| Plan Review Notes For Permit 05041212 |
| Permit Number |
05041212 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-05-16 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)PROVIDE MANEUVERING CLEARANCE ON | | | THE PLAN FOR DOOR 102, PUSH SIDE. | | | | | | 2.)FLORIDA STATE OR LOCAL PRODUCT | | | APPROVALS REQUIRED AS WELL AS TEST | | | REPORT WITH INSTALLATION INSTRUCTIONS OR | | | NOA, FAC9B72 (STOREFRONT WINDOW). | | | | | | 3.)IMPACT PROTECTION REQUIRED | | | FBC1606.1.4.IF THE STOREFRONT WINDOW | | | IS NOT IMPACT, SUBMIT PRODUCT APPROVALS | | | FOR SHUTTERS AND SHOW ON THE PLAN WHERE | | | THEY WILL BE STORED.IF THEY ARE STORED | | | VERTICALLY, PROVIDE A RACK DETAIL. | | | | | | 4.)THE SQUARE FOOTAGE ON THE ENERGY | | | CALC DOESN'T MATCH THE PLAN. | | | | | | 5.)THE LOUNGE SINKS A6 ARE TO COMPLY | | | WITH FBC11-4.24. |
|