Plan Review Notes
Plan Review Notes For Permit 05040945
Permit Number 05040945
Review Stop B
Sequence Number 1
Notes
Date Text
2005-05-18 00:00:00BUILDING PLAN REVIEW
 PERMIT:05040945
 ADD: 2200 45TH STREET
 CONT: PLAN REVIEW
 TEL: (727)639-3598
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) ONCE PLANS ARE READY FOR ISSUANCE A
 NOC WILL BE REQUIRED.PROVIDE NOC
 RECORDED WITH THE CLERK OF COURT BEFORE
 A PERMIT CAN BE ISSUED.
  
 2)FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL
 IS NOT DEFINITLY KNOWN OR IS IN QUESTION
 THE BUILDING OFFICIAL MAY REQUIRE EXPLOR
 ATIONS, TEST OR OTHER ADEQUATE PROOF AS
 TO THE PERMISSIBLE SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL
 PROPERLY LICENSED IN THE STATE OF
 FLORIDA.
  
 3) FL S. S. 553.71(7) " THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN
 CY CLASSIFICATION AS DEINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS
 5,000 SQ FT IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
 105.13.1 THE ENFORCING AGENCY SHALL
 REQUIRE A SPECIAL INSPECTOR TO PERFORM
 SRUCTURAL INSPECTIONS ON A THRESHOLD
 BUILDING PURSUANT TO A STRUCTURAL INSPEC
 TION PLAN PREPARED BY THE ENGINEER OF
 RECORD. THE STRUCTURAL INSPECTION PLAN
 MUST BE SUBMITTED TO THE ENFORCING AGEN-
 CY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESH-
 OLD BUILDING. THE PURPOSE OF THE SRUCTUR
 AL INSPECTION PLAN IS TO PROVIDE SPECIF-
 IC INSPECTION PROCEDURES AND SCHEDULES
 SO THAT THE BUILDING CAN BE ADEQUATELY
 INSPECTED FOR COMPLIANCE WITH THE
 PERMITTED DOCUMENTS.
  
 4) WPB AMENDMENT 105.13.6. W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A
 SPECIAL INSPECTOR AS REQUIRED BY S.
 553.79(5) FLORIDA STATUTES TO THE MIN-
 IMUM INSPECTIONS REQUIRED BY THIS CODE.
 CONTACT HAROLD PISKURA MANAGER OF THE
 SPECIAL INSPECTOR PROGRAM AT (561)
 805-6711 FOR FURTHER INFORMATION BEFORE
 THE PERMIT MAY BE ISSUED.
  
 5)W.P.B. AMENDMENT 105.13.4.4 ALL
 PLANS FOR THE BUILDING WHICH ARE
 REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CON-
 TAIN A STATEMENT THAT, TO THE BEST OF
 THE ARCHITECT'S PR ENGINEER'S KNOWLEDGE,
 THE PLANS AND SPECIFICATIONS COMPLY WITH
 THE APPLICABLE FIRE-SAFETY STANDARDS AS
 DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 6) NOTE, FOR ALL PLANS, REPORTS, PRODUCT
 APPROVALS, SHOP DRAWINGS REVISIONS AND
 SUBMITTALS PROVIDE (3) COPIES OF ALL
 DOCUMENTS.
  
 7) FBC 13-103.1.2 BEFORE A BUILDING
 PERMIT CAN BE ISSUED, THE SUBMITTED
 ENERGY CODE COMPLIANCE FORMS SHALL BE
 SIGNED BY THE BUILDING OWNER, THE
 OWNER'S ARCHETECT OR OTHER AUTHORIZED
 AGENT LEGALLY DESIGNATED BY THE OWNER.
 THE P.E. DID SIGN THE ENERGY FORM BUT
 WHEN SUBMITTED FOR PUBLIC RECORD:
 PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 8) SHEET 0.02 BUILDING DATA, TYPE II,
 NOT 1 HR PROTECTED, SEE TABLE 600 FOR
 RATING OF STRUCTURAL COMPONENTS & FOR
 EXTERIOR WALLS.
  
 9) SHEET 0.02 PLANS INDICATE THAT THE
 BUILDING IS TO BE FIRE SPRINKLERED,
 PROVIDE PLANS AND CALCULATIONS.
 903.8.1. ANY BUILDINGS WHICH IS 3
 STORIES OR MORE HEIGHT SHALL BE EQUIPPED
 WITH AN APPROVED AUTOMATIC SPRINKLER
 SYSTEM IN ACCORDANCE WITH 903.1.
  
 10) SHEET 0.03: HOTELS: R1 OCCUPANCY,
 A) 4.7.3 RAMPS 4.7.3 REQUIRE 44" IF
 PART OF A MEANS OF EGRESS.
 B) 4.8(2) FL. LAW TOP LANDING REQUIRES
 60" AT THE TOP LANDING AND 72" CLEAR RUN
 FOR THE BOTTOM LANDING.
 C) 4.8(3) / FIGURE 17, SAME AS ABOVE
 REQUIRING 44" IF PART OF A MEANS OF
 EGRESS.
  
 11) SHEET 0.04 FIGURE 28 THE 3RD FIGURE
 TO THE RIGHT, WHERE THE PLAN INDICATES
 THE W.C. IS 18", THIS IS AN ABSOLUTE NOT
 A MINIMUM.
  
 12) SHEET 0.05 4.3.3 WIDTH SEE EXCEPTION
 44" IF PART OF A MEANS OF EGRESS.
  
 13) SHEET 0.1.3 NOTE, POOL, SPA ,FENCE &
 SIGNAGE REQUIRE A SEPERATE PERMIT.
  
 14) SHEET 1.1 NOTE 14 TYPE II BUILDING
 REQUIRES FIRE RETADANT TREATED WOOD,
 BACKING, ETC, SEE 609.2.1.
  
 15) SHEET 1.7, 2.1 PLANS INDICATE USE OF
 ASPHALT/ FIBERGLASS COMPOSITE ROOF
 SHINGLES, THE PRODUCT APPROVAL WAS
 TESTED UNDER PA 110 WHICH LIMITS THE USE
 TO A HEIGHT OF 33'. SEE LIMITATIONS 3.2.
  
 16) FL BLD CODE *104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 THERE SEEMS TO BE A DISCREPANCY BETWEEN
 THE STRUCTURAL AND ARCHITECTURAL PLANS.
 A2.1 DETAIL 5.5A/01 INDICATES 2"X6"
 WOOD WALLS, SECTIONS THROUGH VARIOUS
 EXTERIOR DETAILS INDICATE METAL STUD
 WALLS WITH EFIS SYSTEM WHERE AS S-1.03
 INDICATES EXTERIOR WALLS TO BE
 REINFORCED MASONARY WALLS.
  
 17) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 THERE ARE DETAILS FOR STO EFIS SYSTEMS
 BUT THE PRODUCT APPROVALS SUBMITTED ARE
 FOR DRYVIT, WHICH WILL BE USED.
  
 18) THE EFIS DETAILS USED ON A2.3/ A2.4
 DO NOT INDICATE WHAT TYPE OF WALL
 SHEATHING IS TO BE USEDNOR INTERIOR
 FINISH MATERIAL NOR THICKNESS, TABLE 600
 1 HR RATED FOR NON-LOADBEARING WALLS.
  
 19) SHEET S0.03, THE SIMPLIFIED
 PRESSURES INDICATED IN TABLE 1606.2 CAN
 ONLY BE USED TO 30' WITH MULTIPLIERS TO
 60'. DEPENDING ON THE POSITIVE &
 NEGATIVE PRESSURES REQUIRED FOR THIS
 BUILDING THE DRYVIT EFIS SYSTEM
 MAY BE LOW IN PRESSURES.THIS BUILDING
 HAS A MEAN ROOF HEIGHT OF 72', ASCE 7-98
 WILL BE REQUIRED FOR CALCULATING THE
 DESIGN PRESSURES FOR BUILDINGS IN EXCESS
 OF 60' IN HEIGHT.FBC 1606.1.1.S-0.01
 WIND LOADS INDICATES DESIGNED BY ASCE 7
 WHICH VERSION?
 19B) THE ARCHITECT DOES NOT INDICATE HOW
 HE DESIGNED THE BUILDING AT ALL?
  
 20) PLEASE INDICATE ON THE ELEVATIONS
 THE POSITVE & NEGATIVE PRESSURES, FOR
 THE WINDOWS, DOORS EFIS & ROOFING,
 INTERIOR ZONES AS WELL AS END ZONES.
 1606.1.1.
  
 21) A5.3 WALL SECTIONS INDICATE THE USE
 OF WOOD TRUSSES, TYPEII BLDG- SECTION
 604, STRUCTURAL MEMBERS INCLUDING
 TRUSSES, GIRDERS AND ROOFS (PLYWOOD)
 SHALL BE OF NON-COMBUSTIBLE MATERIALS
 AND ARE PROTECTED BY 1HR CONSTRUCTION
 (TABLE 600). ANNOTE PLANS FOR CODE
 COMPLIANCE.
  
 22) SHEET A5.9 LAUNDRY CHUTE, TABLE
 705.1.2 REQUIRES A 2 HR RATED SHAFT:
 A) THE SHAFT WALLS STOP AT THE FLOOR
 LINE PLANS INDICATE A 2 LAYER 2X
  
 B) THE RATED SHAFT STOPS BENEATH THE
 ROOF DECK
  
 C) ABOVE THE ROOF DECK NO SHAFT (2 HR
 RATING) IS REQUIRED.
  
 D) PLANS DO NOT INDICATE WHAT TYPE OF
 MATERIAL THE INTERNAL FRAMING OR
 SHEATHING IS COMPOSED FROM (CHIMNEY).
  
 E) INFORMATION ON HURRICANE STRAPPING
  
 23) SHEET A5.9 ELEVATOR VENTING:
 A)IS A CONTINUATION OF THE 2HR RATED
 SHAFT, TABLE 705.2.1, PROVIDE THE 2 HR
 SHAFTRATING THROUGH TO THE VENT,
 INDICATE WHICH ASSEMBLY WILL BE USED.
  
 B) 3003.6.3 THE AREA OF THE VENTS SHALL
 BE NOT LESS THAN 3 SQ FT FOR EACH
 ELEVATOR CAR, WHICHEVER IS GREATER.
 SINCE THERE IS (2) ELEVATOR CARS, A
 MINIMUM OF 6 SQ FT OF CLEAR VENT AREA IS
 REQUIRED. THE 28" VENT WILL BE ADEQUATE,
 INDICATE ON THE TERMINATION CAP THE
 CLEAR AREA HXW = X SQ FT.
  
 C) INDICATE THE STRTCHER REQUIREMENTS
 IN ONE OF THE ELEVATORS DETAILS:
 ?3003.4.1 IN ALL STRUCTURES THAT ARE
 MORE THAN THREE STORIES HIGH OR IN
 WHICH THE VERTICAL DISTANCE BETWEEN
 THE BOTTOM TERMINAL LANDING AND THE
 TOP TERMINAL LANDING EXCEEDS 25 FEET
 (7.6 M) MUST BE CONSTRUCTED TO
 CONTAIN AT LEAST ONE PASSENGER
 ELEVATOR THAT IS OPERATIONAL AND WILL
 ACCOMMODATE AN AMBULANCE STRETCHER 76
 INCHES (1931 MM) LONG AND 24 INCHES
 (610 MM) WIDE IN THE HORIZONTAL
 POSITION.THIS ELEVATOR SHALL BE
 IDENTIFIED.
  
 24) SHEET A5.9 EXHAUST DUCT DETAIL# 08
 HAS THE SAME PROBLEM AS THE LAUNDRY
 CHUTE THE SHAFT IS NOT CONTINIOUS FROM
 FLOOR TO FLOOR, THERE IS WOOD 2X'S IN
 THE SHAFT CONSTRUCTION, PROVIDE THE
 ASSEMBLY WITH THIS APPLICATION, ALSO IF
 BUILT TO FLOOR/ CEILING AND NOT
 CONTINIOUS:705.7.1 JOINTS INSTALLED
 IN OR BETWEEN FIRE RESISTANT WALLS, FIRE
 RESISTANT FLOORS OR FLOOR/ CEILING
 ASSEMBLIES AND FIRE RESISTANT ROOFS OR
 ROOF/ CEILING ASSEMBLIES SHALL BE
 PROTECTED BY AN APPROVED FIRE RESISTANT
 JOINT SYSTEM DESIGNED TO RESIST THE
 PASSAGE OF FIRE FOR A PERIOD NOT LESS
 THAN THE REQUIRED FIRE RESISTANCE RATING
 OF THE WALL, FLOOR OR FLOOR IN OR
 BETWEEN WHICH IT IS INSTALLED.
  
