| 2005-06-03 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL CODE |
| | FBC-2001 BUILDING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. PLANS SHALL BE ROUTED TO DBPR HOTEL & |
| | RESTURANT DIVISION FOR REVIEW PRIOR TO |
| | RESUBMITTING TO THE CITY WPB FOR REVIEW. |
| | SUBMIT A MINIMUM OF 3 SETS OF PLANS |
| | STAMPED BY DBPR WITH THE TWO PAGE "WORK |
| | SHEETS" ATTACHED TO EACH SET. SECTION |
| | 101.4.7. |
| | 2. INDICATE IF FOOD WILL BE PREPARED ON |
| | SITE OR IF ALL FOOD WILL BE PREPACKAGED |
| | FOOD FOR COMSUMPTION. TO DETERMINE IF A |
| | GREASE INTERCEPTOR IS REQUIRED CONTACT |
| | RODNEY COMPO, ENVIRONMENTAL COMPLIANCE. |
| | (561) 473-4074, FAX (561) 659-7458, OR |
| | E-MAIL [email protected]. PLEASE SUBMIT HIS |
| | DETERMINATION WITH PLANS. |
| | 3. SHT A-0.04 SEPARATE POOL PERMIT |
| | REQUIRED. SECTION 104.1.1. |
| | 4. SHT A0.06 TUB & SHOWER DETAIL, SHOW |
| | MEASURMENTS FOR CONTROLS. SECTIONS |
| | 11-4.20.5 & 11-4.21.5. |
| | 5. SHTS A-2.01 & A-2.02 TOILET ROOMS. |
| | SHOW CLEAR FLOOR SPACE FOR EACH |
| | ACCESSIBLE FIXTURE. SHOW TURNING AREA IN |
| | EACH TOILET ROOM, NOT REQUIRED IN STALL. |
| | SECTION 11-4.22.3 |
| | 6. SHTS A-2.01 & A-2.02 SUBMIT |
| | CALCULATIONS FOR MINIMUM FACILITIES PER |
| | TABLES 1103.1 & 403.1 FOR ALL COMMON |
| | AREAS. SHOW THE SQUARE FOOTAGE OF EACH |
| | COMMON AREA ON THE FLOOR PLAN. |
| | 7. SHT A-2.02 SINK IN EMPLOYEE BREAK |
| | ROOM SHALL COMPLY WITH SECTION 11-4.24 |
| | AND ALL SUBSECTIONS. (FORWARD APPROACH |
| | IS REQUIRED MAXIMUM 19" UNDERNEATH THE |
| | SINK. SINK SHALL BE CENTERED ON THE 30" |
| | WIDTH OF THE CLEAR FLOOR SPACE). |
| | 8. PER TABLE 403.1 A SERVICE SINK IS |
| | REQUIRED. |
| | 9. SHTS A-2.10 & A-2.11 SEE COMMENT #5 |
| | CONCERNING REQUIRED TURNING AREA. |
| | 10. ALL RAIN WATER DOWNSPOUTS AND |
| | CONDENSATE SHALL DRAIN A MINIMUM OF 1FT |
| | FROM THE STRUCTURAL WALL. SECTION |
| | 1503.4.4. |
| | 11. SHT A-8.04 DETAIL #11 SHOW THE |
| | FOLLOWING TO SHOW COMPLIANCE: FOR THE |
| | W/C: |
| | A. HEIGHT 11-4.16.3 |
| | B. GRAB BARS 11-4.16.4 |
| | C. FLUSH CONTROLS 11-4.16.5 |
| | LAV: |
| | A. HEIGHT & CLEARANCES 11-4.19.2 |
| | B. EXPOSED PIPES & SURFACES 11-4.19.4 |
| | C. FAUCETS 11-4.19.5 |
| | DETAIL #10 SAME AS FOR DETAIL #11 PLUS |
| | URINAL: |
| | A. HEIGHT 11-4.18.2 |
| | B. FLUSH CONTROLS 11-4.18.4 |
| | DETAIL #5 SAME AS #11 EXCEPT FOR SECTION |
| | 11-4.19.4 EXPOSED PIPES & SURFACES. |
| | 12. SHT P-2.01 GENERAL NOTES: |
| | #2 GOVERNING CODE IS FBC-2001 NOT 2002 |
| | OBC OR 2002 OHIO PLUMBING CODE. PLEASE |
| | CORRECT. |
| | #12 REVISIONS WILL BE REQUIRED FOR ALL |
| | CHANGES TO A SIGNED/SEALED/DATED SET OF |
| | PLANS. |
| | #27 AIR CHAMBERS ARE NOT APPROVED PER |
| | SECTION 604.9. DELETE FROM REFERENCE. |
| | #29 CONDENSATE SHALL BE PIPED |
| | SEPARATELY FROM THE BUILDING AND |
| | CONNECTED TO STORM, A CATCH BASIN OR TO |
| | DRYWELL/PLANTED AREA. |
| | 13. SHT P-2.01 PIPING SCHEMATIC AT WATER |
| | HEATERS: |
| | A. 160 DEGREE TO AIR HANDLERS, SHOWS |
| | WATER GOING TO THE AIR HANDLERS, BUT NO |
| | RETURN. PLEASE CLARIFY SECTION 104.2.1. |
| | - A CHECK OF THE MECHANICAL PLANS DOES |
| | NOT SHOW 160 DEGREE WATER PIPED TO THE |
| | AIR HANDLERS. PLEASE SUBMIT A DETAIL AND |
| | MORE INFORMATION ON THIS SYSTEM. SECTION |
| | 104.2.1. |
| | B. T&P DRAINAGE SHALL DRAIN TO A FLOOR |
