2005-05-25 00:00:00****FAILED****
  
 1) LOCKING CAPS ARE REQUIRED ON THE FIRE
 DEPARTMENT CONNECTION.
  
 2) LIFE SAFETY SHALL COMPLY WITH NFPA
 101, 2003 EDITION.
  
 3) ALL CONSTRUCTION, ALTERATION AND
 DEMOLITION TO COMPLY WITH NFPA 241.
  
 4) SEPARATE SHOP DRAWING AND PERMITS ARE
 REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM SYSTEMS.
  
 5) NEW FIRE ALARM SYSTEMS SHALL BE
 MONITORED FOR UL CERTIFIED CENTRAL
 STATION SERVICE.
  
 6) TEMPORARY STANDPIPES ARE REQUIRED
 WHEN THE BUILDING REACHES 3 STORIES OR
 30 FEET IN HEIGHT.
  
 7) FIRE DEPARTMENT CONNECTIONS MUST
 REMAIN ACCESSIBLE, AND BE LOCATED NO
 FURTHER THAN 150' FROM THE CLOSEST FIRE
 HYDRANT.
  
 8) PLEASE INDICATE THE OCCUPANT LOAD FOR
 THE POOL AND DECK AREAS.
  
 9) PLEASE PROVIDE THE PRESCRIPTIVE
 STRENGTH REQUIREMENTS FOR ALL HANDRAILS
 AND GUARDRAILS.
  
 10) PLEASE PROVIDE MORE DETAILS IN
 REGARDS TO THE CARD READERS, AND WHAT
 ISSUES IF ANY WILL THEY RAISE IN
 EXITING.
  
 11) 2A-10B,C FIRE EXTINGUISHERS SHALL BE
 PLACED TO SATISFY THE 75' TRAVEL
 DISTANCE REQUIREMENT.
  
 12) TACTILE SIGNAGE IS REQUIRED AT ALL
 EXIT DOORS.
  
 13) IT APPEARS THAT ADDITIONAL EXIT
 SIGNS WILL BE NEEDED TO SATISFY THE 100'
 TRAVEL REQUIREMENT BETWEEN SIGNS.
  
 14) AN ADDRESS NUMBER IS REQUIRED TO BE
 INSTALLED ON THE BUILDING, A MINIMUM OF
 6" IN HEIGHT AND CONTRASTING TO THE
 BACKGROUND.
  
 15) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION OF THE WALLS AND
 CEILINGS.
  
 16) LOCAL REQUIREMENTS REQUIRE THE DUCT
 SMOKE DETECTORS TO BE WIRED INTO THE
 FIRE ALARM SYSTEM TO CAUSE A GENERAL
 FIRE ALARM, AND NOT A SUPERVISORY
 SIGNAL.
  
 17) A CHAIN AND LOCK IN ADDITION TO
 ELECTRONIC SUPERVISION WILL BE REQUIRED
 ON THE DOUBLE CHECK DETECTOR ASSEMBLY.
  
 18) PLEASE ILLUSTRATE STRETCHER
 ACCESSIBILITY IN ELEVATORS.
  
 19) PLEASE SHOW THE LOCATIONS OF LIVING
 UNIT SINGLE STATION SMOKE DETECTORS.
  
 20) ARE THE ELEVATOR LOBBIES ABOVE THE
 FLOOR OF EXIT DISCHARGE FIRE RATED?
  
 21) A KNOX BOX WILL BE REQUIRED.
  
 22) PLEASE SHOW EXISTING AND NEW FIRE
 HYDRANT LOCATIONS.
  
 23) NO FIRE PROTECTION OF LIFE SAFETY
 DRAWINGS WERE SUBMITTED.
  
  