| 2005-06-02 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | |
| | 1- SEE COMMENTS BY ZONING. IF HOUSE |
| | NEEDS TO BE LOCATED ON THE ZERO LOT |
| | LINE, THEN, OPENINGS ARE NOT ALLOWED BY |
| | TABLE 600 FBC 2001. |
| | |
| | 2- NEED RECORDED NOTICE OF COMMENCEMENT. |
| | |
| | 3- SHEET T1: A) UPDATE GENERAL NOTES. |
| | SEE COMMENTS ON PLANS. SEE RESPECTIVE |
| | FBC CHAPTER FOR PROPER REFERENCE (EG: |
| | CHAPTER 19 ACI 318) AND CHAPTER 35 FOR |
| | PROPER REFERENCE EDITION. |
| | |
| | B) DESIGN PARAMETERS: CLARIFY WHERE IS |
| | THE BASIC VELOCITY PRESSURE TAKEN FROM. |
| | SEE SECTION 1606 FBC 2001. |
| | ALSO, CLARIFY WHY THE MIN. SOIL BEARING |
| | PRESSURE IS - NA?. |
| | |
| | 4- PROVIDE COMPLETE SPECS FOR BBQ |
| | SHOWING THAT IT WAS DESIGNED TO BE |
| | INSTALLED IN THE PORCH. SEC. 2808 FBC |
| | 2001. |
| | |
| | 5- PROVIDE COMPLETE INFORMATION FOR |
| | STORM SHUTTERS OR APPLY FOR A SEPARATE |
| | PERMIT. |
| | |
| | 6- SHEET A1: A) SPECIFY COLUMNS AT BAY |
| | WINDOW IN MASTER BEDROOM. |
| | |
| | B) WHAT DOES TS-2 SPECIFIED ON CONCRETE |
| | PAD BETWEEN GARAGE AND BEDROOM #2 STANDS |
| | FOR?. SEC. 104.2.1.2 CITY AMENDMENTS TO |
| | FBC 2001. |
| | |
| | C) DETAIL 5 FOR FOOTING BETWEEN GARAGE |
| | AND CLUB ROOM DOESN'T MATCH. REVISE AS |
| | REQUIRED. |
| | |
| | 7- SHEET A2; A) NOTE #1 AND #6 CALL FOR |
| | IMPACT GLAZING ON DOORS AND WINDOWS. |
| | NOTE ON DESIGN PRESSURES CHART SHOWN ON |
| | ELEVATIONS CALLS FOR STORM SHUTTERS. |
| | CLARIFY/REVISE AS REQUIRED. |
| | |
| | B) REVISE SIZES FOR FIXED WINDOWS AT |
| | LIVING ROOM (36' X 234" FG ?). |
| | |
| | C) SPECIFY SAFETY GLASS AT HIS BATH, HER |
| | BATH, GUEST SUITE BATH, BATH #3 AND |
| | LIVING ROOM. SEE PLANS AND SECTION |
| | 2405.2 FBC 2001. |
| | |
| | 8- SHEET A3: A) REVISE/UPDATE TRUSS |
| | ANCHOR SCHEDULE. SEE LATEST CATALOGUE |
| | (2005) WHICH WAS REVISED TO COMPLY WITH |
| | SEC. 1609.4.3 FBC 2001. OR, PROVIDE |
| | COMPLETE ENGINEERING CALCS THAT COMPLY |
| | WITH SEC. 1609.4.3 FBC 2001 FOR TYPE AND |
| | NUMBER OF CONNECTORS THAT DIFFER FROM |
| | THOSE TESTED AND PUBLISHED BY THE |
| | MANUFACTURER. SEC. 104.2.1.2OF CITY |
| | AMENDMENTS TO FBC 2001. |
| | |
| | B) CONNECTOR THD210 IS A WOOD TO WOOD |
| | CONNECTOR. NEED MASONRY CONNECTOR. SEE |
| | CATALOGUE FOR PROPER MASONRY CONNECTOR. |
| | |
| | C) DETAIL E/13 DOESN'T APPLY. THERE IS |
| | NOT CONCRETE WALL TO BE ATTACHED TO. |
| | REVISE AS REQUIRED. SEE PLANS. SECTION |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | |
| | D) SPECIFY CONNECTOR FOR TRUSS GIRDER |
| | RESTING ON WOOD COLUMN LOCATED IN |
| | VESTIBULE FOR CLUB ROOM AND MASTER |
| | BEDROOM. SEC. 104.2.1.2 CITY AMENDMENTS. |
| | |
| | 9- PROVIDE FLORIDA OR APPLY FOR LOCAL |
| | PRODUCT APPROVAL FOR CORNER SLIDING |
| | GLASS DOORS. |
| | |
| | 10- WINDOW AND DOOR MULLIONS: CLEARLY |
| | SPECIFY MULLION SIZE AND ANCHOR TYPE TO |
| | BE USED ACCORDING TO THE ASSEMBLY TO BE |
| | INSTALLED ON TO VERIFY COMPLIANCE WITH |
| | THE DESIGN PRESSURES. SEC. 104.2.1.2 |
| | CITY AMENDMENTS TO FBC 2001. |
| | |
| | 11- DADE COUNTY NOA SUBMITTED FOR |
| | CASEMENT WINDOWS DOESN'T MATCH NOA |
| | LISTED ON FLORIDA PRODUCT APPROVAL COVER |
| | PAGE. REVISE AS REQUIRED. |
| | |
| | 12- PROVIDE COMPLETE SPECS AND LISTING |
| | FOR FIREPLACE SHOWING COMPLIANCE WITH UL |
| | 127 REQUIREMENTS. SEC. 2806 FBC 2001. |
| | |
| | ***PLEASE DON'T STAPLE PRODUCT APPROVALS |
| | TO PLANS. |
| | |