| Plan Review Notes For Permit 05040909 |
| Permit Number |
05040909 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2006-06-16 00:00:00 | ************** UNSAT *********** | | | | | | 1) NOTE: PLEASE SEE 250.52(5) FOR MIN | | | SIZE OF THE GRND ROD. | | | SHOWN AS 6 FT, 8FT MIN. | | | | | | 2) NOTE: PLEASE SEE 424.3B FOR MIN OCP | | | TO BE 125% FOR AHU'S. | | | PLEASE SEE BOTH UNITS INDICATE 10KW, YET | | | THE OCPIS WAY UNDERSIZED. | | | PLEASE ALSO SEE 9.8KW LOAD INDICATED FOR | | | THE CU#1, WHICH SEEMS HIGH FOR THE OCP | | | AS SHOWN. | | | | | | 3) NOTE: PLEASE SEE BACK COVERED PATIO | | | SHALL CONTAIN A MIN LT FIXTURE OF SOME | | | SORT FOR EGRESS. | | | 210.70, LS 101 7.8, CHAPTER 24. | | | | | | 4) NOTE: PLEASE SEE A CIRCUIT #38 IS | | | STILL BEING SHOWN ON PLANS FOR BATH RM , | | | YET PANEL SCHEDULE IS BLANK AT THIS | | | LOCATION. | | | | | | ** SOME OF THESE SAME ITEMS WERE | | | REDLINED ON PREVIOUS PLANS. | | | | | | PLEASE SUBMIT THE ABOVE CORRECTIONS FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW. | | | 561-805-6717 | | | [email protected] |
|