| Plan Review Notes For Permit 05041212 |
| Permit Number |
05041212 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-05-10 00:00:00 | PASSED | | | | | | | | | 1) IN THE CITY OF WEST PALM BEACH, DUCT | | | SMOKE DETECTORS SHALL BE WIRED INTO THE | | | FIRE ALARM PANEL TO INITIATE A GENERAL | | | FIRE ALARM, NOT SUPERVISORY SIGNAL. | | | | | | 2) NEW FIRE ALARM SYSTEMS SUPERVISING A | | | SPRINKLER SYSTEM SHALL BE UL CERTIFIED | | | FOR CENTRAL STATION SERVICE. | | | | | | 3) SEPARATE SHOP DRAWING AND PERMITS ARE | | | REQUIRED FOR FIRE ALARM AND FIRE | | | SPRINKLER REMODELS. | | | | | | | | | MIKE WENNERGREN, A/CAPTAIN | | | WPBFR(561) 835-2910 OR 805-6722 |
|