| Date |
Text |
| 2005-05-02 00:00:00 | *** ALL ELECTRICAL ROOMS PER 110.26, |
| | DOOR SWINGS, PANIC HARDWARE ETC. |
| 2005-04-28 00:00:00 | *********** UNSAT *********** |
| | |
| | FAIRFIELD INN 6- STORY |
| | PLANS SUBMITTED FOR "PLAN REVIEW" ONLY |
| | AND NOT SUBMITTED FOR PERMIT. |
| | |
| | |
| | 1)NOTE: PLEASE SEE ALL BACKGROUNDS FOR |
| | ELECTRICAL PLANS ARE VERY FAINT AND |
| | UNABLE TO VIEW CORRECTLY. |
| | PLEASE ALSO SEE ALL PLANS TO BE |
| | SUBMITTED ARE REQUIRED TO BE A MIN OF |
| | 1/8" SCALE. |
| | 104.2.1 |
| | |
| | 2)NOTE: PLEASE SHOW LOCATION OF ALL |
| | ELECTRICAL PANELS, DISCONNECTS ETC ON |
| | PLANS. UNABLE TO LOCATE ANY ON PLANS. |
| | PLEASE ALSO SHOW PANELS ETC IN |
| | ELECTRICAL RMS AS REQUIRED. |
| | PLEASE INCLUDE PROPOSED FIRE PUMP RM |
| | ETC. |
| | 110.26,215.5 |
| | |
| | 3)NOTE: PLEASE SEE FAC 61G1-16.004 AND |
| | FS 481.219 FOR MISSING REQUIRED |
| | INFORMATION ON/IN TITLE BLOCKS. |
| | THIS IS REQUIRED FOR ALL TRADES AND FOR |
| | ALL SHEETS WHEATHER OR NOT COMMENT IS |
| | MADE BY OTHER REVIEWER(S). |
| | |
| | 4)NOTE: PLEASE SEE ELECTRICAL NOTES |
| | MENTIONS "PLANS TO COMPLY WITH:"?? |
| | PLEASE COMPLETE NOTE AND PLEASE SEE WE |
| | ARE CURRENTLY UNDER THE 2002 NEC. |
| | 215.5 |
| | |
| | 5)NOTE: PLEASE SEE 2002 NEC FOR GFI |
| | PROTECTION REQUIRED FOR "ALL" RECEPTS IN |
| | KITCHENS.210.8B3 |
| | PLEASE ALSO SEE RECEPTS LOCATED IN BREAK |
| | RM AND CLOSE PROXIMITY TO SINKS. 6' |
| | 210.8 |
| | |
| | 6)NOTE:PLEASE INCLUDE ALL CIRCUITING ON |
| | PLANS AND CORRELATE WITH PANEL SCHEDULES |
| | SUBMITTED. |
| | PLEASE SEE ROOM TYPICAL DETAILS ALSO. |
| | |
| | 7)NOTE: PLEASE SEE SOME ROOMS APPEAR TO |
| | SHOW MORE THAN ONE SINGLE POLE SWITCH |
| | CONTROLLING THE SAME DEVICE. THESE |
| | SHOULD BE 3-WAYS? |
| | |
| | 8)NOTE: PLEASE SEE DETAIL ON E4.1.1E |
| | REFERS TO #7 ON E4.4F, HOWEVER THIS |
| | DEATIL FOR CIRCLED NOT SHOWN.?? |
| | |
| | 9)NOTE: PLEASE SOME BATHRMS DO NOT |
| | INDICATES RECETPS AS GFI? |
| | 210.8A3 |
| | |
| | 10)NOTE: PLEASE SEE CIRCUITING LABELD ON |
| | MSB. PLEASE CORRELATE CIRCUITS # WITH |
| | PLANS. |
| | 215.5 |
| | |
| | 11)NOTE:PLEASE SEE NOTE #1 , PLEASE |
| | SHOW ELEVATOR EQUIPMENT RMS. PLEASE SEE |
| | 620.23,620.24 FOR MIN CIRCUITING |
| | REQUIRED. |
| | CIRCUITS SHOWN ON PANEL SCHEDULE 6C, BUT |
| | UNCLEAR IF THESE ARE FOR "CARS" OR |
| | MACHINE RM? |
| | |
| | 12)NOTE: PLEASE SHOW ALL CONTINUOUS |
| | LOADS AT 125% ON EACH PANEL ALSO.THIS |
| | MAY BE A NOTE, IF INDEED THESE LOADS ARE |
| | ALREADY FIGURED AT 125%. |
| | IT IS NOTED THAT MAIN SERVICE CONTAINS |
| | THE 125% ALREADY. |
| | 215.3,230.42 ETC. |
| | |
| | 13)NOTE: PLEASE CORRELATE ALL CONDUCTOR |
