| 2005-08-16 00:00:00 | BUILDING REVISION REVIEW CHECKLIST: |
| | 1- PLANS DON'T SHOW ANY REVISIONS. ONLY |
| | ADDITIONAL DETAILS ARE SHOWN IN SHEET D2 |
| | CLEARLY SPECIFY WHAT ARE THE REVISIONS. |
| | |
| | 2- MISSING FOUNDATION PAGE. |
| | |
| | 3- PROVIDE THE FOLLOWING INFORMATION |
| | REQUSTED ON PROVISO DATED 6-30-05: |
| | |
| | A) APPLY FOR SHUTTERS PERMIT. |
| | |
| | B) REVISE DOOR/WINDOW SCHEDULE. DON'T |
| | MISMATCH DOORS IN WINDOW SCHEDULE. |
| | |
| | C) REVISE DETAIL 5/D1: CONNECTOR HTS20 |
| | CAN'T SUPPORT GIRDER TRUSS. SEC. |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | |
| | D) TRUSS ANCHOR SCHEDULE. UPDATE NAIL |
| | SIZE FOR HUS26. SEE CATALOGUE. |
| | |
| | E) ROOF FRAMING PLAN: REVISE CONNECTORS |
| | SPECIFIED AT ENTRY PORCH TO MATCH |
| | DETAILS 5 AND 6 OF DRAWING D-1. |
| | |
| | F) PROVIDE FLORIDA OR LOCAL PRODUCT |
| | APPROVAL FOR: |
| | * 9'-0" WIDE SLIDING GLASS DOORS. |
| | |
| | **8'-0" HIGH ENTRY DOORS. |
| | |
| | G) SHEET A-5.0 SHEAR VALUES NOTE: |
| | PROVIDE HAND CALCULATIONS. CLARIFY WHY |
| | USING THE TIMBER MANUAL TO CALCULATE |
| | TAPCONS VALUES. WHAT EDITION OF THE |
| | MANUAL WAS USED. SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | |