Notes
Date Text
2005-05-03 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE. - PIPE SIZING OUT OF THE
 PRV THRU THE TEE FOR CHAR GRILLE IS
 SHOWN AS 1" BUT SHALL BE 1-1/4" PER
 TABLE 402(2)
 2. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34). - GAS CLACULATIONS SHOW
 DIFFERENT BTU RATINGS FOR CHAR GRILLE
 AND GRIDDLE THAN IS SHOWN ON THE
 ISOMETRIC. PLEASE CORRELATE CALCULATIONS
 & ISOMETRIC. SECTION 104.2.1.
 3. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 4. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. - SHOW THE
 UNION ON THE ISOMETRIC. SECTION 104.2.1.
 5. GAS PERMIT SHALL NOT BE ISSUED UNTIL
 ARCHITECTURAL PLANS SHOWING THE FLOOR
 PLAN WITH ALL SEATING, SQUARE FOOTAGE OF
 INTERIOR, EXISTING TOILET ROOM
 FACILITIES ECT. INDICATE IF ALL KITCHEN
 FACILITIES ARE EXISTING OR NEW. THESE
 PLANS SHALL BE ROUTED TO DBPR DEPT. OF
 BUSINESS REGULATION HOTEL & RESTURANT
 DIVISION. TWO SETS OF PLANS SHALL BE
 STAMPED BY DBPR PLAN REVIEW AND HAVE THE
 TWO PAGE "WORK SHEETS" ATTACHED. SECTION
 101.4.7.
 6) CERTIFICATE OF AUTHORIZATION IS
 REQUIRED FOR METRO DESIGN REFERENCED IN
 THE TITLE BLOCK. FAC61G15-23.002(2) AND
 FS 471.025.
  