| 2005-05-31 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1- NEED RECORDED NOTICE OF COMMENCEMENT. |
| | |
| | 2- FLOOR PLANS SHOW HANDRAIL ON ONE SIDE |
| | OF STAIRS ONLY. NEED HANDRAIL AT RUN |
| | THAT GOES FROM LANDING TO 2ND FLOOR. |
| | SEC. 1007.5.1 EXCEPTION #3. |
| | |
| | 3- DESIGNER OF RECORD TO SPECIFY ROOF |
| | TILE FASTENING AS REQ'D BY SEC. |
| | 104.2.1.1 CITY AMENDMENTS TO FBC 2001. |
| | |
| | 4- SPECIFY CONTROL JOINTS OR SPECIFY WWM |
| | SUPPORTS AND SPACING AS REQ'D BY SEC. |
| | 1909.3 FBC 2001. |
| | |
| | 5- SPECIFY ROOF SHEATHING NAIL SIZE AND |
| | SPACING. SEE TABLE 2306.1 OF CITY |
| | AMENDMENTS TO FBC 2001 FOR MEAN ROOF |
| | HEIGHT ABOVE 25'-0" FOR ZONES 1,2 AND 3. |
| | |
| | 6- PROVIDE ATTIC ACCESS AT MASTER |
| | BEDROOM WING. SEC. 2309.6 FBC 2001. |
| | |
| | 7- PROVIDE CUT SHEETS FOR 24SH WINDOWS |
| | SHOWING COMPLIANCE WITH MIN. EGRESS |
| | OPENING OF 5.7SF. AS REQUIRED BY SEC. |
| | 1005.4.4 FBC 2001. |
| | NOTE: PRODUCT APPROVAL SUBMITTED DOESN'T |
| | HAVE THIS SIZE WINDOWS. |
| | |
| | 8- REVISE NOTE #3 ON SHEET A-3.1. NEED |
| | 7/8" STUCCO THICKNESS. NO 5/8". SEE ASTM |
| | C-926. |
| | |
| | 9- PROVIDE DETAIL/SPECS FOR CEILING |
| | INSTALLATION AT ENTRY AND REAR PORCH. |
| | SEE ASTM C-926 AND C-1063. SPECIFY |
| | FASTENER SIZE AND SPACING. |
| | |
| | 10- SHEET A-7: A) REVISE STAIR KEY NOTE |
| | #1. HANDRAIL TO BE BETWEEN 34" AND 38" |
| | AS REQ'D BY SEC. 1007.5.1 EXCEPTION #3. |
| | NOTE: HANDRAIL AND GUARDRAIL ARE NOT THE |
| | SAME THING. |
| | |
| | B) SPECIFY MATERIAL AND LOCATION OF |
| | FIREBLOCKING AT STAIRS. ALSO MISSING |
| | FIREBLOCKING AT TOP OF STAIRS. SEC. |
| | 2305.1.4 FBC 2001. |
| | |
| | C) SPECIFY ALL FASTENERS FOR STAIR |
| | FRAMING. SEC. 104.2.1.2 CITY AMENDMENTS |
| | TO FBC 2001. |
| | |
| | 11- PROVIDE CALCULATIONS SHOWING HOW 2 |
| | STORY STRUCTURE ONLY REQUIRES 2000PSF |
| | SOIL BEARING CAPACITY. SEC. 104.2.1.2 |
| | CITY AMMENDMENTS TO FBC 2001. |
| | |
| | 12- THERE ARE 2 GARAGE DOOR BUCK DETAILS |
| | WITH DIFFERENT SPECS.CLARIFY WHICH ONE |
| | APPLIES TO THIS JOB. SEE SHEET A-6 AND |
| | SHEET S-4. |
| | |
| | 13- SPECIFY DRAFSTOPPING LOCATION AND |
| | MATERIAL ON 2ND FLOOR FRAMING PLAN AS |
| | REQ'D BY SEC. 2305.2.2.1 FBC 2001. |
| | |
| | 14- PROVIDE SMOKE DETECTOR AT FIRST |
| | FLOOR IN CLOSE PROXIMITY TO STAIRS. |
| | ELECTRICAL PLAN SHOWS SMOKE DETECTOR ON |
| | FOYER CEILING WHICH IS A DOUBLE VOLUME |
| | CEILING. SEC. 905.2.2 FBC 2001. |
| | |
| | 15- SHEET S-1: A) UPDATE STRUCTURAL |
| | NOTES 2(B) AND 3(A). SEE CHAPTER 19 FOR |
| | PROPER ACI REFERENCE AND CHAPTER 35 FOR |
| | PROPER EDITION. |
| | |
| | B) DETAIL #6 FOR PRIVACY WALL IS FOR |
| | 6'-0" HIGH WALL. FIRST FLOOR PLAN CALLS |
| | FOR 8'-0" HIGH WALL. REVISE AS REQ'D. |
| | |
| | C) FOOTING FOR COLUMN AT REAR PORCH IS |
| | ENCROACHING INTO NEIGHBOR'S PROPERTY AT |
| | ZERO LOT LINE. REVISE AS REQUIRED. |
| | |
| | D) STEEL COLUMN BY AHU #1 CALLS FOR F30 |
| | FOOTING. THERE IS NOT F30 ON FOOTING |
| | SCHEDULE. REVISE AS REQUIRED. |
| | |
| | E) SPECIFY CONNECTORS AT TOP OF ALL WOOD |
| | COLUMNS. SEC. 104.2.1.2 CITY AMENDMENTS |
| | TO FBC 2001. |
| | |
| | F) SOIL STATEMENT. DESIGNER OF RECORD TO |
| | REVIEW SOIL TEST REPORT. THERE IS NO |
| | LIMEROCK. |
| | ALSO, REPORT RECOMMENDS 18" MIN. WIDTH |
| | FOR FOOTINGS. FOOTING M-16 CALLS FOR 16" |
| | WIDTH. SPECIFY IF DESIGNER REVIEWED SOIL |
| | TEST REPORT AND FOOTING RECOMMENDATION |
| | IS NOT REQUIRED. SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | |
| | 16- SHEET S-2: A) FRAMING PLAN CALLS FOR |
| | CONNECTOR #22. WHERE IS IT ON THE TRUSS |
| | CONNECTOR SCHEDULE? |
| | |
| | B) CONNECTOR #5 IS A WOOD TO WOOD |
| | CONNECTOR. NEED WOOD TO MASONRY |
| | CONNECTOR. REVISE AS REQUIRED. |
| | |
| | C) THERE IS OVERLAPPING INFORMATION BY |
| | MASTER BEDROOM ROOF AREA. REVISE. |
| | |
| | D) COLUMN BY STAIRWAY SAYS STEEL COLUMN |
| | DETAIL #38. FOUNDATION PLAN CALLS FOR |
| | WOOD COLUMN. REVISE AS REQUIRED. |
| | |
| | E) SPECIFY CONNECTOR FOR TRUSS GIRDER |
| | ABOVE LAUNDRY AREA. SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | |
| | 17- SHEET S-3: A) CONNECTOR SCHEDULE: |
| | REVISE NUMBER AND TYPE OF NAILS. SEE |
| | LATEST CATALOGUE FOR PROPER NUMBER OF |
| | NAILS. |
| | |
| | B) WHERE IS CONNECTOR #22? |
| | |
| | C) REVISE CONNECTOR #5. NEED WOOD TO |
| | MASONRY CONNECTOR. |
| | |
| | 18- SHEET S-5: A) DETAIL 38. THERE ARE |
| | NOT SPECS FOR SIZE AND NUMBER OF BOLTS. |
| | |
| | B) DETAIL 50: NEED TO SPECIFY WOOD TO |
| | MASONRY STRAPS. SEE CATALOGUE FOR |
| | MASONRY CONNECTORS. |
| | |
| | 19- ENTRY DOOR PRODUCT APPROVAL |
| | SUBMITTED IS FOR 6'-8" DOORS. NEED 8'-0" |
| | HIGH DOORS. |
| | |
| | 20- REVISE ENERGY CALCULATIONS. THERE IS |
| | NOT EXTERIOR FRAMED WALLS. 2ND FLOOR IS |
| | MASONRY TOO. |
| | |
| | 21- SURVEYOR NEED TO SIGN AND DATE |
| | SURVEY AS REQUIRED BY CHAPTER 471 |
| | FLORIDA STATUTES. |
| | |
| | 22- PROVIDE COMPLETE INFORMATION FOR |
| | STORM SHUTTERS OR APPLY FOR A SEPARATE |
| | PERMIT. |
| | |