| 2005-04-25 00:00:00 | ********UNSAT ********* |
| | |
| | 1)NOTE: PLEASE SEE PANEL "B" (2P80A) |
| | FEEDING #12 AWG.PLEASE SEE 310.16,240.4 |
| | |
| | 2)NOTE: PLEASE SEE SOME MISSING RECEPTS |
| | PER 210.52 |
| | |
| | 3)NOTE: PLEASE SEE CODES REFERENCED IN |
| | NOTES ARE FROM THE 1996 NEC. PLEASE SEE |
| | NEW REVISED ARTS. IN 2002 NEC. |
| | |
| | 4)NOTE: PLEASE SEE SD'S SHOWN ON MORE |
| | THAN ONE CIRCUIT. |
| | PLEASE SEE ALL SD'S ARE REQUIRED TO BE |
| | WIRED "INLINE". THEY CAN NOT BE WIRED |
| | INLINE AND BE ON TWO SEPARATE |
| | PHASES/CIRCUITS. |
| | NEC |
| | |
| | 5)NOTE: PLEASE CORRELATE CIRCUITING ON |
| | PLANS WITH PANEL SCHEDULE. |
| | PLEASE SEE A-21 FOR OVEN ALSO SHOWN FOR |
| | SD'S. |
| | PLEASE SEE OVEN SHOWN ON PLANS AS SPACE? |
| | ETC. |
| | |
| | 6)NOTE: PLEASE LABEL PANEL IN GARAGE. |
| | PLEASE VERIFY PANEL "B WHICH IS SHOWN |
| | NEXT TO METER, BUT BEING FED FROM PANEL |
| | "A" LOCATED INSIDE. |
| | PLEASE ALSO SEE MIN CLEARENCE FOR PANEL |
| | "B". 110.26 |
| | |
| | 7)NOTE: PLEASE VERIFY KW LOAD FOR OVEN. |
| | (THIS IS ONLY A NOTE). |
| | |
| | PLEASE SEE SOME OF THE ABOVE ITEMS HAVE |
| | BEEN REDLINED IN SOME LOCATIONS ON PLANS |
| | FOR ABOVE COMMENTS. |
| | |
| | PLEASE REMOVE ANY OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |