| 2005-05-31 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1- NEED RECORDED NOTICE OF COMMENCEMENT. |
| | |
| | 2- SHEET T1: A) UPDATE GENERAL NOTES. |
| | SEE COMMENTS ON PLANS AND RETURN |
| | REVIEWED PAGE AFTER CORRECTIONS ARE DONE |
| | TO EXPEDITE THE REVIEW PROCESS. |
| | |
| | B) DESIGN PARAMETERS. CLARIFY WHERE IS |
| | THE BASIC VELOCITY PRESSURE TAKEN FROM. |
| | THIS IS NO APPLICABLE TO THE FBC. SEE |
| | CHAPTER 16 FBC 2001. (THIS WAS |
| | APPLICABLE TO THE SBC 1997) |
| | ALSO, CLARIFY WHY THE MIN. SOIL BEARING |
| | PRESSURE IS: NA? |
| | |
| | 3- PROVIDE COMPLETE SPECS FOR BBQ |
| | SHOWING THAT IT WAS DESIGNED TO BE |
| | INSTALLED IN THE PORCH. SEC.2808 FBC |
| | 2001. |
| | |
| | 4- PROVIDE COMPLETE INFORMATION FOR |
| | STORM SHUTTERS OR APPLY FOR A SEPARATE |
| | PERMIT. |
| | |
| | 5- SHEET A1: A) SPECIFY COLUMNS AT BAY |
| | WINDOW AT MASTER BEDROOM. |
| | |
| | B) WHAT IS TS-2 SPECIFIED ON CONCRETE |
| | PAD BETWEEN GARAGE AND BEDROOM #2. SEC. |
| | 104.2.1.2 CITY AMENDMENTS TO FBC. |
| | |
| | C) DETAIL 5 FOR FOOTING BETWEEN GARAGE |
| | AND CLUB ROOM DON'T MATCH. REVISE AS |
| | REQUIRED. |
| | |
| | 6) REVISE SIZESFOR FIXED WINDOW AT |
| | LIVING ROOM (36" X 234" FG ?). |
| | |
| | 7) SHEET A3: A) REVISE/UPDATE TRUSS |
| | ANCHOR SCHEDULE. SEE LATEST CATALOGUE |
| | WHICH WAS REVISED TO COMPLY WITH SEC. |
| | 1609.4.3 FBC 2001. PROVIDE COMPLETE |
| | ENGINEERING CALCULATIONS FOR FASTENERS |
| | THAT DIFFER FROM THOSE TESTED AND |
| | PUBLISHED BY MANUFACTURER. |
| | |
| | B) CONNECTOR THD210 IS A WOOD TO WOOD |
| | CONNECTOR. NEED MASONRY HANGER. SEE |
| | CATALOGUE FOR PROPER MASONRYCONNECTOR. |
| | |
| | C) DETAIL E/A3: CLARIFY WHY HAVING 6" |
| | BOLTS INTO CONCRETE. THERE IS NOT |
| | CONCRETE WALL TO BE ATTACHED TO? SEC. |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | |
| | 8- PROVIDE FLORIDA OR APPLY FOR LOCAL |
| | PRODUCT APPROVAL FOR SLIDING GLASS DOORS |
| | WITH CORNER ASSEMBLY AS SHOWN ON PLANS. |
| | |
| | 9-WINDOW AND DOOR MULLIONS: CLEARLY |
| | INDICATE MULLION SIZE AND FASTENERS TO |
| | BE USED TO VERIFY THAT IT MEETS THE |
| | DESIGN PRESSURES CALCULATED ON PLANS. |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC |
| | 2001. |
| | |
| | 10- DADE COUNTY NOA SUBMITTED FOR |
| | CASEMENT WINDOWS DOESN'T MATCH NOA |
| | SUBMITTTED FOR FLORIDA PRODUCT APPROVAL. |
| | PROVIDE MATCHING NOA. |
| | |