| Plan Review Notes For Permit 05040945 |
| Permit Number |
05040945 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-05-14 00:00:00 | PLAN DENIED | | | 1) BATHROOM EXHAUST MUST BE INSTALLED IN | | | A 2HR.SHAFT.PER SECTION 607.4 FLOOR | | | PENETRATION FBC(M) | | | 2) PAGE M1.01 AIRHANDLER #3 NEEDS FAN | | | SHUTDOWN.SECTION 606 FBC(M) | | | 3) ALL METERALS IN RETURN AIR PLENUM | | | MUST BE NONCOMBUSTIBLE SECTION 602.2.1 | | | FBC(M) | | | 4) PLEASE SHOW FRESH AIR DUCT FOR | | | AIRHANDLERS 1 THROUGH 6 ON PLANS. | | | 5) PLEASE SHOW LOCATION AND DUCT SIZE | | | FOR RETURN AIR ON AIRHANDLERS 1,2,3,6 | | | 6) IF EXHAUST FANS AER LOCATED ON ROOF | | | PLAESE REFER TO SECTION 306.6 FBC(M) | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|