 25) SHEET 6.2 STAIR HANDRAILS:
 A) ?11-4.9.4(1) HANDRAILS SHALL BE
 CONTINUOUS ALONG BOTH SIDES OF STAIRS.
 THE INSIDE HANDRAIL ON SWITCHBACK OR
 DOGLEG STAIRS SHALL ALWAYS BE CONTINUOUS
 SEE FIGURE 11-19(A) & FIGURE 11-19(B)).
  
 B) SAME SHEET DETAIL NUMBER 5:
 11-4.9.4(3) THE CLEAR SPACE BETWEEN
 HANDRAILS AND WALL SHALL BE 1-1/2 INCHES
 (38 MM).
  
 C) SAME SHEET DETAIL NUMBER 10:
 11-4.9.4(2) AT THE BOTTOM, THE HANDRAIL
 SHALL CONTINUE TO SLOPE FOR A DISTANCE
 OF THE WIDTH OF ONE TREAD FROM THE
 BOTTOM RISER; THE REMAINDER OF THE
 EXTENSION SHALL BE HORIZONTAL (SEE
 FIGURE 11-19(C) AND FIGURE 11-19(D)).
 HANDRAIL EXTENSIONS SHALL COMPLY WITH
 11-4.4.
  
 26) A-9.06 DOOR SCHEDULE DOORS TO THE
 STAIR TOWERS TO BE 60 MIN TABLE 705.1.2
 REQUIRESA 1 1/2 HR RATED DOOR.
  
 27) SHEET A5.15/A5.16
 A) DISCREPANCY, A5.15 DETAIL 1 INDICATES
 A FLUE WHILE THE NEXT PAGE INDICATES A
 VENTLESS FIRE PLACE.
  
 B) PROVIDE THE MANUFACTURES SPEC FOR
 THE VENTLESS FIREPLACE:SECTION 2809
 GAS APPLIANCES:GAS APPLIANCES SHALL BE
 INSTALLED AND VENTED IN ACCORDANCE WITH
 THE REQUIREMENTS OF THE FLORIDA BUILDING
 CODE, FUEL GAS.
  
  
  
 27) A-201/ A-202, THERE ARE NUMEROUS
 DOORS THAT DO NOT HAVE THE REQUIRED18"
 CLEAR ON THE PULL LATCH SIDE.
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 28) SHEET A-2,01 RESTROOMS 112, DOORS
 SWING INTO THE REQUIRED CLEAR FLOORSPACE
 FOR FIXTURES, 11-4.19.3.
  
  
  
  
  
 31) SHEET A-10.06/A-10.07/ A-10.08
 ADDITIONAL INFORMATION IS REQUIRED,
 SUBMITTED IS A FLORIDA COVER SHEET
 LISTING FL 3627, WHICH TIES TO PRODUCT
 EVALUATION REPORTS FROM FRANK L BENNARDO
 A MIAMI-DADE REPORT WAS SUBMITTED. THERE
 IS A DIFFERENT FL# (FL#379) FOR THE
 MIAMI-DADE REPORT. PROVIDE THE CORRECT
 FLORIDA COVERSHEET WITH THE ASSOCIATED
 REPORT.
  
 32) SHEET A-10.11/ A-10.12 SUBMITTED A
 ROOFING REPORT FOR NON STRUCTURAL METAL
 ROOFING. THIS REPORT PRESSURE ISGOOD
 FOR ONLY 52.5 PSF. THIS ROOF WILL
 ENCOUNTER HIGHER PRESSURES THAN THIS IN
 ROOF ZONES 2 AND 3. SECOND PROBLEM THE
 ENGINEERING SHEETS THAT TIE TO THE FL
 COVERSHEET FROM C-BUCK ENGINEERING WERE
 NEVER SUBMITTED.
  
 33) SHEET A-10.13/ A-10.14 ARE FOR PGT
 HORIZONTAL SLIDERS ,THE FL COVERSHEET
 INDICATES THIS IS A NON-IMPACTWINDOW,
 SEE HIGHLIGHTED NOA# INDICATING NON-
 IMPACT RATING. THE SECOND ISSUE INDICATE
  
 WHICH TYPE OF GLAZING TO BE INSTALLED
 FOR PRESSURE RATINGS, MAY BE LOW VALUES.
  
