Plan Review Notes
Plan Review Notes For Permit 05040948
Permit Number 05040948
Review Stop B
Sequence Number 1
Notes
Date Text
2005-05-24 00:00:00BUILDING PLAN REVIEW
 PERMIT:05040948"STAYBRIDGE"
 ADD: 2200 45TH STREET
 CONT: PLAN REVIEW
 TEL: (727)639-3598
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) ONCE PLANS ARE READY FOR ISSUANCE A
 NOC WILL BE REQUIRED.PROVIDE NOC
 RECORDED WITH THE CLERK OF COURT BEFORE
 A PERMIT CAN BE ISSUED.
  
 2)FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL
 IS NOT DEFINITLY KNOWN OR IS IN QUESTION
 THE BUILDING OFFICIAL MAY REQUIRE EXPLOR
 ATIONS, TEST OR OTHER ADEQUATE PROOF AS
 TO THE PERMISSIBLE SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL
 PROPERLY LICENSED IN THE STATE OF
 FLORIDA.
  
 3) FL S. S. 553.71(7) " THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN
 CY CLASSIFICATION AS DEINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS
 5,000 SQ FT IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
 105.13.1 THE ENFORCING AGENCY SHALL
 REQUIRE A SPECIAL INSPECTOR TO PERFORM
 SRUCTURAL INSPECTIONS ON A THRESHOLD
 BUILDING PURSUANT TO A STRUCTURAL INSPEC
 TION PLAN PREPARED BY THE ENGINEER OF
 RECORD. THE STRUCTURAL INSPECTION PLAN
 MUST BE SUBMITTED TO THE ENFORCING AGEN-
 CY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESH-
 OLD BUILDING. THE PURPOSE OF THE SRUCTUR
 AL INSPECTION PLAN IS TO PROVIDE SPECIF-
 IC INSPECTION PROCEDURES AND SCHEDULES
 SO THAT THE BUILDING CAN BE ADEQUATELY
 INSPECTED FOR COMPLIANCE WITH THE
 PERMITTED DOCUMENTS.
  
 4) WPB AMENDMENT 105.13.6. W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A
 SPECIAL INSPECTOR AS REQUIRED BY S.
 553.79(5) FLORIDA STATUTES TO THE MIN-
 IMUM INSPECTIONS REQUIRED BY THIS CODE.
 CONTACT HAROLD PISKURA MANAGER OF THE
 SPECIAL INSPECTOR PROGRAM AT (561)
 805-6711 FOR FURTHER INFORMATION BEFORE
 THE PERMIT MAY BE ISSUED.
  
 5)W.P.B. AMENDMENT 105.13.4.4 ALL
 PLANS FOR THE BUILDING WHICH ARE
 REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CON-
 TAIN A STATEMENT THAT, TO THE BEST OF
 THE ARCHITECT'S PR ENGINEER'S KNOWLEDGE,
 THE PLANS AND SPECIFICATIONS COMPLY WITH
 THE APPLICABLE FIRE-SAFETY STANDARDS AS
 DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 6) NOTE, FOR ALL PLANS, REPORTS, PRODUCT
 APPROVALS, SHOP DRAWINGS REVISIONS AND
 SUBMITTALS PROVIDE (3) COPIES OF ALL
 DOCUMENTS.
  
 7) FBC 13-103.1.2 BEFORE A BUILDING
 PERMIT CAN BE ISSUED, THE SUBMITTED
 ENERGY CODE COMPLIANCE FORMS SHALL BE
 SIGNED BY THE BUILDING OWNER, THE
 OWNER'S ARCHETECT OR OTHER AUTHORIZED
 AGENT LEGALLY DESIGNATED BY THE OWNER.
 THE P.E. DID SIGN THE ENERGY FORM BUT
 WHEN SUBMITTED FOR PUBLIC RECORD:
 PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 8) SHEET 0.02 BUILDING DATA, TYPE V,
 1 HR PROTECTED/ "SPRINKLERED". SEE TABLE
 600 FOR RATING.
  
 9) SHEET INDEX PLANS INDICATE THAT THE
 BUILDING IS TO BE FIRE SPRINKLERED,
 PROVIDE PLANS AND CALCULATIONS.
 903.8.1. ANY BUILDINGS WHICH IS 3
 STORIES OR MORE HEIGHT SHALL BE EQUIPPED
 WITH AN APPROVED AUTOMATIC SPRINKLER
 SYSTEM IN ACCORDANCE WITH 903.1.NOTE FOR
 A (4) STORY BUILDING A 13R SYSTEM CAN BE
 USED.
  
 10) SHEET A0.05:
 A) 4.8.3 RAMPS 4.8.3 REQUIRE 44" IF
 PART OF A MEANS OF EGRESS.
 B) 4.8(2) FL. LAW TOP LANDING REQUIRES
 60" AT THE TOP LANDING AND 72" CLEAR RUN
 FOR THE BOTTOM LANDING.
 C) 4.8(3) / FIGURE 17, SAME AS ABOVE
 REQUIRING 44" IF PART OF A MEANS OF
 EGRESS.
  
 11) SHEET A0.06 FIGURE 28 THE 3RD FIGURE
 TO THE RIGHT, WHERE THE PLAN INDICATES
 THE W.C. IS 18", THIS IS AN ABSOLUTE NOT
 A MINIMUM.
  
 12) SHEET A0.06 4.3.3 WIDTH SEE
 EXCEPTION 44" IF PART OF A MEANS OF
 EGRESS.
  
 13) SHEET A0.04 NOTE, POOL, SPA ,FENCE &
 SIGNAGE REQUIRE A SEPERATE PERMIT.
  
 14) SHEET A-1.06DETAIL#2PLANS INDICATE
 USE OF ASPHALT/ FIBERGLASS COMPOSITE
 ROOF SHINGLES, THE PRODUCT APPROVAL WAS
 TESTED UNDER PA 110 WHICH LIMITS THE USE
 TO A HEIGHT OF 33'. SEE LIMITATIONS 3.2.
 SEE A-10.09 DADE-COUNTY NOA LIMITATIONS
 3.1.
  
 15 FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 THERE ARE DETAILS FOR STO EFIS SYSTEMS
 BUT THE PRODUCT APPROVALS SUBMITTED ARE
 FOR DRYVIT, WHICH WILL BE USED.
  
 16) THE EFIS DETAILS USED ON A6.06-
 A6.08 DO NOT INDICATE WHAT TYPE OF WALL
 SHEATHING IS TO BE USEDNOR INTERIOR
 FINISH MATERIAL NOR THICKNESS, TABLE 600
 1 HR RATED FOR NON-LOADBEARING WALLS.
 PROVIDE UL RATING.
  
 17) A-6.08 DRAWING # 2.11,INDICATE
 COMPLIANCE,?1804.6.2.7.2 FOAM PLASTIC
 INSULATION SHALL BE PERMITTED BELOW
 GRADE ON FOUNDATION WALLS IN ACCORDANCE
 WITH ONE OF THE FOLLOWING CONDITIONS:
  
 1. WHEN IN ADDITION TO THE REQUIREMENTS
 OF ?2304.1.2, AN APPROVED METHOD OF
 PROTECTING THE FOAM PLASTIC AND
 STRUCTURE FROM SUBTERRANEAN TERMITE
 DAMAGE IS PROVIDED.
 2. WITHIN TYPES I, II AND IV
 CONSTRUCTION.
 3. ON THE INTERIOR SIDE OF BASEMENT
 WALLS.
  
 18) MISSING SHEETS S-0.01, S-0.02, S0.03
 & S1.01?
  
 19) FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 20A) SHEET S0.03, THE SIMPLIFIED
 PRESSURES INDICATED IN TABLE 1606.2 CAN
 ONLY BE USED TO 30' WITH MULTIPLIERS TO
 60'. DEPENDING ON THE POSITIVE &
 NEGATIVE PRESSURES REQUIRED FOR THIS
 BUILDING THE DRYVIT EFIS SYSTEM
 MAY BE LOW IN PRESSURES.THIS BUILDING
 HAS A MEAN ROOF HEIGHT OF 51'-0.
  
 20B) THE ARCHITECT DOES NOT INDICATE HOW
 HE DESIGNED THE BUILDING (WIND)AT ALL?
  
 20C) PLEASE INDICATE ON THE ELEVATIONS
 THE POSITVE & NEGATIVE PRESSURES, FOR
 THE WINDOWS, DOORS EFIS & ROOFING,
 INTERIOR ZONES AS WELL AS END ZONES.
 1606.1.1.
  
 21A) A-5.14 THE LAUNDRY CHUTE DOESN'T
 PROVIDE WHAT TYPE OF METAL FRAMING IS TO
 BE USED FOR THE CHIMNEYABOVE THE ROOF
 LINE.
 21B) NO INFORMATION ON HURRICANE
 STRAPPING FOR FRAMED CHIMNEY.
 21C) SHEET A5.07 DETAIL# 9 INDICATES USE
 OF WOOD 2X IN THE 2 HR SHAFT, AND WOOD
 WALL ABOVE THE ROOF LINE, IF SO PROVIDE
 THE UL LISTING.
  
 22) SHEET A6.03 ELEVATOR VENTING:
 A)IS A CONTINUATION OF THE 2HR RATED
 SHAFT, TABLE 705.2.1, PROVIDE THE 2 HR
 SHAFTRATING THROUGH TOBUT NOT
 INCLUDING THE CURB MOUNTED ON THE ROOF.
  
 B) PROVIDE ANCHORING (STRAPPING) DETAILS
  
 C) INDICATE THE STRTCHER REQUIREMENTS
 IN ONE OF THE ELEVATORS DETAILS:
 ?3003.4.1 IN ALL STRUCTURES THAT ARE
 MORE THAN THREE STORIES HIGH OR IN
 WHICH THE VERTICAL DISTANCE BETWEEN
 THE BOTTOM TERMINAL LANDING AND THE
 TOP TERMINAL LANDING EXCEEDS 25 FEET
 (7.6 M) MUST BE CONSTRUCTED TO
 CONTAIN AT LEAST ONE PASSENGER
 ELEVATOR THAT IS OPERATIONAL AND WILL
 ACCOMMODATE AN AMBULANCE STRETCHER 76
 INCHES (1931 MM) LONG AND 24 INCHES
 (610 MM) WIDE IN THE HORIZONTAL
 POSITION.THIS ELEVATOR SHALL BE
 IDENTIFIED.
  
 23) PROVIDE DETAILS OF HOW THE EXHAUST
 DUCTS WILL BE VENTED TO THE ROOF. TABLE
 705.1.2 REEQUIRES 2 HR RATING FOR
 SHAFTS.
  
 24)) SHEETA-6.02 DETAIL 1 STAIR
 HANDRAILS:A) 11-4.9.4(1) HANDRAILS
 SHALL BE CONTINUOUS ALONG BOTH SIDES OF
 STAIRS. THE INSIDE HANDRAIL ON
 SWITCHBACK OR DOGLEG STAIRS SHALL ALWAYS
 BE CONTINUOUS SEE FIGURE 11-19(A) &
 FIGURE 11-19(B)).
  
 B) SAME SHEET DETAIL NUMBER 10:
 11-4.9.4(2) AT THE BOTTOM, THE HANDRAIL
 SHALL CONTINUE TO SLOPE FOR A DISTANCE
 OF THE WIDTH OF ONE TREAD FROM THE
 BOTTOM RISER; THE REMAINDER OF THE
 EXTENSION SHALL BE HORIZONTAL (SEE
 FIGURE 11-19(C) AND FIGURE 11-19(D)).
 HANDRAIL EXTENSIONS SHALL COMPLY WITH
 11-4.4.
  
  
  
  
 25 A-9.06 THE DOOR SCHEDULE INDICATES
 ALL STAIRWELL DOORS AS 60 MIN, TABLE
 705.1.2 REQUIRES 1 1/2 HR RATED DOORS
 FOR 2 HR RATED WALLS.
  
 26A) SHEET A-5.15/A-5.16, THERE IS A
 DISCREPANCY, ONE SHEET INDICATES A FLUE
 THE OTHER A VENTLESS SYSTEM.
 B) PROVIDE THE MANUFACTURES SPEC FOR
 THE VENTLESS FIREPLACE:SECTION 2809
 GAS APPLIANCES:GAS APPLIANCES SHALL BE
 INSTALLED AND VENTED IN ACCORDANCE WITH
 THE REQUIREMENTS OF THE FLORIDA BUILDING
 CODE, FUEL GAS.
  
 27)THE PLANS APPEARS TO HAVE ALOT OF
 DOORS ON THE FIRST FLOOR MISSING THE 18"
 CLEARENCE ON THE LATCH SIDE(PULL) OF THE
 DOOR, PLANS RED LINED.11-4.13.6
 MANEUVERING CLEARENCES AT DOORS. MINIMUM
 MANEUVERING CLEARENCES AT DOORS THAT ARE
 NOT AUTOMATIC OR POWER-ASSISTED SHALL BE
 AS SHOWN IN FIG. 25. THEFLOOR OR
 GROUND AREA WITH IN THE REQUIRED
 CLEARENCES SHALL BE CLEAR & LEVEL.
  
 28) SHEET A-2.01/ A-2.02 RESTROOM# 111 &
 112 ARE MISSING THE CLEAR FLOOR SPACE IN
 FRONT OF THE LAV, 11-4.24.5.
  
 29)SHEET A-10.11/ A-10.12 SUBMITTED A
 ROOFING REPORT FOR NON STRUCTURAL METAL
 ROOFING. THIS REPORT PRESSURE ISGOOD
 FOR ONLY 52.5 PSF. THIS ROOF WILL
 ENCOUNTER HIGHER PRESSURES THAN THIS IN
 ROOF ZONES 2 AND 3. SECOND PROBLEM THE
 ENGINEERING SHEETS THAT TIE TO THE FL
 COVERSHEET FROM C-BUCK ENGINEERING WERE
 NEVER SUBMITTED.
  
 30) SHEET A-10.13/ A-10.14 ARE FOR PGT
 HORIZONTAL SLIDERS ,THE FL COVERSHEET
 INDICATES THIS IS A NON-IMPACTWINDOW,
 SEE HIGHLIGHTED NOA# INDICATING NON-
 IMPACT RATING. THE SECOND ISSUE INDICATE
 WHICH TYPE OF GLAZING TO BE INSTALLED
 FOR PRESSURE RATINGS, MAY BE LOW VALUES.
  
 31) SHEET A-10.15/ A-10.16 SUBMITTED
 SHEETS FOR PGT FIXED GLAZING, INDICATE
 WHICH GLAZING SHALL BE USED TO SEE IF
 THE PRESSURES ARE MET.
  
 32)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) FIXED WINDOWS
 B) HORIZONTAL SLIDERS
 C) SWING DOORS- GLAZED
 D) SWING DOORS-SOLID
 E) MULLIONS
 F) LOUVERS
 G) EFIS SYSTEMS
 H) TRUSS ANCHORS
 I) ROOFING ASSEMBLIES
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 33)1707.4.3 EACH EXTERIOR DOOR ASSEMBLY
 NOT COVERED BY 1707.4.2
 (GLAZED DOORS) SHALL BE LISTED AND TEST-
 ED FOR A PERIOD EQUAL TO THE QUANITY
 3600/ V WHERE THE TIME PERIOD IS IN
 SECTIONS AND V IS IN MILES PER HR TAKEN
 FROM FIGURE 1606. THE TIME PERIOD SHALL
 ALSO INCLUDE A 10 SECOND PERIOD AT A
 LOAD EQUAL TO 1.5 TIMES THE DESIGN
 PRESSURE. DADE COUNTY & SBCCI REPORTS
 ARE ACCEPTED.
  
 34) 1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 35) 1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 36) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED, SHEET
 S-101 INDICATES THAT THE FOUNDATION
 DESIGN IS INCOMPLETE DEPENDING ON THE
 SOILS REPORT? PLANS DO NOT PROVIDE
 INFORMATION ON CAST IN PLACE CONCRETE
 PILES, LOCATION, GROUT, ETC.
  
