| 2005-07-06 00:00:00 | SECOND CHECKLIST: |
| | 1- NEED RECORDED NOTICE OF COMMENCEMENT. |
| | |
| | 2- THERE ARE COMPANIES WHO HAVE DESIGNED |
| | BBQ'S SPECIFICALLY FOR LANAI OR PORCH |
| | AND THEY REQUIRE EXHAUST HOOD. THE |
| | BUILDING OFFICIAL NEEDS TESTING AND |
| | ENGINEERING TO SUPPORT STATEMENT ON |
| | LETTER THAT EXHAUST HOOD IS NOT |
| | REQUIRED. ALSO, LETTER IS NOT ACCEPTABLE |
| | BECAUSE IT'S SIGNED BY NOBODY. |
| | |
| | 3- CLARIFY IF USING STORM SHUTTERS OR |
| | DOORS WITH IMPACT GLAZING. SLIDING GLASS |
| | DOORS PRODUCT APPROVAL SUBMITTED HAVE |
| | IMPACT GLAZING. |
| | CLARIFY WHICH OPENINGS WILL HAVE |
| | SHUTTERS OR NOT. |
| | PROVIDE COMPLETE SHUTTERS INFORMATION OR |
| | APPLY UNDER A SEPARATE PERMIT. STILL, |
| | CLARIFY OPENINGS TO HAVE SHUTTERS. |
| | |
| | 4- SHEET A3: A) REVISE/UPDATE TRUSS |
| | ANCHOR SCHEDULE (NOT DONE FROM PREVIOUS |
| | CHECKLIST). SEE LATEST CATALOGUE THAT |
| | WAS REVISED TO COMPLY WITH SEC. 1609.4.3 |
| | FBC 2001. OTHERWISE, PROVIDE TESTING AND |
| | ENGINEERING FOR NAIL SIZE AND NUMBER |
| | THAT DIFFER FROM THOSE TESTED AND |
| | PUBLISHED BY THE MANUFACTURER. SEC. |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | |
| | B) CONNECTOR THD210 IS A WOOD TO WOOD |
| | CONNECTOR. NEED MASONRY HANGER. SEE |
| | CATALOGUE FOR PROPER MASONRY CONNECTOR. |
| | |
| | C) DETAIL E/A3: CLARIFY WHY HAVING 6" |
| | BOLTS INTO CONCRETE IF THERE IS NOT |
| | CONCRETE WALL TO BE ATTACHED TO.SEC. |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | |
| | 5- A)FLORIDA PRODUCT APPROVAL FOR CORNER |
| | |
| | SLIDING GLASS DOORS AND DADE COUNTY NOA |
| | SUBMITTED DON'T CORRESPOND TO EACH OTHER |
| | |
| | B) CLARIFY IF USING DOORS WITH IMPACT |
| | GLASS OR NOT AND PROVIDE CORRECT FLORIDA |
| | PRODUCT APPROVAL. |
| | |
| | 6- MULLION SIZE SPECIFIED FOR FIXED |
| | WINDOWS AT LIVING ROOM IS NOT GOOD. SEE |
| | DESIGN PRESSURES ON PLANS AND ON |
| | PRODUCT APPROVAL. REVISE MULLION SIZE |
| | AND ANCHOR AS REQUIRED AND PROVIDE |
| | PROPER FLORIDA PRODUCT APPROVAL FOR EACH |
| | TYPE OF MULLIONS. |
| | |
| | 7- DADE COUNTY NOA SUBMITTED FOR |
| | CASEMENT WINDOWS DOESN'T MATCH NOA |
| | SUBMITTED FOR FLORIDA PRODUCT APPROVAL. |
| | PROVIDE MATCHING NOA AND VERIFY THAT |
| | ASSEMBLY MATCHES ONE SHOWN ON PLANS TOO. |
| | |
| | 8- REAR ELEVATION DOESN'T MATCH FLOOR |
| | PLAN. SEE WINDOWS SPECIFIED ON PLAN FOR |
| | LIVING ROOM AREA AND REVISE AS REQUIRED. |
| | |
| | 9- PROVIDE FLORIDA PRODUCT APPROVAL FOR |
| | IMPACT GLASS CASEMENT WINDOW AT |
| | BREAKFAST AREA. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |