| 2005-08-31 00:00:00 | SUBMITTAL BUILDING REVIEW CHECKLIST: |
| | 1- SEPARATE PERMIT FOR SHUTTERS HAS NOT |
| | BEEN APPLIED FOR YET. |
| | |
| | 2- ROOF FRAMING PLAN: CONNECTORS NEED TO |
| | BE REVISED AT ENTRY FOYER AREA. TRUSSES |
| | ARE RESTING ON A GIRDER TRUSS, NOT ON A |
| | CONCRETE BEAM. REVISE AS REQUIRED. SEC. |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | |
| | 3- TRUSS ANCHOR SCHEDULE: REVISE NUMBER |
| | OF NAILS SPECIFIED FOR CONNECTOR HUS26. |
| | SEE 2005 CATALOGUE. |
| | |
| | 4- ONE HOUR FIRE RATED DOOR AT ATRIUM |
| | PRODUCT APPROVAL SUBMITTED IS FOR |
| | OUTSWING DOOR. PLANS SHOW INSWING DOOR. |
| | REVISE AS REQUIRED. |
| | ***NOTE: DOOR AT THIS LOCATION NEED NOT |
| | TO BE FIRE RATED. WALL IS NOT LOCATED IN |
| | THE ZERO LOT LINE. BESIDES, THIS WALL IS |
| | MORE LIKE A FENCE NOT A BUILDING WALL. |
| | THEREFORE, TABLE 600 FBC 2001 DOESN'T |
| | APPLY. |
| | |
| | 5- WINDOW MULLION SIZE SPECIFIED FOR |
| | FIXED WINDOWS AT GREAT ROOM DOESN'T |
| | RESIST THE CALCULATED DESIGN PRESSURES. |
| | SEE PRODUCT APPROVAL AND REVISE SIZE AS |
| | REQUIRED. SEC. 104.2.1.2 CITY AMENDMENTS |
| | TO FBC 2001. |
| | |
| | 6- ALL REVISED DRAWINGS WILL BE SUBJECT |
| | TO THE REVISION FEES. SEE THE SUBMITTAL |
| | FORM FOR APPLICABLE FEES. |
| | |
| | 7- PROVIDE FLORIDA OR LOCAL PRODUCT |
| | APPROVAL FOR FRENCH DOORS. SEE PLANS FOR |
| | REQUIRED SIZE. |
| | |