Plan Review Notes
Plan Review Notes For Permit 05040945
Permit Number 05040945
Review Stop E
Sequence Number 1
Notes
Date Text
2005-05-02 00:00:00*** ALL ELECTRICAL ROOMS PER 110.26,
 DOOR SWINGS, PANIC HARDWARE ETC.
2005-04-28 00:00:00*********** UNSAT ***********
  
 FAIRFIELD INN 6- STORY
 PLANS SUBMITTED FOR "PLAN REVIEW" ONLY
 AND NOT SUBMITTED FOR PERMIT.
  
  
 1)NOTE: PLEASE SEE ALL BACKGROUNDS FOR
 ELECTRICAL PLANS ARE VERY FAINT AND
 UNABLE TO VIEW CORRECTLY.
 PLEASE ALSO SEE ALL PLANS TO BE
 SUBMITTED ARE REQUIRED TO BE A MIN OF
 1/8" SCALE.
 104.2.1
  
 2)NOTE: PLEASE SHOW LOCATION OF ALL
 ELECTRICAL PANELS, DISCONNECTS ETC ON
 PLANS. UNABLE TO LOCATE ANY ON PLANS.
 PLEASE ALSO SHOW PANELS ETC IN
 ELECTRICAL RMS AS REQUIRED.
 PLEASE INCLUDE PROPOSED FIRE PUMP RM
 ETC.
 110.26,215.5
  
 3)NOTE: PLEASE SEE FAC 61G1-16.004 AND
 FS 481.219 FOR MISSING REQUIRED
 INFORMATION ON/IN TITLE BLOCKS.
 THIS IS REQUIRED FOR ALL TRADES AND FOR
 ALL SHEETS WHEATHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
 4)NOTE: PLEASE SEE ELECTRICAL NOTES
 MENTIONS "PLANS TO COMPLY WITH:"??
 PLEASE COMPLETE NOTE AND PLEASE SEE WE
 ARE CURRENTLY UNDER THE 2002 NEC.
 215.5
  
 5)NOTE: PLEASE SEE 2002 NEC FOR GFI
 PROTECTION REQUIRED FOR "ALL" RECEPTS IN
 KITCHENS.210.8B3
 PLEASE ALSO SEE RECEPTS LOCATED IN BREAK
 RM AND CLOSE PROXIMITY TO SINKS. 6'
 210.8
  
 6)NOTE:PLEASE INCLUDE ALL CIRCUITING ON
 PLANS AND CORRELATE WITH PANEL SCHEDULES
 SUBMITTED.
 PLEASE SEE ROOM TYPICAL DETAILS ALSO.
  
 7)NOTE: PLEASE SEE SOME ROOMS APPEAR TO
 SHOW MORE THAN ONE SINGLE POLE SWITCH
 CONTROLLING THE SAME DEVICE. THESE
 SHOULD BE 3-WAYS?
  
 8)NOTE: PLEASE SEE DETAIL ON E4.1.1E
 REFERS TO #7 ON E4.4F, HOWEVER THIS
 DEATIL FOR CIRCLED NOT SHOWN.??
  
 9)NOTE: PLEASE SOME BATHRMS DO NOT
 INDICATES RECETPS AS GFI?
 210.8A3
  
 10)NOTE: PLEASE SEE CIRCUITING LABELD ON
 MSB. PLEASE CORRELATE CIRCUITS # WITH
 PLANS.
 215.5
  
 11)NOTE:PLEASE SEE NOTE #1 , PLEASE
 SHOW ELEVATOR EQUIPMENT RMS. PLEASE SEE
 620.23,620.24 FOR MIN CIRCUITING
 REQUIRED.
 CIRCUITS SHOWN ON PANEL SCHEDULE 6C, BUT
 UNCLEAR IF THESE ARE FOR "CARS" OR
 MACHINE RM?
  
 12)NOTE: PLEASE SHOW ALL CONTINUOUS
 LOADS AT 125% ON EACH PANEL ALSO.THIS
 MAY BE A NOTE, IF INDEED THESE LOADS ARE
 ALREADY FIGURED AT 125%.
 IT IS NOTED THAT MAIN SERVICE CONTAINS
 THE 125% ALREADY.
 215.3,230.42 ETC.
  
