| 2005-05-25 00:00:00 | ****FAILED**** |
| | |
| | 1) LOCKING CAPS ARE REQUIRED ON THE FIRE |
| | DEPARTMENT CONNECTION. |
| | |
| | 2) LIFE SAFETY SHALL COMPLY WITH NFPA |
| | 101, 2003 EDITION. |
| | |
| | 3) ALL CONSTRUCTION, ALTERATION AND |
| | DEMOLITION TO COMPLY WITH NFPA 241. |
| | |
| | 4) SEPARATE SHOP DRAWING AND PERMITS ARE |
| | REQUIRED FOR FIRE SPRINKLER AND FIRE |
| | ALARM SYSTEMS. |
| | |
| | 5) NEW FIRE ALARM SYSTEMS SHALL BE |
| | MONITORED FOR UL CERTIFIED CENTRAL |
| | STATION SERVICE. |
| | |
| | 6) TEMPORARY STANDPIPES ARE REQUIRED |
| | WHEN THE BUILDING REACHES 3 STORIES OR |
| | 30 FEET IN HEIGHT. |
| | |
| | 7) FIRE DEPARTMENT CONNECTIONS MUST |
| | REMAIN ACCESSIBLE, AND BE LOCATED NO |
| | FURTHER THAN 150' FROM THE CLOSEST FIRE |
| | HYDRANT. |
| | |
| | 8) PLEASE INDICATE THE OCCUPANT LOAD FOR |
| | THE POOL AND DECK AREAS. |
| | |
| | 9) PLEASE PROVIDE THE PRESCRIPTIVE |
| | STRENGTH REQUIREMENTS FOR ALL HANDRAILS |
| | AND GUARDRAILS. |
| | |
| | 10) PLEASE PROVIDE MORE DETAILS IN |
| | REGARDS TO THE CARD READERS, AND WHAT |
| | ISSUES IF ANY WILL THEY RAISE IN |
| | EXITING. |
| | |
| | 11) 2A-10B,C FIRE EXTINGUISHERS SHALL BE |
| | PLACED TO SATISFY THE 75' TRAVEL |
| | DISTANCE REQUIREMENT. |
| | |
| | 12) TACTILE SIGNAGE IS REQUIRED AT ALL |
| | EXIT DOORS. |
| | |
| | 13) IT APPEARS THAT ADDITIONAL EXIT |
| | SIGNS WILL BE NEEDED TO SATISFY THE 100' |
| | TRAVEL REQUIREMENT BETWEEN SIGNS. |
| | |
| | 14) AN ADDRESS NUMBER IS REQUIRED TO BE |
| | INSTALLED ON THE BUILDING, A MINIMUM OF |
| | 6" IN HEIGHT AND CONTRASTING TO THE |
| | BACKGROUND. |
| | |
| | 15) PLEASE PROVIDE INTERIOR FINISH |
| | CLASSIFICATION OF THE WALLS AND |
| | CEILINGS. |
| | |
| | 16) LOCAL REQUIREMENTS REQUIRE THE DUCT |
| | SMOKE DETECTORS TO BE WIRED INTO THE |
| | FIRE ALARM SYSTEM TO CAUSE A GENERAL |
| | FIRE ALARM, AND NOT A SUPERVISORY |
| | SIGNAL. |
| | |
| | 17) A CHAIN AND LOCK IN ADDITION TO |
| | ELECTRONIC SUPERVISION WILL BE REQUIRED |
| | ON THE DOUBLE CHECK DETECTOR ASSEMBLY. |
| | |
| | 18) PLEASE ILLUSTRATE STRETCHER |
| | ACCESSIBILITY IN ELEVATORS. |
| | |
| | 19) PLEASE SHOW THE LOCATIONS OF LIVING |
| | UNIT SINGLE STATION SMOKE DETECTORS. |
| | |
| | 20) ARE THE ELEVATOR LOBBIES ABOVE THE |
| | FLOOR OF EXIT DISCHARGE FIRE RATED? |
| | |
| | 21) A KNOX BOX WILL BE REQUIRED. |
| | |
| | 22) PLEASE SHOW EXISTING AND NEW FIRE |
| | HYDRANT LOCATIONS. |
| | |
| | 23) NO FIRE PROTECTION OF LIFE SAFETY |
| | DRAWINGS WERE SUBMITTED. |
| | |
| | |
| | MIKE WENNERGREN, A/CAPTAIN |
| | WPBFR(561) 835-2951 OR 805-6722 |