| 2005-04-21 00:00:00 | ********** UNSAT ********** |
| | |
| | 1)NOTE: PLEASE PROVIDE LOAD CALCULATIONS |
| | FOR EXISTING PANEL/SERVICE PER 220.31B |
| | |
| | 2) NOTE: PLEASE SEE MISSING RECEPT REQ'D |
| | FOR A/C EQUIPMENT. 210.63 |
| | |
| | 3)NOTE: PLEASE SEE MISSING LIGHTING |
| | REQUIRED FOR AHU. 210.70 |
| | |
| | 4)NOTE: PLEASE SEE MISSING A/C DISC'S |
| | PER 440.11. |
| | |
| | 5)NOTE: PLEASE SEE MISSING RECEPTS PER |
| | 210.52 |
| | |
| | 6)NOTE: PLEASE SEE MISSING MEANS OF |
| | EGRESS CONTROL FOR LIGHTING. PLEASE SEE |
| | CONTROL FOR ENTERING NEW LIVING FROM |
| | EXIST OFFICE(3-WAY SW?). PLEASE ALSO SEE |
| | EGRESS CONTROL AND FIXTURE REQUIRED FOR |
| | EGRESS FROM NEW LIVING RM AREA TO |
| | OUTSIDE. |
| | BOTH PER 210.70 |
| | |
| | 7)NOTE: PLEASE SEE MISSING REQUIRED |
| | LICENSE INFORMATION ON TITLE BLOCKS PER |
| | FAC 61G1-16.004 AND FS 481.219 |
| | PLEASE SEE THIS COMMENTS IS REQUIRED FOR |
| | ALL SHEETS AND FOR ALL TRADES WHEATHER |
| | OR NOT COMMENT IS MADE BY OTHER |
| | REVIEWER(S). |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | ONE SET OF OLD SHEETS SHOULD BE |
| | SUBMITTED FOR REFERENCE ONLY. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |