Plan Review Notes
Plan Review Notes For Permit 05040945
Permit Number 05040945
Review Stop P
Sequence Number 1
Notes
Date Text
2005-06-04 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL CODE
 FBC-2001 BUILDING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. PLANS SHALL BE ROUTED TO DBPR HOTEL &
 RESTURANT DIVISION FOR REVIEW PRIOR TO
 RESUBMITTING TO THE CITY WPB FOR REVIEW.
 SUBMIT A MINIMUM OF 3 SETS OF PLANS
 STAMPED BY DBPR WITH THE TWO PAGE "WORK
 SHEETS" ATTACHED TO EACH SET. SECTION
 101.4.7.
 2. INDICATE IF FOOD WILL BE PREPARED ON
 SITE OR IF ALL FOOD WILL BE PREPACKAGED
 FOOD FOR COMSUMPTION. TO DETERMINE IF A
 GREASE INTERCEPTOR IS REQUIRED CONTACT
 RODNEY COMPO, ENVIRONMENTAL COMPLIANCE.
 (561) 473-4074, FAX (561) 659-7458, OR
 E-MAIL [email protected]. PLEASE SUBMIT HIS
 DETERMINATION WITH PLANS.
 3. SHT 0.1.3 SEPARATE POOL PERMIT
 REQUIRED. SECTION 104.1.1.
 4. SHT 3.1 TOILET ROOMS. SHOW CLEAR
 FLOOR SPACE FOR EACH ACCESSIBLE FIXTURE.
 SHOW TURNING AREA IN EACH TOILET ROOM. .
 SECTION 11-4.22.3
 5. SHTS A-2.01 & A-2.02 SUBMIT
 CALCULATIONS FOR MINIMUM FACILITIES PER
 TABLES 1103.1 & 403.1 FOR ALL COMMON
 AREAS. SHOW THE SQUARE FOOTAGE OF EACH
 COMMON AREA ON THE FLOOR PLAN.
 6. SHT 3.1 SINK IN EMPLOYEE BREAK ROOM
 #156 SHALL COMPLY WITH SECTION 11-4.24
 AND ALL SUBSECTIONS. (FORWARD APPROACH
 IS REQUIRED MAXIMUM 19" UNDERNEATH THE
 SINK. SINK SHALL BE CENTERED ON THE 30"
 WIDTH OF THE CLEAR FLOOR SPACE).
 7. SHT P1.01 INDICATE THE USE OF FD1 IN
 VENDING ROOM 154. IF USED FOR INDIRECT
 WASTE, A FLOOR SINK OR HUB DRAIN IS
 REQUIRED. SECTIONS 802.3 & 802.3.2.
 8. SHT P1.01 BUILDING DRAIN LINE DOES
 NOT REFLECT PIPING SHOWN ON SHT P-5.01.
 PIPING ON SHT P-5.01 SHOWS THE LAUNDRY
 ROOM CONNECTING UPSTREAM OF RISER S/3
 CONNECTION TO BUILDING DRAIN. CORRELATE
 PLANS. SECTION 104.2.1.
 9. SHT P2.01 WATER HEATER SCHEMATIC:
 A. T&P LINE SHALL BE PIPED TO AN
 APPROVED INDIRECT WASTE RECEPTOR. FLOOR
 SINK OR HUB DRAIN REQUIRED. FLOOR DRAINS
 ARE NOT APPROVED WASTE RECEPTORS.
 SECTIONS 802.3 & 802.3.2.
 B. SCHEMATIC SHOWS 2-1/2" STUB OUTS FOR
 FUTURE WATER SOFTENER (HOT ONLY), BUT IT
 APPEARS TO BE ON THE COLD WATER SIDE OF
 THE HEATERS. PLEASE CLARIFY. SECTION
 104.2.1.
 C. DIELECTRIC UNIONS NOT APPROVED FOR
 WATER DISTRIBUTION SYSTEM. DIELECTRIC
 COUPLINGS SHOULD BE USED.
 10. SHT P-201 GENERAL PLUMBING NOTES:
 #12 REVISIONS WILL BE REQUIRED FOR ALL
 CHANGES TO A SIGNED/SEALED/DATED SET OF
 PLANS.
 #27 AIR CHAMBERS ARE NOT APPROVED PER
 SECTION 604.9. DELETE FROM REFERENCE.
 #29 CONDENSATE SHALL BE PIPED
 SEPARATELY FROM THE BUILDING AND
 CONNECTED TO STORM, A CATCH BASIN OR TO
 DRYWELL OR PLANTED AREA.
 11. SUBMIT A BUILDING DRAIN SANITARY
 ISOMETRIC SHOWING ALL PIPE SIZES, DFU'S
 AS THEY ACCUMULATE IN THE SYSTEM, AND
 SHOW RISER LOCATIONS WITH RISER
 DESIGNATION NUMBERS. SECTIONS 104.2.1 &
 104.3.1.1.
 12) SHT P-3.01 ALL SANT. RISER DIAGRAMS,
 (EXCEPT S/16), DO NOT REFLECT THE FLOOR
 PLAN, NOR DO THEY MEET CODE REQUIREMENTS
 A. RISER S/15 EW1 NOT SHOWN ON RISER.
 B. RISERS SHALL REFLECT THE SANT.
 LAYOUT ON SHTS P-4.01 & P-4.02.
 C. A VENT STACK SHALL BE REQUIRED FOR
 EVERY DRAINAGE STACK THAT IS FIVE BRANCH
 INTERVALS OR MORE. SECTION 903.2.
 D. EVERY VENT STACK SHALL CONNECT TO
 THE BASE OF THE DRAINAGE STACK. THE VENT
 STACK SHALL CONNECT AT OR BELOW THE
 LOWEST HORIZONTAL BRANCH. SECTION 903.4.
 13. SUBMIT A WATER RISER DIAGRAM IN
 ISOMETRIC FORM FOR THE LAUNDRYAND ALL
 COMMON AREAS SHOWING ALL PIPE SIZES,
 VALVES, AND WATER HAMMER ARRESTORS,
 (WHERE REQUIRED BY SECTION 604.9).
 14. SUBMIT A WATER RISER DIAGRAM IN
 ISOMETRIC FORM FOR THE WATER
 DISTRIBUTION SYSTEM SHOWING THE LOCATION
 OF THE WATER ENTERING THE BUILDING, ALL
 PIPING NOT SHOWN ON RISERS, ALL PIPE
 SIZES, WATER HAMMER ARRESTORS, LOCATION
 OF WATER RISERS CONNECTING TO
 DISTRIBUTION LINE WITH RISER DESIGNATION
 NUMBERS ECT. SECTIONS 104.2.1 AND
 104.3.1.1.
 15. SUBMIT A CONDENSATE RISER DIAGRAM
 SHOWING ALL PIPE SIZES, MATERIAL, AND
 TERMINATION POINT. SECTIONS 104.2.1. &
 104.3.1.1.
 16. THE FOLLOWING INFORMATION IS
 REQUIRED FOR A GAS PERMIT:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
 C. TYPE OF GAS, (LP OR NATURAL)
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 F. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 G. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 I. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 J. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 17. AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE TO THE BUILDING. SECTION
 608.13.2.
 18. BACKFLOW PROTECTION IS REQUIRED FOR
 POOL WATER SUPPLY. THIS CAN BE INDICATED
 ON THE POOL PLANS WHEN SUBMITTED.
 19. ALL INFORMATION REQUIRED BY FAC
 61G1-16.004 & FS 481.219 TO BE IN THE
 TITLE BLOCK OF THE ARCHITECT.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]