 34) SHEET A-10.15/ A-10.16 SUBMITTED
 SHEETS FOR PGT FIXED GLAZING, INDICATE
 WHICH GLAZING SHALL BE USED TO SEE IF
 THE PRESSURES ARE MET.
  
 35)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) FIXED WINDOWS
 B) HORIZONTAL SLIDERS
 C) EXTERIOR GLAZED HORIZONTAL SLIDING
 DOORS
 D) SWING DOORS- GLAZED
 E) SWING DOORS-SOLID
 F) MULLIONS
 G) LOUVERS
 H) EFIS SYSTEMS
 I) TRUSS ANCHORS
 J) ROOFING ASSEMBLIES
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 36)1707.4.3 EACH EXTERIOR DOOR ASSEMBLY
 NOT COVERED BY 1707.4.2
 (GLAZED DOORS) SHALL BE LISTED AND TEST-
 ED FOR A PERIOD EQUAL TO THE QUANITY
 3600/ V WHERE THE TIME PERIOD IS IN
 SECTIONS AND V IS IN MILES PER HR TAKEN
 FROM FIGURE 1606. THE TIME PERIOD SHALL
 ALSO INCLUDE A 10 SECOND PERIOD AT A
 LOAD EQUAL TO 1.5 TIMES THE DESIGN
 PRESSURE. DADE COUNTY & SBCCI REPORTS
 ARE ACCEPTED.
  
 37) 1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 38) 1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 39) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED, SHEET
 S-101 INDICATES THAT THE FOUNDATION
 DESIGN IS INCOMPLETE DEPENDING ON THE
 SOILS REPORT? PLANS DO NOT PROVIDE
 INFORMATION ON CAST IN PLACE CONCRETE
 PILES, LOCATION, GROUT, ETC.
  
 40) S-2.02 SECTION B PORT COCHERE
 INDICATES THE USE OF WOOD TRUSSES AND
 WOOD SHEATHING, TYPE II BUILDING, SEE
 TABLE 600 ROOFS & ROOF /CEILING
 ASSEMBLIES FOOTNOTE "E".
  
 41) S1.04 ROOF TRUSSES:
 A)TYPE II BUILDING ROOF- NONCOMBUSTIBLE
 STRUCTURAL ELEMENTS TRUSSES & WOOD DECK.
 B) PROVIDE UPLIFT FOR THE ROOF FRAMING
 MEMBERS, DIRECTION,MAGNITUDE OF THE
 LOADS TO BE RESISTED.1606.1.1/ 1606.1.3,
 PART OF THE MAIN WIND FORCE RESISTING
 SYSTEM.
 C)1707.3.1 JOIST HANGERS, FRAMING
 ANCHORS & SIMILAR DEVICES SHALL BE TEST-
 ED IN ACCORDANCE W/ ASTM D 1761 & BE
 LABELED AND LISTED FOR THEIR LOAD CARRY-
 ING CAPACITY.
 D) 1609.4.3 LOAD REDUCTION.
 WHEN STRUCTURAL EFFECTS DUE TO TWO OR
 MORE LOADS IN COMBINATION WITH DEAD LOAD
 ARE INVESTIGATED IN LOAD COMBINATIONS OF
 1609.4.1 OR 1609.4.2, THE COMBINED
 EFFECTS DUE TO THE TWO OR LOADS MULTI-
 PLIED BY 0.75 PLUS EFFECTS DUE TO DEAD
 LOADS SHALL NOT BE LESS THAN THE EFFECTS
 FROM THE LOAD COMBINATION OF THE DEAD
 LOAD PLUS THE LOAD PRODUCING THE LARGEST
 EFFECTS. INCREASE IN ALLOWABLE STRESS
 SPECIFIED IN THE MATERIALS SECTIONS OF
 THIS CODE OR A REFRENCED STANDARD SHALL
 NOT BE USED WITH THESE LOAD COMBINATIONS
 EXCEPT THAT A DURATION OF LOAD INCREASE
 SHALL BE PERMITTED IN ACCORDANCE WITH
 CHAPTER 23 (WOOD).
  
