITY OF WEST PALM BEACH, DUCT
 SMOKE DETECTORS SHALL BE WIRED INTO THE
 FIRE ALARM PANEL TO INITIATE A GENERAL
 FIRE ALARM, NOT SUPERVISORY SIGNAL.
  
 2) NEW FIRE ALARM SYSTEMS SUPERVISING A
 SPRINKLER SYSTEM SHALL BE UL CERTIFIED
 FOR CENTRAL STATION SERVICE.
  
 3) SEPARATE SHOP DRAWING AND PERMITS ARE
 REQUIRED FOR FIRE ALARM AND FIRE
 SPRINKLER REMODELS.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 835-2910 OR 805-6722