 13)NOTE: PLEASE CORRELATE ALL CONDUCTOR
 SIZES SHOWN ON EQUIPMENT SCHEDULE WITH
 PANEL SCHEDULES FOR EACH.
 215.5
 PLEASE SEE MIN AWG FOR OCP AND KW LOADS.
 310.16,240.4
  
 14)NOTE: PLEASE SEE EQUIPMENT SCHEDULE
 MENTIONS REFERENCE TO NOTE #7 ON E1.00,
 YET NO E-1.00 COULD BE LOCATED IN SETS??
 215.5
  
 14)NOTE: PLEASE VERIFY FEEDERS INDICATED
 FOR 200A PANELS, 2A -6A.
 SHOWN AS 500MCM?
 THIS IS ONLY A NOTE:
  
 15)NOTE: PLEASE SEE FIRE PUMP IS SHOWN
 BEING FED FROM MSB. PLEASE SEE 695.3,
 THIS "ISNOT" PERMITTED.
 PLEASE ALSO SEE FIRE PUMP IS SHOWN WITH
 A ADDITIONAL FEED FROM FPL THROUGH AN
 ATS??
 PLEASE SEE NO SIZE OF FIRE PUMP IS
 SHOWN?
 PLEASE SEE NO MAIN SHOWN FOR THIS?
 PLEASE SEE NO INFORMATION SUBMITTED FOR
 FIRE PUMP?
 PLEASE SEE THIS IS PHYISCALLY
 IMPOSSIBLE.
 PLEASE SUBMIT ALL INFORMATION FOR FIRE
 PUMP, ATS, GENERATOR ETC.
 PLEASE SUBMIT MANUFACTURE SPEC SHEETS
 FOR ALL EQUIPMENT.
 PLEASE INCLUDE PRIME MOVER FOR
 GENERATOR.
 PLEASE SEE MISSING DISCONNECTING MEANS
 PER 225.31-225.36.
 PLEASE SEE MISSING EQUIPMENT GROUNDING
 FOR FEEDS TO FIRE PUMP.
 250.110,250.122
 PLEASE SEE MISSING INFORMATION FOR
 LOCKED ROTOR PER 695.4B1
 PLEASE SHOW ALL LOCATIONS OF ALL
 EQUIPMENT ON ELECTRICAL PLANS.
  
 16)NOTE: PLEASE CORRELATE GROUNDING
 ELECTRODE CONDUCTOR SIZES ON PLANS.
 PLEASE SEE ONE LOCATION SHOWS 4/0 AND
 THE OTHER 3/0?
 250.66
  
 17)NOTE: PLEASE VERIFY SEC'S SHOWN.
 THIS IS ONLY A NOTE AND NO CODE
 VIOLATION EXIST FOR SEC'S.
  
 18)NOTE: PLEASE SEE PANEL "L" IS SHOWN
 ON RISER TO BE FED FROM MSB, HOWEVER MSB
 SCHEDULE DOES NOT INDICATE THIS ?
 PLEASE CORRELATE.215.5
  
 19)NOTE: PLEASE SEE FIRE REVIEW COMMENTS
 PERTAINING TO FIRE ALARM PLANS REQUIRED.
  
 20)NOTE: PLEASE SEE OTHER POSSIBLE
 COMMENTS FROM OTHER REVIEWER(S) WHICH
 MAY HAVE AN AFFECT ON ELECTRICAL PLANS.
  
 PLEASE BE SURE TO REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW SHEETS INTO
 THREE COMPLETED SETS FOR REVIEW AND
 STAMPING.
  
 *** PLEASE SEE DUE TO THE AMOUNT OF
 MISSING INFORMATION ON PLANS, A COMPLETE
 REVIEWFOR CODE COMPLIANCE CAN NOT BE
 DONE AT THIS TIME.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  
 *** PLEASE SEE DUE TO THE AMOUNT OF
 MISSING INFORMATION ON PLANS, A COMPLETE
 REVIEWFOR CODE COMPLIANCE CAN NOT BE
 DONE AT THIS TIME.
2005-04-27 00:00:001 ROLL IN FOR ELECTRICAL REVIEW.