2005-05-14 00:00:00PLAN DENIED
 1) BATHROOM EXHAUST MUST BE INSTALLED IN
 A 2HR.SHAFT.PER SECTION 607.4 FLOOR
 PENETRATION FBC(M)
 2) PAGE M1.01 AIRHANDLER #3 NEEDS FAN
 SHUTDOWN.SECTION 606 FBC(M)
 3) ALL METERALS IN RETURN AIR PLENUM
 MUST BE NONCOMBUSTIBLE SECTION 602.2.1
 FBC(M)
 4) PLEASE SHOW FRESH AIR DUCT FOR
 AIRHANDLERS 1 THROUGH 6 ON PLANS.
 5) PLEASE SHOW LOCATION AND DUCT SIZE
 FOR RETURN AIR ON AIRHANDLERS 1,2,3,6
 6) IF EXHAUST FANS AER LOCATED ON ROOF
 PLAESE REFER TO SECTION 306.6 FBC(M)
 PLAN REVIEW BY HAROLD MOSER 561-805-6732