| 2005-06-30 00:00:00 | BUILDING REVIEW PROVISO: | | | 1-SHUTTERS UNDER A SEPARATE PERMIT. | | | 2-REVISE DOOR/WINDOW SCHEDULE TO MATCH | | | PLANS/ELEVATIONS. INCLUDING SYMBOLS USED | | | 3- DETAIL 5/D-1: CONNECTOR HTS20 CANN'T | | | SUPPORT BEAM. REVISE AS REQUIRED. SEC. | | | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. | | | 4- TRUSS ANCHOR SCHEDULE: UPDATE NAIL | | | SIZE FOR HUS26. SEE CATALOGUE. | | | 5- ROOF FRAMING PLAN: REVISE CONNECTOR | | | SPECIFIED AT ENTRY PORCH TO MATCH | | | DETAILS 5 & 6 OF DRAWING D-1. | | | 6- PROVIDE PRODUCT APPROVAL FOR: | | | A) 9'-0" WIDE SLIDING GLASS DOORS. | | | B) 8'-0" HIGH ENTRY DOORS. | | | 7- SHEET A-5.0 SHEAR VALUES NOTE: | | | A) PROVIDE HAND CALCULATIONS. SECTION | | | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. | | | B) WHY USING TIMBER MANUAL TO CALCULATE | | | TAPCON VALUES AND WHAT EDITION IS USED. |
|