Plan Review Notes
Plan Review Notes For Permit 05040962
Permit Number 05040962
Review Stop E
Sequence Number 1
Notes
Date Text
2005-04-25 00:00:00**** UNSAT ****
  
 1)NOTE: PLEASE CLARIFY PANEL SHOWN FOR
 CIRCUITING IS LABLED 11LB AND RISER
 DIAGRAM DOES NOT REFLECT THIS PANEL.
 PLEASE ALSO SEE NOTE(S) ON REFERENCE
 CIRCUITING TO BE IN PANEL 12LAA.?
  
 PLEASE CORRELATE AND SUBMIT THE ABOVE
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717