| 2005-08-02 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1- NEED TO PASS ZONING FIRST. IF HOUSE |
| | NEEDS TO BE LOCATED ON THE ZERO LOT LINE |
| | THEN OPENINGS ARE NOT ALLOWED BY TABLE |
| | 600 FBC 2001. |
| | |
| | 2- NEED RECORDED NOTICE OF COMMENCEMENT. |
| | |
| | 3- PROVIDE COMPLETE SPECS FOR APPROVED |
| | BBQ AND EXTERIOR HOOD. SEC. 2808 FBC |
| | 2001. SEE PLANS FOR ARCHITECT'S SPECS. |
| | |
| | 4- STILL IS NOT CLEAR IF USING SHUTTERS |
| | OR IMPACT GLAZING. LETTER SUBMITTED |
| | STATES THAT SHUTTERS UNDER A SEPARATE |
| | PERMIT. WHILE, ARCHITECT'S PLANS STATES |
| | THAT IMPACT GLASS TO BE USED IN DOORS |
| | AND WINDOWS. IN ADDITION, SOME OF THE |
| | PRODUCT APPROVALS SUBMITTED ARE WITH |
| | IMPACT GLAZING AND OTHERS ARE NOT. |
| | PROVIDE COMPLETE CONSTANT INFORMATION |
| | FOR EITHER WAY TO EXPEDITE AND |
| | FACILITATE THE REVIEW. |
| | |
| | 5- IF IMPACT GLASS IS NOT USED, THEN |
| | PLANS NEED TO SPECIFY SAFETY GLASS IN |
| | HIS BATH, HER BATH, GUEST BATH AND BATH |
| | #3. SEC. 2405.2. FBC 2001. |
| | |
| | 6- ANCHOR SCHEDULE: CLARIFY WHY |
| | CONNECTORS G AND H HAVE THE SAME UPLIFT |
| | CAPACITY IF THEY HAVE DIFFERNT NUMBER OF |
| | NAILS. SEE CATALOGUE FOR NUMBER OF NAILS |
| | TO BE USED TO OBTAIN TESTED UPLIFT |
| | CAPACITY. PROVIDE TESTING RESULTS AND |
| | ENGINEERED CALCS FOR NAIL NUMBER THAT |
| | DIFFER FROM THOSE TESTED AND PUBLISHED |
| | BY THE MANUFACTURER. SEC. 104.2.1.2 |
| | CITY AMENDMENTS TO FBC 2001. |
| | |
| | 7- MULLION SIZE SPECIFIED FOR FIXED |
| | WINDOWS IN LIVING ROOM AREA DOESN'T |
| | RESIST THE DESIGN PRESSURES. SEE PRODUCT |
| | APPROVAL. SPECIFY BIGGER MULLION AND |
| | ANCHORS. SEC. 104.2.1.2 CITY AMENDMENTS. |
| | |
| | 8- PROVIDE FLORIDA OR LOCAL PRODUCT |
| | APPROVAL FOR: |
| | A) MULLION SPECIFIED BY ARCHITECTON |
| | ITEM #7 ABOVE. |
| | B) CASEMENT WINDOWS THAT MATCH FLORIDA |
| | PRODUCT APPROVAL AND WINDOWS SHOWN ON |
| | PLANS. |
| | C) ALL WINDOWS AND DOORS TO BE USED. |
| | IMPACT OR NON IMPACT. |
| | |
| | 9- PROVIDE COMPLETE SPECS AND LISTING |
| | FOR FIREPLACE SHOWING COMPLIANCE WITH |
| | 2806 FBC 2001. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ AT (561)805-6712. |