| Plan Review Notes For Permit 05040918 |
| Permit Number |
05040918 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-04-26 00:00:00 | MECH. PLAN REVIEW. | | | | | | FIRST FLOOR: | | | 1. NO R/A OUT OF FIRST FLOOR MASTER | | | BEDROOM AREA.2003 FBC/M 601.4 . | | | 2. NO EXHAUST FAN REFLECTED IN MASTER | | | BATH AREA.2001 FBC/M 402.3.1 . | | | 3. AHU #1 SUPPLY AIR REFLECT 12" TO | | | FIRST TRIANGEL THEN GOES TO 14" . | | | | | | SECOND FLOOR: | | | 1. AHU #2 NOT REFLECTED ON PLAN. | | | 2. R/A DUCT BETWEEN AHU #2 AND 24/18 | | | GRILL NOT REFLECTED. | | | | | | PAT RAFTER 561/805/6728 OR 805/6719 | | | PATTY KRAUSS. | | | PLEASE CALL IF THEAR ANY QUESTIONS. |
|