Plan Review Notes
Plan Review Notes For Permit 05040985
Permit Number 05040985
Review Stop E
Sequence Number 1
Notes
Date Text
2005-04-21 00:00:00*********** UNSAT **********
  
  
 1)NOTE: PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
 PLEASE SEE THESE ARE SHOWN AS 15A,
 PLEASE ALSO SEE NO WIRE SIZES ARE SHOWN
 ON PANEL SCHEDULE.
  
 2 )NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
 PLEASE SEE 210.12 2002 NEC.
  
 3)NOTE: PLEASE SEE MISSING RECEPT(S) PER
 210.52 FOR WALL SPACE IN BEDRM. IF
 EXSITING PLEASE LABEL.
  
 4)NOTE: PLEASE CLARIFY NEW OR EXISTING
 SD'S REQUIRED INSIDE AND OUT SIDE
 BEDROOM. NFPA-72 8-1.4.1.6.2
  
 5)NOTE: PLEASE SEE MISSING GFI RECEPT
 W/IN 3' OF SINK/LAV EDGE.
 210.52
  
 6)NOTE: PLEASE SEE PLANS ARE SHOWING
 PANEL, SUB PANELS ETC, HOWEVER THERE IS
 NO INDICATION IF THESE ARE EXISTING. ?
 PLEASE INCLUDE A COMPLETE RISER DIAGRAM
 310.16,240.4,250.50,110.9 ETC.
  
 7)NOTE: PLEASE SEE PANEL AND MCB IS
 SHOWN AS 210A'S? PLEASE SEE 240.6, 210A
 OCP IS NOT A COMMON OCP SIZE.
 PLEASE ADJUST.
  
 8)NOTE: PLEASE VERIFY NEW OR EXISTING
 EGRESS LIGHTING REQUIRED IN BEDRM.
 210.70,LS 101 5-8
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 PLEASE SUBMIT ONE SET OF OLD/VOIDED
 SHEETS FOR REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  
  