| | SIZES SHOWN ON EQUIPMENT SCHEDULE WITH |
| | PANEL SCHEDULES FOR EACH. |
| | 215.5 |
| | PLEASE SEE MIN AWG FOR OCP AND KW LOADS. |
| | 310.16,240.4 |
| | |
| | 14)NOTE: PLEASE SEE EQUIPMENT SCHEDULE |
| | MENTIONS REFERENCE TO NOTE #7 ON E1.00, |
| | YET NO E-1.00 COULD BE LOCATED IN SETS?? |
| | 215.5 |
| | |
| | 14)NOTE: PLEASE VERIFY FEEDERS INDICATED |
| | FOR 200A PANELS, 2A -6A. |
| | SHOWN AS 500MCM? |
| | THIS IS ONLY A NOTE: |
| | |
| | 15)NOTE: PLEASE SEE FIRE PUMP IS SHOWN |
| | BEING FED FROM MSB. PLEASE SEE 695.3, |
| | THIS "ISNOT" PERMITTED. |
| | PLEASE ALSO SEE FIRE PUMP IS SHOWN WITH |
| | A ADDITIONAL FEED FROM FPL THROUGH AN |
| | ATS?? |
| | PLEASE SEE NO SIZE OF FIRE PUMP IS |
| | SHOWN? |
| | PLEASE SEE NO MAIN SHOWN FOR THIS? |
| | PLEASE SEE NO INFORMATION SUBMITTED FOR |
| | FIRE PUMP? |
| | PLEASE SEE THIS IS PHYISCALLY |
| | IMPOSSIBLE. |
| | PLEASE SUBMIT ALL INFORMATION FOR FIRE |
| | PUMP, ATS, GENERATOR ETC. |
| | PLEASE SUBMIT MANUFACTURE SPEC SHEETS |
| | FOR ALL EQUIPMENT. |
| | PLEASE INCLUDE PRIME MOVER FOR |
| | GENERATOR. |
| | PLEASE SEE MISSING DISCONNECTING MEANS |
| | PER 225.31-225.36. |
| | PLEASE SEE MISSING EQUIPMENT GROUNDING |
| | FOR FEEDS TO FIRE PUMP. |
| | 250.110,250.122 |
| | PLEASE SEE MISSING INFORMATION FOR |
| | LOCKED ROTOR PER 695.4B1 |
| | PLEASE SHOW ALL LOCATIONS OF ALL |
| | EQUIPMENT ON ELECTRICAL PLANS. |
| | |
| | 16)NOTE: PLEASE CORRELATE GROUNDING |
| | ELECTRODE CONDUCTOR SIZES ON PLANS. |
| | PLEASE SEE ONE LOCATION SHOWS 4/0 AND |
| | THE OTHER 3/0? |
| | 250.66 |
| | |
| | 17)NOTE: PLEASE VERIFY SEC'S SHOWN. |
| | THIS IS ONLY A NOTE AND NO CODE |
| | VIOLATION EXIST FOR SEC'S. |
| | |
| | 18)NOTE: PLEASE SEE PANEL "L" IS SHOWN |
| | ON RISER TO BE FED FROM MSB, HOWEVER MSB |
| | SCHEDULE DOES NOT INDICATE THIS ? |
| | PLEASE CORRELATE.215.5 |
| | |
| | 19)NOTE: PLEASE SEE FIRE REVIEW COMMENTS |
| | PERTAINING TO FIRE ALARM PLANS REQUIRED. |
| | |
| | 20)NOTE: PLEASE SEE OTHER POSSIBLE |
| | COMMENTS FROM OTHER REVIEWER(S) WHICH |
| | MAY HAVE AN AFFECT ON ELECTRICAL PLANS. |
| | |
| | PLEASE BE SURE TO REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW SHEETS INTO |
| | THREE COMPLETED SETS FOR REVIEW AND |
| | STAMPING. |
| | |
| | *** PLEASE SEE DUE TO THE AMOUNT OF |
| | MISSING INFORMATION ON PLANS, A COMPLETE |
| | REVIEWFOR CODE COMPLIANCE CAN NOT BE |
| | DONE AT THIS TIME. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | *** PLEASE SEE DUE TO THE AMOUNT OF |
| | MISSING INFORMATION ON PLANS, A COMPLETE |
| | REVIEWFOR CODE COMPLIANCE CAN NOT BE |
| | DONE AT THIS TIME. |
| 2005-04-27 00:00:00 | 1 ROLL IN FOR ELECTRICAL REVIEW. |