| | SINK OR HUB DRAIN. FLOOR DRAINS ARE NOT |
| | APPROVED INDIRECT WASTE RECEPTORS. |
| | SECTIONS 802.3 & 802.3.2. |
| | C. DIELECTRIC UNIONS ARE NOT APPROVED |
| | FOR WATER PIPING USAGE. DIELECTRIC |
| | COUPLINGS SHALL BE USED. |
| | D. 2-1/2" STUB OUTS W/BY-PASS FOR |
| | FUTURE SOFTENER (HOT WATER ONLY) APPEARS |
| | TO BE ON THE COLD WATER INLET PIPING. |
| | PLEASE CLARIFY. SECTION 104.2.1. |
| | 14. SHTS P-3.01, P-3.02, & P-3.03 SANT. |
| | RISER DIAGRAMS, TUBS AND SHOWERS REQUIRE |
| | A TRAP. SECTION 1002.1. - RISER DIAGRAMS |
| | DO NOT REFLECT THE FLOOR PLANS. PLEASE |
| | SUBMIT RISER DIAGRAMS IN AN ISOMETRIC |
| | FORM THAT REFLECT THE FLOOR PLAN, AND |
| | MEET CODE REQUIREMENTS. SHOW ALL PIPE |
| | SIZES, VENTS AND DFU FOR EACH RISER. |
| | SECTION 104.2.1. |
| | 15. SUBMIT A BUILDING DRAIN SANITARY |
| | ISOMETRIC SHOWING ALL PIPE SIZES, DFU'S |
| | AS THEY ACCUMULATE IN THE SYSTEM, AND |
| | SHOW RISER LOCATIONS WITH RISER |
| | DESIGNATION NUMBERS. SECTIONS 104.2.1 & |
| | 104.3.1.1. |
| | 16. SHTS P3.04, P-3.05, & P-3.06 WATER |
| | RISER DIAGRAMS, FULL OPEN VALVES ARE |
| | REQUIRED ON THE BASE OF EVERY WATER |
| | RISER PIPE. SECTION 606.1(3). |
| | 17. SUBMIT A WATER RISER DIAGRAM IN |
| | ISOMETRIC FORM FOR THE LAUNDRYAND ALL |
| | COMMON AREAS SHOWING ALL PIPE SIZES, |
| | VALVES, AND WATER HAMMER ARRESTORS, |
| | (WHERE REQUIRED BY SECTION 604.9). |
| | 18. SUBMIT A WATER RISER DIAGRAM IN |
| | ISOMETRIC FORM FOR THE WATER |
| | DISTRIBUTION SYSTEM SHOWING THE LOCATION |
| | OF THE WATER ENTERING THE BUILDING, ALL |
| | PIPING NOT SHOWN ON RISERS, ALL PIPE |
| | SIZES, WATER HAMMER ARRESTORS, LOCATION |
| | OF WATER RISERS CONNECTING TO |
| | DISTRIBUTION LINE WITH RISER DESIGNATION |
| | NUMBERS ECT. SECTIONS 104.2.1 AND |
| | 104.3.1.1. |
| | 19. SUBMIT A CONDENSATE RISER DIAGRAM |
| | SHOWING ALL PIPE SIZES, MATERIAL, AND |
| | TERMINATION POINT. SECTIONS 104.2.1. & |
| | 104.3.1.1. |
| | 20. THE FOLLOWING INFORMATION IS |
| | REQUIRED FOR A GAS PERMIT: |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | FUEL GAS CODE. |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE IF BEING USED. |
| | C. TYPE OF GAS, (LP OR NATURAL) |
| | D. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2001 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.5.2 AND TABLES 402(1) THRU |
| | 402(34). |
| | E. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES (A)(3). |
| | F. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES (A)(3). |
| | G. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2001 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2001 FUEL GAS CODE SEC 402.2 |
| | I. CLEARLY SHOW THE LOCATION AND CAP- |
| | ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| | OR ASME), THE DISTANCE OF THE TANK FROM |
| | THE BUILDING AND ADJACENT PROPERTY LINES |
| | THE DISTANCE OF THE TANK FROM ALL SOUR- |
| | CES OF IGNITION, OTHER CONTAINERS, BUILD |
| | INGS, AND THE LOCATION OF ANY BUILDING |
| | OPENINGS BELOW THE RELIEF VALVE OF THE |
| | TANK PER NFPA 58, TABLE 3-2.2.2. |
| | J. CLEARLY INDICATE ON THE PLAN IF THE |
| | LP TANK IS ABOVE OR BELOW GROUND, AND |
| | SHOW REQUIRED PROTECTION OF THE TANK AND |
| | APPURTENANCES PER NFPA 58. IF THE TANK |
| | IS BELOW GROUND THE CONTAINER SHALL BE |
| | SECURILY ANCHORED PER NFPA 58 SECTION |
| | 3-2.2.7(H). |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |