| 2005-05-10 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1- NEED RECORDED NOTICE OF COMMENCEMENT. |
| | |
| | 2- SOIL TEST REPORT RECOMMENDS 18" MIN. |
| | FOOTING WIDTH. FOUNDATION PLAN CALLS FOR |
| | 16" WIDTH. REVISE AS REQUIRED. |
| | |
| | 3- 45 DEGREE WINDOW ON BEDROOM #3 AT |
| | ZERO LOT LINE WALL IS NOT ALLOWED BY |
| | TABLE 600 FBC 2001. NO OPENINGS ALLOWED. |
| | |
| | 4- PROVIDE NOTE ON DEN ROOM STATING THAT |
| | ROOM IS NOT ALLOWED TO BE USED FOR |
| | SLEEPING PURPOSES. OR, PROVIDE COMPLETE |
| | EGRESS REQUIREMENTS INCLUDING RECORDED |
| | EGRESS EASEMENT. |
| | |
| | 5- PROVIDE DETAIL/SPECS FOR CEILING |
| | INSTALLATION AT ENTRY AND REAR PORCHES. |
| | SPECIFY FASTENERS TYPE AND SPACING . SEE |
| | SEC. 2504.2 FBC 2001. |
| | |
| | 6- SPECIFY SUPPORTS AND SPACING FOR WWM |
| | IN CONCRETE SLAB. SEE EXCEPTION IN SEC. |
| | 1909.3 FBC 2001. |
| | |
| | 7- SPECIFY FOOTINGS FOR ENTRY COLUMNS. |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| | |
| | 8- SHEET A-5.0:A) ROOF NAILING ZONE |
| | DIAPHRAGM IS MISSING ZONE 3. SEE FIGURE |
| | 1606.2(C) FBC 2001. |
| | |
| | B) DETAIL 3 SPECIFIES HGUS 28-2 SIMPSON |
| | CONNECTOR IS A WOOD TO WOOD CONNECTOR. |
| | NEED TO SPECIFY CIFY WOOD TO MASONRY |
| | CONNECTOR. REVISE AS REQUIRED. |
| | |
| | C) DETAILS 1 AND 2: REVISE TYPE OF |
| | NAILS. SEE SIMPSON CATALOGUE. |
| | |
| | D) REVISE CONNECTOR SPECIFIED AT ENTRY |
| | PORCH. NEED MASONRY CONNECTOR. SEE |
| | DETAIL 5/D-1. |
| | |
| | 9- REVISE/UPDATE TRUSS ANCHOR SCHEDULE. |
| | SEE LATEST CATALOGUE THAT WAS REVISED TO |
| | COMPLY WITH SEC. 1609.4.3 FBC 2001. |
| | PROVIDE COMPLETE ENGINEERING CALCS FOR |
| | TYPE AND NUMBER OF NAILS THAT DIFFER |
| | FROM THOSE TESTED AND PUBLISHED BY THE |
| | MANUFACTURER. SECTION 104.2.1.2 OF CITY |
| | AMENDMENTS TO FBC 2001. |
| | |
| | 10- A)RIGHT SIDE ELEVATION DOESN'T MATCH |
| | PLANS. BATHROOM #2 HAS GLASS BLOCK NOT |
| | WINDOW. |
| | |
| | B) SHOW GLASS BLOCK ON LEFT ELEVATION TO |
| | MATCH PLAN. |
| | |
| | 11- CLARIFY IF USING STORM SHUTTERS OR |
| | IMPACT GLAZING. THEN, PROVIDE COMPLETE |
| | INFORMATION FOR EITHER METHOD. |
| | |
| | 12- PROVIDE FLORIDA/LOCAL PRODUCT |
| | APPROVAL FOR:A) ONE HOUR FIRE RATED |
| | ASSEMBLY AT EMERGENCY EGRESS OPENING. |
| | |
| | B) SLIDING GLASS DOORS. DRAWINGS |
| | SUBMITTED DON'T MATCH DADE COUNTY NOA |
| | SUBMITTED. |
| | |
| | C) PROVIDE PRODUCT APPROVAL FOR 12'-0" |
| | WIDE SLIDING GLASS DOORS. SEE PLANS. |
| | |
| | D) LARGE FIXED WINDOWS AS SHOWN ON GREAT |
| | ROOM. PRODUCT APPROVAL SUBMITTED DOESN'T |
| | COVER THOSE SIZES. |
| | |
| | E) ENTRY DOORS. DRAWINGS SUBMITTED ARE |
| | FOR 6'-8" HIGH DOORS. SEE PLANS. |
| | |
| | F) TRUSS CONNECTORS SPECIFIED ON PLANS. |
| | AFTER CORRECTIONS TO SPECIFY PROPER |
| | ANCHORS ARE DONE ON PLANS. |
| | |
| | 13- SHEET D-1:A) CONNECTORS CS-16 X |
| | AND HTS-20 SHOWN ON DETAILS 3, 4 AND 5 |
| | ARE WOOD TO WOOD CONNECTORS. NEED TO |
| | SPECIFY MASONRY CONNECTORS. SEE |
| | CATALOGUE AND REVISE AS REQUIRED. SEC. |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | |
| | B) REVISE TYPE AND NUMBER OF NAILS FOR |
| | HUS26 CONNECTOR. SEE CATALOGUE. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ AT (561)805-6712. |