| Plan Review Notes For Permit 05040907 |
| Permit Number |
05040907 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2005-08-31 00:00:00 | SUBMITTAL BUILDING REVIEW CHECKLIST: | | | 1- SEPARATE PERMIT FOR SHUTTERS HAS NOT | | | BEEN APPLIED FOR YET. | | | | | | 2- REVISE DETAIL 5/D-1 TO MATCH ACTUAL | | | CONDITIONS SHOWN ON ROOF FRAMING PLAN. | | | TRUSSES ARE PARALLEL TO CONCRETE WALL | | | NOT PERPENDICULAR. THEN, SPECIFY | | | CONNECTOR FOR GIRDER TRUSS THAT IS | | | CARRYING THE OTHER TRUSSES. SEE ROOF | | | FRAMING PLAN AND REVISE AS REQUIRED. | | | ***NOTE: BY REVISING DETAIL WILL CLARIFY | | | THAT CONNECTOR HTS20 IS NOT ADEQUATE TO | | | SUPPORT THE GIRDER TRUSS. SPECIFY THE | | | CALCULATED UPLIFT LOADS FOR THIS GIRDER | | | TRUSS AT THE END SUPPORTED ON THE WOOD | | | LEDGER.SECTION 104.2.1.2 CITY | | | AMENDMENTS TO FBC 2001. | | | | | | 3- ALL REVISED DRAWINGS WILL BE SUBJECT | | | TO THE REVISION FEES. SEE THE SUBMITTAL | | | FORM FOR APPLICABLE FEES. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ AT (561)805-6712. |
|