 42) SHEET A-5.2 SECTION 02, BUILDING
 SECTION B-B:
  
 A) DEMONSTRATE COMPLIANCE WITH:
 2305.2.2 3. OTHER BUILDINGS.IN
 FLOOR/CEILING ASSEMBLIES SO THAT
 HORIZONTAL AREAS DO NOT EXCEED 1,000 SQ
 FT (92.9 M^2).
 2305.2.3(3) WHERE APPROVED SPRINKLERS
 ARE PROVIDED, DRAFTSTOPPING SHALL BE
 REQUIRED FOR AREAS OVER 9,000 SQ FT (836
 M^2).
  
 B)SEE NOTE FOR VENTILATION AND DRAFT
 STOPPING "LOCAL CODE REQUIREMENTS",
 104.2.1 W.P.B. ADMINISTRATIVE CODE
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR
 OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES.
 SUCH INFORMATION SHALL BE SPECIFIC AND
 THE TECHNICAL CODES "SHALL NOT BE CITED
 AS A WHOLE OR IN PART, NOR THE TERM
 "LEGAL" OR ITS RQUIVALENT BE USED AS A
 SUBSTITUTE FOR SPECIFIC INFORMATION".
  
 C)(WOOD)?2309.7.1 FOR GABLED AND HIPPED
 ROOFS, VENTILATION SHALL BE PROVIDED TO
 FURNISH CROSS VENTILATION OF EACH
 SEPARATE ATTIC SPACE WITH WEATHER
 PROTECTED VENTS.ALL VENTS SHALL BE
 SCREENED TO PROTECT THE INTERIOR FROM
 INTRUSION OF BIRDS.THE RATIO OF
 TOTAL NET FREE VENTILATING AREA TO THE
 AREA OF THE CEILING SHALL BE NOT LESS
 THAN 1/150.
  
 43) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 SHEET A-5.3 INDICATES THE USE OF GABLE
 TRUSSES WITH A LOWER ROOF AND HIGHER
 SECTION OF TRUSS CREATING A WALL SECTION
 BETWEEN THE TO ROOF SYSTEMS. PROVIDE A
 SECTION INDICATING THE ROOF BRACING OF
 WALL.
  
 44) SHEET M101-107 GENERAL NOTES
 INDICATE "PROVIDE A CONCEALED CONDENSATE
 STACK WITHIN THE OUTSIDE WALL, PROVIDE
 ADDITIONAL INFORMATION, ?705.6
 PENETRATIONS OF HORIZONTAL ASSEMBLIES.
 ALL PENETRATIONS OF A FLOOR, FLOOR
 / CEILING ASSEMBLY, OR THE CEILING
 MEMBRANE OF A ROOF/CEILING ASSEMBLY
 SHALL BE PROTECTED BY A SHAFT ENCLOSURE
 IN ACCORDANCE WITH ?705.2 OR
 SHALL COMPLY WITH ?705.6.1 THROUGH
 ?705.6.4.?705.6.1 THROUGH
 PENETRATIONS. THROUGH-PENETRATIONS OF
 FIRE RATEDHORIZONTAL ASSEMBLIES SHALL
 COMPLY WITH ?705.6.1.1 OR ?705.6.1.2.
  
 45) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 SHEET M-201 INDICATES THE USE OF ROOFTOP
 MAKE UP AIR AND EXHAUST UNITS, PROVIDE
 THE FRAMING AND ANCHORING DETAILS.
  
 46) SHEET A-5.5A SECTION# 9, INDICATES
 THE USSE OF 5/8" TYPE"X" GYPSUM SOFFIT
 BOARD FINISH. PROVIDE REPORT FOR THIS TO
 BE AN ACCEPTABLE APPLICATION FOR THIS
 PRODUCT (PRODUCT APPROVAL). ES REPORTS
 INDICATE THIS ISTO BE USED FOR
 CEILINGS IN CARPORTS WHAT FINISH
 APPLICATION IS TO BE USED?
  
 47)DAVID I WALLACE & ASSOCIATES, P. A.,
 481.219 F.S.CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ARCHITECT
 PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING
 ARCHITECTURAL SERVICES, SHALL INCLUDE
 THE CERTIFICATE OF AUTHORIZATION
 NUMBER.ADD THE NUMBER TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
  
 48)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 49) ADDITIONAL FEES DUE, CALCULATED
 VALUE FOR THIS BUILDING IS :
 $6,195,792.00.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  
  
  
  
  