Plan Review Notes
Plan Review Notes For Permit 05041142
Permit Number 05041142
Review Stop E
Sequence Number 1
Notes
Date Text
2005-04-21 00:00:00********** UNSAT **********
  
 1)NOTE: PLEASE PROVIDE LOAD CALCULATIONS
 FOR EXISTING PANEL/SERVICE PER 220.31B
  
 2) NOTE: PLEASE SEE MISSING RECEPT REQ'D
 FOR A/C EQUIPMENT. 210.63
  
 3)NOTE: PLEASE SEE MISSING LIGHTING
 REQUIRED FOR AHU. 210.70
  
 4)NOTE: PLEASE SEE MISSING A/C DISC'S
 PER 440.11.
  
 5)NOTE: PLEASE SEE MISSING RECEPTS PER
 210.52
  
 6)NOTE: PLEASE SEE MISSING MEANS OF
 EGRESS CONTROL FOR LIGHTING. PLEASE SEE
 CONTROL FOR ENTERING NEW LIVING FROM
 EXIST OFFICE(3-WAY SW?). PLEASE ALSO SEE
 EGRESS CONTROL AND FIXTURE REQUIRED FOR
 EGRESS FROM NEW LIVING RM AREA TO
 OUTSIDE.
 BOTH PER 210.70
  
 7)NOTE: PLEASE SEE MISSING REQUIRED
 LICENSE INFORMATION ON TITLE BLOCKS PER
 FAC 61G1-16.004 AND FS 481.219
 PLEASE SEE THIS COMMENTS IS REQUIRED FOR
 ALL SHEETS AND FOR ALL TRADES WHEATHER
 OR NOT COMMENT IS MADE BY OTHER
 REVIEWER(S).
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE SET OF OLD SHEETS SHOULD BE
 SUBMITTED FOR REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  