Plan Review Notes
Plan Review Notes For Permit 05040948
Permit Number 05040948
Review Stop E
Sequence Number 1
Notes
Date Text
2005-05-03 00:00:00*********** UNSAT *************
  
 ** REVIEW FOR STAYBRIDGE SUITES ***
 THIS IS UBMITTED FOR PLAN REVIEW ONLY
 AND NOT SUBMITTED FOR PERMIT.
 PLEASE SEE THIS WAS SUBMITTED UDNER THE
 SAME ADDRESS AS THE "FAIRFILED INN
 SUITES".
  
 1)NOTE: PLEASE SEE 240.4C
 WHERE THE OVERCURRENT DEVICE IS RATED
 OVER 800 AMPERES, THE AMPACITY OF THE
 CONDUCTORS IT PROTECTS SHALL BE EQUAL TO
 OR GREATER THAN THE RATING OF THE
 OVERCURRENT DEVICE DEFINED IN 240.6.
 PLEASE SEE CONDUCTORS SHOWN ARE ONLY
 RATED FOR 2100A'S.
 310.15,110.14C1
  
 2)NOTE: PLEASE IDENTIFY FOOTER STEEL AS
 PART OF THE GROUNDING ELECTRODE SYSTEM
 AS REQUIRED UNDER 250.50.
  
 3)NOTE: PLEASEMSB MAY HAVE AN
 ADDITIONAL "SHUNT TRIP" , HOWEVER THE
 MCB MUST STILL MEET 230.76,230.79.
 PLEASE NOTE ON PLANS/RISER/PANEL
 SCHEDULE.
  
 4)NOTE: PLEASE SEE FEEDERS SHOWN ON
 RISER DIAGRAM FOR PANEL "M". THIS NOTES
 FEEDER SCHEDULE #28. PLEASE SEE OCP FROM
 MSB IS 600A'S AND FEEDER IS ONLY RATED
 FOR 380A'S.
 310.16,240.4
  
 5)NOTE: PLEASE SEE GROUND FLR ELECTRICAL
 ROOM DOORS. PLEASE SEE REQUIRED
 "OUT-SWING" FOR DOORS PER 110.26. PLEASE
 ALSO NOTE ON PLANS FOR PANIC HARDWARE
 REQUIRED ETC.
  
 6)NOTE: PLEASE CLARIFY ARC FAULT
 PROTECTION PER 210.12 2002 NEC.
 PLEASE SEE INDIVIDUAL UNITS ARE NOT
 LABELED FOR CIRCUITING, IT IS UNCLEAR
 WHEATHER ARC FAULT PROTECTION IS
 PROVIDED FOR ALL RECEPTS, LTS ETC.
  
 7)NOTE: PLEASE PROVIDE CIRCUITING ON
 UNIT LAYOUTS AND COORELATE WITH THE
 PANEL SCHEDULES SUBMITTED.
 CIRCUITING SHOWN ON POWER PLANS DO NOT
 ISOLATE.
  
 8)NOTE: PLEASE SEE 2002 NEC FOR GFI
 PROTECTION OF RECEPTS IN KITCHENS.
 PLEASE SEE KITCHEN AREA IN BREAKRM, AND
 KITCHEN AREA FOR BUFFET AREA.
 210.8B3
  
 9)NOTE: PLEASE SEE 210.60, ALL RECEPTS
 IN "GUEST RMS" AND SUITES ARE TO MEET
 210.52. PLEASE SEE THERE ARE SOME
 EXCEPTIONS PERMITTED, HOWEVER THERE
 APPEARS TO BE SOME MISSING.
 PLEASE SEE 2' OF WALL SPACES WOULD BE
 REQUIRED UNDER 210.52, PLEASE SEE
 PENINSULAR IN KITCHENS ALSO PER 210.52C3
  
 10)NOTE: PLEASE PROVIDE WIND LOADING FOR
 SITE LIGHTING POLES.
 THIS WILL BE REQUIRED AT THIS TIME AND
 REVIEWED BY BLDG PLAN REVIEW TO MEET FBC
 140MPH.
  
 11)NOTE: PLEASE CLARIFY WHERE ELEVATOR
 MACHINE RM LIGHTING CAN BE LOCATED.
 PLEASE SEE 620.23,24 FOR MIN REQUIRED
 BRANCH CIRCUITS. ELEV CLOSET RECEPT
 BRANCH CIRCUIT WAS LOCATED.
  
 12)NOTE: PLEASE SEE PANEL "P" MENTIONS
 "IN ELECTRICAL ROOM" BUT THIS PANEL
 COULD NOT BE LOCATED ON PLANS IN ANY OF
 THE ELECTRICAL ROOMS SHOWN. PLEASE
 CLARIFY??
 215.5
  
 13)NOTE: PLEASE BE SURE TO SEE ANY
 POSSIBLE COMMENTS FROM OTHER REVIEWER(S)
 WHICH MAY HAVE AN AFFECT ON ELECTRICAL
 PLANS.
  
 14)NOTE: PLEASE BE SURE TO REMOVE ANY
 OLD/VOIDED SHEETS AND ONLY INSERT NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
2005-05-02 00:00:00NOTES TO FOLLOW.5/2/05
2005-04-27 00:00:001 ROLL IN ELEC FOR REVIEW.