| Date |
Text |
| 2005-06-04 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL CODE |
| | FBC-2001 BUILDING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. PLANS SHALL BE ROUTED TO DBPR HOTEL & |
| | RESTURANT DIVISION FOR REVIEW PRIOR TO |
| | RESUBMITTING TO THE CITY WPB FOR REVIEW. |
| | SUBMIT A MINIMUM OF 3 SETS OF PLANS |
| | STAMPED BY DBPR WITH THE TWO PAGE "WORK |
| | SHEETS" ATTACHED TO EACH SET. SECTION |
| | 101.4.7. |
| | 2. INDICATE IF FOOD WILL BE PREPARED ON |
| | SITE OR IF ALL FOOD WILL BE PREPACKAGED |
| | FOOD FOR COMSUMPTION. TO DETERMINE IF A |
| | GREASE INTERCEPTOR IS REQUIRED CONTACT |
| | RODNEY COMPO, ENVIRONMENTAL COMPLIANCE. |
| | (561) 473-4074, FAX (561) 659-7458, OR |
| | E-MAIL [email protected]. PLEASE SUBMIT HIS |
| | DETERMINATION WITH PLANS. |
| | 3. SHT 0.1.3 SEPARATE POOL PERMIT |
| | REQUIRED. SECTION 104.1.1. |
| | 4. SHT 3.1 TOILET ROOMS. SHOW CLEAR |
| | FLOOR SPACE FOR EACH ACCESSIBLE FIXTURE. |
| | SHOW TURNING AREA IN EACH TOILET ROOM. . |
| | SECTION 11-4.22.3 |
| | 5. SHTS A-2.01 & A-2.02 SUBMIT |
| | CALCULATIONS FOR MINIMUM FACILITIES PER |
| | TABLES 1103.1 & 403.1 FOR ALL COMMON |
| | AREAS. SHOW THE SQUARE FOOTAGE OF EACH |
| | COMMON AREA ON THE FLOOR PLAN. |
| | 6. SHT 3.1 SINK IN EMPLOYEE BREAK ROOM |
| | #156 SHALL COMPLY WITH SECTION 11-4.24 |
| | AND ALL SUBSECTIONS. (FORWARD APPROACH |
| | IS REQUIRED MAXIMUM 19" UNDERNEATH THE |
| | SINK. SINK SHALL BE CENTERED ON THE 30" |
| | WIDTH OF THE CLEAR FLOOR SPACE). |
| | 7. SHT P1.01 INDICATE THE USE OF FD1 IN |
| | VENDING ROOM 154. IF USED FOR INDIRECT |
| | WASTE, A FLOOR SINK OR HUB DRAIN IS |
| | REQUIRED. SECTIONS 802.3 & 802.3.2. |
| | 8. SHT P1.01 BUILDING DRAIN LINE DOES |
| | NOT REFLECT PIPING SHOWN ON SHT P-5.01. |
| | PIPING ON SHT P-5.01 SHOWS THE LAUNDRY |
| | ROOM CONNECTING UPSTREAM OF RISER S/3 |
| | CONNECTION TO BUILDING DRAIN. CORRELATE |
| | PLANS. SECTION 104.2.1. |
| | 9. SHT P2.01 WATER HEATER SCHEMATIC: |
| | A. T&P LINE SHALL BE PIPED TO AN |
| | APPROVED INDIRECT WASTE RECEPTOR. FLOOR |
| | SINK OR HUB DRAIN REQUIRED. FLOOR DRAINS |
| | ARE NOT APPROVED WASTE RECEPTORS. |
| | SECTIONS 802.3 & 802.3.2. |
| | B. SCHEMATIC SHOWS 2-1/2" STUB OUTS FOR |
| | FUTURE WATER SOFTENER (HOT ONLY), BUT IT |
| | APPEARS TO BE ON THE COLD WATER SIDE OF |
| | THE HEATERS. PLEASE CLARIFY. SECTION |
| | 104.2.1. |
| | C. DIELECTRIC UNIONS NOT APPROVED FOR |
| | WATER DISTRIBUTION SYSTEM. DIELECTRIC |
| | COUPLINGS SHOULD BE USED. |
| | 10. SHT P-201 GENERAL PLUMBING NOTES: |
| | #12 REVISIONS WILL BE REQUIRED FOR ALL |
| | CHANGES TO A SIGNED/SEALED/DATED SET OF |
| | PLANS. |
| | #27 AIR CHAMBERS ARE NOT APPROVED PER |
| | SECTION 604.9. DELETE FROM REFERENCE. |
| | #29 CONDENSATE SHALL BE PIPED |
| | SEPARATELY FROM THE BUILDING AND |
| | CONNECTED TO STORM, A CATCH BASIN OR TO |
| | DRYWELL OR PLANTED AREA. |
| | 11. SUBMIT A BUILDING DRAIN SANITARY |
| | ISOMETRIC SHOWING ALL PIPE SIZES, DFU'S |
| | AS THEY ACCUMULATE IN THE SYSTEM, AND |
| | SHOW RISER LOCATIONS WITH RISER |
| | DESIGNATION NUMBERS. SECTIONS 104.2.1 & |
| | 104.3.1.1. |
