| 2005-04-21 00:00:00 | *********** UNSAT ********** |
| | |
| | |
| | 1)NOTE: PLEASE LIST ALL THE REQ'D |
| | DEDICATED BATH(S) CIRCUIT(S) ON PANEL |
| | SCHEDULE. PER 210.52D, 210.11C3 |
| | PLEASE SEE THESE ARE SHOWN AS 15A, |
| | PLEASE ALSO SEE NO WIRE SIZES ARE SHOWN |
| | ON PANEL SCHEDULE. |
| | |
| | 2 )NOTE: PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CURCUIT(S) ON PANEL |
| | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| | IN BEDROOMS ARE TO BE PROTECTED , |
| | INCLUDING, LTS, RECEPTS, SD'S ETC. |
| | PLEASE SEE 210.12 2002 NEC. |
| | |
| | 3)NOTE: PLEASE SEE MISSING RECEPT(S) PER |
| | 210.52 FOR WALL SPACE IN BEDRM. IF |
| | EXSITING PLEASE LABEL. |
| | |
| | 4)NOTE: PLEASE CLARIFY NEW OR EXISTING |
| | SD'S REQUIRED INSIDE AND OUT SIDE |
| | BEDROOM. NFPA-72 8-1.4.1.6.2 |
| | |
| | 5)NOTE: PLEASE SEE MISSING GFI RECEPT |
| | W/IN 3' OF SINK/LAV EDGE. |
| | 210.52 |
| | |
| | 6)NOTE: PLEASE SEE PLANS ARE SHOWING |
| | PANEL, SUB PANELS ETC, HOWEVER THERE IS |
| | NO INDICATION IF THESE ARE EXISTING. ? |
| | PLEASE INCLUDE A COMPLETE RISER DIAGRAM |
| | 310.16,240.4,250.50,110.9 ETC. |
| | |
| | 7)NOTE: PLEASE SEE PANEL AND MCB IS |
| | SHOWN AS 210A'S? PLEASE SEE 240.6, 210A |
| | OCP IS NOT A COMMON OCP SIZE. |
| | PLEASE ADJUST. |
| | |
| | 8)NOTE: PLEASE VERIFY NEW OR EXISTING |
| | EGRESS LIGHTING REQUIRED IN BEDRM. |
| | 210.70,LS 101 5-8 |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | PLEASE SUBMIT ONE SET OF OLD/VOIDED |
| | SHEETS FOR REFERENCE ONLY. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |