| 2005-07-06 00:00:00 | SECOND CHECKLIST: |
| | 1- NEED RECORDED NOTICE OF COMMENCEMENT. |
| | |
| | 2- PROVIDE COMPLETE INFORMATION FOR |
| | STORM SHUTTERS OR APPLY FOR A SEPARATE |
| | PERMIT. |
| | |
| | 3- THE BUILDING OFFICIAL IS THE ONE WHO |
| | APPROVES THE BBQ INSTALLATION. HE WANTS |
| | TO SEE TESTING AND ENGINEERING |
| | JUSTIFYING WHY PROPOSED INSTALLATION |
| | DOESN'T NEED THE EXHAUST HOOD SINCE |
| | THERE ARE OTHER COMPANIES WHO DESIGNED |
| | BBQ'S FOR LANAI OR PORCH INSTALLATION |
| | AND THEY REQUIRE HOOD EXHAUST. |
| | LETTER SUBMITTED IS INSUFFICIENT AND IS |
| | SIGNED BY NOBODY. BESIDES, MANUFACTURER |
| | SPECS SAYS FOR OUTDOOR INSTALLATION ONLY |
| | |
| | 4- SHEET A3: A) REVISE/UPDATE TRUSS |
| | ANCHOR SCHEDULE (NOT DONE FROM PREVIOUS |
| | CHECKLIST). SEE LATEST CATALOGUE WHICH |
| | WAS REVISED TO COMPLY WITH SECTION |
| | 1609.4.3 FBC 2001. PROVIDE TESTING AND |
| | ENGINEERING CALCS FOR NUMBER AND SIZE OF |
| | NAILS THAT DIFFER FROM THOSE ALREADY |
| | TESTED AND PUBLISHED BY MANUFACTURER. |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| | |
| | B) CONNECTOR THD210 IS A WOOD TO WOOD |
| | CONNECTOR. NEED TO SPECIFY MASONRY |
| | CONNECTOR. SEE CATALOGUE FOR PROPER |
| | MASONRY CONNECTOR. |
| | |
| | C) SPECIFY CONNECTOR FOR TRUSS GIRDER |
| | END AT INTERSECTION OF MASTER BEDROOM |
| | AND CLUB ROOM CORNER. SEE PLANS. |
| | |
| | 5- A)SLIDING GLASS DOORS NOA AND FLORIDA |
| | PRODUCT APPROVAL DON'T CORRESPOND TO |
| | EACH OTHER. |
| | B) NOA SUBMITTED IS FOR IMPACT DOORS. |
| | ARE IMPACT DOORS GOING TO BE INSTALLED? |
| | |
| | 6- MULLIONS SPECIFIED FOR WINDOWS AT |
| | LIVING ROOM DON'T RESIST CALCULATED |
| | DESIGN PRESSURES. REVISE SIZE OF |
| | MULLIONS AND PROVIDE PRODUCT APPROVAL |
| | AS REQUIRED. |
| | |
| | 7- DADE COUNTY NOA SUBMITTED FOR |
| | CASEMENT WINDOWS DOESN'T MATCH NOA |
| | LISTED IN THE FLORIDA PRODUCT APPROVAL. |
| | REVISE AS REQUIRED AND MAKE SURE IS THE |
| | TYPE OF WINDOW ASSEMBLY TO BE INSTALLED. |
| | |
| | 8- REAR ELEVATION DOESN'T MATCH FLOOR |
| | PLAN. REVISE LIVING ROOM WINDOW AND |
| | CABANA BATH WING TO MATCH FLOOR PLAN. |
| | |
| | 9- PROVIDE FLORIDA OR LOCAL PRODUCT |
| | APPROVAL FOR IMPACT GLASS CASEMENT |
| | WINDOW FOR BREAKFAST AREA. |
| | |
| | 10- PROVIDE ENERGY CALCULATIONS SHOWING |
| | WORST CASE SCENARIO FOR THIS MODEL. |
| | CALCULATIONS TO MATCH FLOOR PLAN. SEE |
| | OVERHANG LENGTH AND HEIGHT, SIZES OF |
| | WINDOWS/DOORS ETC. |
| | |
| | |