| | 12) SHT P-3.01 ALL SANT. RISER DIAGRAMS, |
| | (EXCEPT S/16), DO NOT REFLECT THE FLOOR |
| | PLAN, NOR DO THEY MEET CODE REQUIREMENTS |
| | A. RISER S/15 EW1 NOT SHOWN ON RISER. |
| | B. RISERS SHALL REFLECT THE SANT. |
| | LAYOUT ON SHTS P-4.01 & P-4.02. |
| | C. A VENT STACK SHALL BE REQUIRED FOR |
| | EVERY DRAINAGE STACK THAT IS FIVE BRANCH |
| | INTERVALS OR MORE. SECTION 903.2. |
| | D. EVERY VENT STACK SHALL CONNECT TO |
| | THE BASE OF THE DRAINAGE STACK. THE VENT |
| | STACK SHALL CONNECT AT OR BELOW THE |
| | LOWEST HORIZONTAL BRANCH. SECTION 903.4. |
| | 13. SUBMIT A WATER RISER DIAGRAM IN |
| | ISOMETRIC FORM FOR THE LAUNDRYAND ALL |
| | COMMON AREAS SHOWING ALL PIPE SIZES, |
| | VALVES, AND WATER HAMMER ARRESTORS, |
| | (WHERE REQUIRED BY SECTION 604.9). |
| | 14. SUBMIT A WATER RISER DIAGRAM IN |
| | ISOMETRIC FORM FOR THE WATER |
| | DISTRIBUTION SYSTEM SHOWING THE LOCATION |
| | OF THE WATER ENTERING THE BUILDING, ALL |
| | PIPING NOT SHOWN ON RISERS, ALL PIPE |
| | SIZES, WATER HAMMER ARRESTORS, LOCATION |
| | OF WATER RISERS CONNECTING TO |
| | DISTRIBUTION LINE WITH RISER DESIGNATION |
| | NUMBERS ECT. SECTIONS 104.2.1 AND |
| | 104.3.1.1. |
| | 15. SUBMIT A CONDENSATE RISER DIAGRAM |
| | SHOWING ALL PIPE SIZES, MATERIAL, AND |
| | TERMINATION POINT. SECTIONS 104.2.1. & |
| | 104.3.1.1. |
| | 16. THE FOLLOWING INFORMATION IS |
| | REQUIRED FOR A GAS PERMIT: |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | FUEL GAS CODE. |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE IF BEING USED. |
| | C. TYPE OF GAS, (LP OR NATURAL) |
| | D. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2001 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.5.2 AND TABLES 402(1) THRU |
| | 402(34). |
| | E. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES (A)(3). |
| | F. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES (A)(3). |
| | G. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2001 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2001 FUEL GAS CODE SEC 402.2 |
| | I. CLEARLY SHOW THE LOCATION AND CAP- |
| | ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| | OR ASME), THE DISTANCE OF THE TANK FROM |
| | THE BUILDING AND ADJACENT PROPERTY LINES |
| | THE DISTANCE OF THE TANK FROM ALL SOUR- |
| | CES OF IGNITION, OTHER CONTAINERS, BUILD |
| | INGS, AND THE LOCATION OF ANY BUILDING |
| | OPENINGS BELOW THE RELIEF VALVE OF THE |
| | TANK PER NFPA 58, TABLE 3-2.2.2. |
| | J. CLEARLY INDICATE ON THE PLAN IF THE |
| | LP TANK IS ABOVE OR BELOW GROUND, AND |
| | SHOW REQUIRED PROTECTION OF THE TANK AND |
| | APPURTENANCES PER NFPA 58. IF THE TANK |
| | IS BELOW GROUND THE CONTAINER SHALL BE |
| | SECURILY ANCHORED PER NFPA 58 SECTION |
| | 3-2.2.7(H). |
| | 17. AN RPZ BACKFLOW IS REQUIRED ON THE |
| | WATER SERVICE TO THE BUILDING. SECTION |
| | 608.13.2. |
| | 18. BACKFLOW PROTECTION IS REQUIRED FOR |
| | POOL WATER SUPPLY. THIS CAN BE INDICATED |
| | ON THE POOL PLANS WHEN SUBMITTED. |
| | 19. ALL INFORMATION REQUIRED BY FAC |
| | 61G1-16.004 & FS 481.219 TO BE IN THE |
| | TITLE BLOCK OF THE ARCHITECT. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |