| Plan Review Notes For Permit 05041102 |
| Permit Number |
05041102 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-04-21 00:00:00 | REVISION: DELETED GAS LIGHTS, INCREASED | | | DRYER AND WATER HEATER BTU SIZE. | | | | | | IF DRYER ROOM IS A CONFINED SPACE, | | | OPENINGS REQUIRED PER SECTION 304.5 OR | | | SECTION 304.6 SHALL BE INSTALLED. | | | MINIMUM 1,500 CUBIC FEET REQUIRED. | | | | | | IF WATER HEATER ROOM IS A CONFINED SPACE | | | OPENINGS REQUIRED PER SECTION 304.5 OR | | | SECTION 304.6 SHALL BE INSTALLED. | | | MINIMUM 7,000 CUBIC FEET REQUIRED. |
|