| Plan Review Notes For Permit 05041195 |
| Permit Number |
05041195 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2005-08-03 00:00:00 | DENIED | | | REFERENCE: FBC-2001 CHAPTER 1 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | A. FROM PREVIOUS REVIEW: | | | 1. SHT P-1 ALL FIXTURES THAT HAVE BEEN | | | REMOVED, MOVED, OR ADDED SHALL BE SHOWN | | | ON THE RISER DIAGRAM THAT REFLECTS THE | | | CHANGE. THE SINK IN THE HALLWAY NEXT TO | | | THE DINING ROOM IS NOT SHOWN ON THE | | | RISER DIAGRAM. - SHT A-2 INDICATES THAT | | | THIS SINK HAS BEEN RELOCATED FROM THE | | | MASTER BEDROOM AND SHT A-1 DOES NOT SHOW | | | A SINK AS EXISTING. SHT P-1 INDICATES | | | THAT THIS IS AN EXISTING SINK. PLEASE | | | CORRELATE ARCHITECTURAL SHEETS AND | | | PLUMBING SHEET. SECTIONS 104.2.1 AND | | | 104.3.1.1. | | | 2. ALL MEP SHEETS - ENGINEERS SHALL | | | INDICATE THEIR CERTIFICATE OF | | | AUTHORIZATION ON EACH SHEET. FAC | | | 61G15-23.002(2) & FS 471.025. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|