 37) S-2.02 SECTION B PORT COCHERE
 INDICATES THE USE OF WOOD TRUSSES AND
 WOOD SHEATHING, TYPE II BUILDING, SEE
 TABLE 600 ROOFS & ROOF /CEILING
 ASSEMBLIES FOOTNOTE "E".
  
 38) S1.04 ROOF TRUSSES:
 A) PROVIDE UPLIFT FOR THE ROOF FRAMING
 MEMBERS, DIRECTION,MAGNITUDE OF THE
 LOADS TO BE RESISTED.1606.1.1/ 1606.1.3,
 PART OF THE MAIN WIND FORCE RESISTING
 SYSTEM.
 B)1707.3.1 JOIST HANGERS, FRAMING
 ANCHORS & SIMILAR DEVICES SHALL BE TEST-
 ED IN ACCORDANCE W/ ASTM D 1761 & BE
 LABELED AND LISTED FOR THEIR LOAD CARRY-
 ING CAPACITY.
 C) 1609.4.3 LOAD REDUCTION.
 WHEN STRUCTURAL EFFECTS DUE TO TWO OR
 MORE LOADS IN COMBINATION WITH DEAD LOAD
 ARE INVESTIGATED IN LOAD COMBINATIONS OF
 1609.4.1 OR 1609.4.2, THE COMBINED
 EFFECTS DUE TO THE TWO OR LOADS MULTI-
 PLIED BY 0.75 PLUS EFFECTS DUE TO DEAD
 LOADS SHALL NOT BE LESS THAN THE EFFECTS
 FROM THE LOAD COMBINATION OF THE DEAD
 LOAD PLUS THE LOAD PRODUCING THE LARGEST
 EFFECTS. INCREASE IN ALLOWABLE STRESS
 SPECIFIED IN THE MATERIALS SECTIONS OF
 THIS CODE OR A REFRENCED STANDARD SHALL
 NOT BE USED WITH THESE LOAD COMBINATIONS
 EXCEPT THAT A DURATION OF LOAD INCREASE
 SHALL BE PERMITTED IN ACCORDANCE WITH
 CHAPTER 23 (WOOD).
  
 39) SHEET M101-105 GENERAL NOTES
 INDICATE "PROVIDE A CONCEALED CONDENSATE
 STACK WITHIN THE OUTSIDE WALL, PROVIDE
 ADDITIONAL INFORMATION, ?705.6
 PENETRATIONS OF HORIZONTAL ASSEMBLIES.
 ALL PENETRATIONS OF A FLOOR, FLOOR
 / CEILING ASSEMBLY, OR THE CEILING
 MEMBRANE OF A ROOF/CEILING ASSEMBLY
 SHALL BE PROTECTED BY A SHAFT ENCLOSURE
 IN ACCORDANCE WITH 705.2 OR
 SHALL COMPLY WITH 705.6.1 THROUGH
 705.6.4. 705.6.1 THROUGH
 PENETRATIONS. THROUGH-PENETRATIONS OF
 FIRE RATEDHORIZONTAL ASSEMBLIES SHALL
 COMPLY WITH 705.6.1.1 OR 705.6.1.2.
  
 40) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 SHEET M-301 INDICATES THE USE OF ROOFTOP
 MAKE UP AIR AND EXHAUST UNITS, PROVIDE
 THE FRAMING AND ANCHORING DETAILS.
  
 41) SHEET A-5.06 COVERED ENTRY INDICATES
 THE USE OF STEEL TRUSSES AND TOUNGE AND
 GROOVE DECKING NO NO ADDITIONAL
 INFORMATION?
  
 42)DAVID I WALLACE & ASSOCIATES, P. A.,
 481.219 F.S.CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ARCHITECT
 PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING
 ARCHITECTURAL SERVICES, SHALL INCLUDE
 THE CERTIFICATE OF AUTHORIZATION
 NUMBER.ADD THE NUMBER TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
  
 43)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 44) ADDITIONAL FEES DUE, CALCULATED
 VALUE FOR THIS BUILDING IS :
 $6,776,174.00
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 BUILDING PLAN REVIEW